Plan Review Notes
Plan Review Notes For Permit 07071001
Permit Number 07071001
Review Stop P
Sequence Number 2
Notes
Date Text
2007-12-05 15:43:27DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 EXISTING BUILDING CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. ARCHITECTURAL SHEETS. THE PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT SHALL BE INDICATED IN THE TITLE
 BLOCK PER FAC 61G1-16.004(6) & FS 481.2055.
 ****RESPONSE NOTED, BUT DOES NOT ADDRESS THE COMMENT
 FOR THE PRINTED NAME OF THE PERSON SEALING THE DOCUMENT
 ON THE ARCHITECTURAL SHEETS.
  
 2. OK
  
 3. TABLE 403.1 REQUIRES A DRINKING FOUNTAIN. PLEASE
 INDICATE THE LOCATION OF THE DRINKING FOUNTAIN AND
 SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION 11-4.15
 AND ALL SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
 ****RESPONSE NOTED, BUT SECTION 11-4.1.3(10)(A) HAS NOT
 BEEN ADDRESSED.
  
 4. OK
  
 5. SHT A-2DETAIL 1/A-2, THE TOILET ROOM SHALL BE
 ACCESSIBLE PER SECTION 806.1 OF THE EXISTING BUILDING
 CODE. SUBMIT DETAILS/ELEVATIONS SHOWING COMPLIANCE WITH
 SECTION 11-4.22 & ALL SUBSECTIONS.
 ****RESPONSE NOTED, BUT THE FOLLOWING HAS NOT BEEN
 ADDRESSED:
 ___FOR THE W/C:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.5 FLUSH CONTROLS
 ___FOR THE URINAL:
 A. 11-4.18.3 CLEAR FLOOR SPACE
 B. 11-4.18.4 FLUSH CONTROLS
 ___FOR THE LAV:
 A. 11-4.19.3 CLEAR FLOOR SPACE
 B. 11-4.19.5 FAUCETS
 (NOTE: THE DOOR SHALL NOT SWING INTO THE CLEAR FLOOR
 SPACE REQUIRED FOR ANY FIXTURE).
  
 6. OK
 7. OK
 8. OK
 9. OK
 10. OK
  
 11. SHT MP-1 NOTES FOR GREASE INTERCEPTOR: NOTE 6.
 GREASE INTERCEPTORS ARE TO BE SIZED BY ENVIRONMENTAL
 COMPLIANCE SECTION OF THE UTILITY DEPT. PLEASE CONTACT
 RODNEY COMPO, (561) 822-2272, E-MAIL [email protected], OR
 CALVIN WILLIAMS, (561) 822-2284, E-MAIL
 [email protected]. THEIR FAX NUMBER IS (561) 822-2287.
 A WRITTEN VERIFICATION FROM ENVIRONMENTAL COMPLIANCE
 SHALL BE SUBMITTED WITH PLANS FOR GREASE INTERCEPTOR
 APPROVAL.
 ****RESPONSE NOTED, BUT NO WRITTEN DOCUMENTATION
 SUBMITTED.
  
 12. OK
 13. OK
 14. OK
 15. OK
 16. OK
  
 ********NEW COMMENTS**********
 (MISSED THE GAS REVIEW THE FIRST TIME THROUGH)
  
 1B. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE
 FOLLOWING INFORMATION:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. RISER DOES NOT SHOW THE CUT LENGTH
 SECTIONS, NOR DOES IT REFLECT THE FLOOR PLAN.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). (TO BE VERIFIED WHEN
 COMMENT A IS SUBMITTED).
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 H. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 I. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 J. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,IDENTIFYING THE
 SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]