Text |
| 2007-12-05 15:43:27 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FBC-2004 EXISTING BUILDING CODE |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. ARCHITECTURAL SHEETS. THE PRINTED NAME OF THE PERSON |
| | SEALING THE DOCUMENT SHALL BE INDICATED IN THE TITLE |
| | BLOCK PER FAC 61G1-16.004(6) & FS 481.2055. |
| | ****RESPONSE NOTED, BUT DOES NOT ADDRESS THE COMMENT |
| | FOR THE PRINTED NAME OF THE PERSON SEALING THE DOCUMENT |
| | ON THE ARCHITECTURAL SHEETS. |
| | |
| | 2. OK |
| | |
| | 3. TABLE 403.1 REQUIRES A DRINKING FOUNTAIN. PLEASE |
| | INDICATE THE LOCATION OF THE DRINKING FOUNTAIN AND |
| | SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION 11-4.15 |
| | AND ALL SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A) |
| | PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR |
| | STOOPING. |
| | ****RESPONSE NOTED, BUT SECTION 11-4.1.3(10)(A) HAS NOT |
| | BEEN ADDRESSED. |
| | |
| | 4. OK |
| | |
| | 5. SHT A-2DETAIL 1/A-2, THE TOILET ROOM SHALL BE |
| | ACCESSIBLE PER SECTION 806.1 OF THE EXISTING BUILDING |
| | CODE. SUBMIT DETAILS/ELEVATIONS SHOWING COMPLIANCE WITH |
| | SECTION 11-4.22 & ALL SUBSECTIONS. |
| | ****RESPONSE NOTED, BUT THE FOLLOWING HAS NOT BEEN |
| | ADDRESSED: |
| | ___FOR THE W/C: |
| | A. 11-4.16.2 CLEAR FLOOR SPACE |
| | B. 11-4.16.5 FLUSH CONTROLS |
| | ___FOR THE URINAL: |
| | A. 11-4.18.3 CLEAR FLOOR SPACE |
| | B. 11-4.18.4 FLUSH CONTROLS |
| | ___FOR THE LAV: |
| | A. 11-4.19.3 CLEAR FLOOR SPACE |
| | B. 11-4.19.5 FAUCETS |
| | (NOTE: THE DOOR SHALL NOT SWING INTO THE CLEAR FLOOR |
| | SPACE REQUIRED FOR ANY FIXTURE). |
| | |
| | 6. OK |
| | 7. OK |
| | 8. OK |
| | 9. OK |
| | 10. OK |
| | |
| | 11. SHT MP-1 NOTES FOR GREASE INTERCEPTOR: NOTE 6. |
| | GREASE INTERCEPTORS ARE TO BE SIZED BY ENVIRONMENTAL |
| | COMPLIANCE SECTION OF THE UTILITY DEPT. PLEASE CONTACT |
| | RODNEY COMPO, (561) 822-2272, E-MAIL [email protected], OR |
| | CALVIN WILLIAMS, (561) 822-2284, E-MAIL |
| | [email protected]. THEIR FAX NUMBER IS (561) 822-2287. |
| | A WRITTEN VERIFICATION FROM ENVIRONMENTAL COMPLIANCE |
| | SHALL BE SUBMITTED WITH PLANS FOR GREASE INTERCEPTOR |
| | APPROVAL. |
| | ****RESPONSE NOTED, BUT NO WRITTEN DOCUMENTATION |
| | SUBMITTED. |
| | |
| | 12. OK |
| | 13. OK |
| | 14. OK |
| | 15. OK |
| | 16. OK |
| | |
| | ********NEW COMMENTS********** |
| | (MISSED THE GAS REVIEW THE FIRST TIME THROUGH) |
| | |
| | 1B. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE |
| | FOLLOWING INFORMATION: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. RISER DOES NOT SHOW THE CUT LENGTH |
| | SECTIONS, NOR DOES IT REFLECT THE FLOOR PLAN. |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | |
| | C. TYPE OF GAS, (LP OR NATURAL). |
| | |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33).4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| | BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | |
| | 4. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33).4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| | BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). (TO BE VERIFIED WHEN |
| | COMMENT A IS SUBMITTED). |
| | |
| | F. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | |
| | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | H. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | |
| | I. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| | PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | |
| | J. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE,IDENTIFYING THE |
| | SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |