2007-12-03 10:49:46REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. OK
  
 2. OK
  
 3. PREVIOUS COMMENT REQUESTED OUTSIDE AIR CALCULATIONS
 FOR ALL AREAS, NOT JUST CUSTOMER AREA. KITCHEN AREA AND
 2ND FLOOR AREA CALCULATIONS ARE ALSO REQUIRED.
 NOTE: 2ND FLOOR AREA IS PART OF LEVEL 2 ALTERATION AS
 THERE ARE WINDOW OPENINGS BEING CLOSED. LEVEL 2
 ALTERATIONS INCLUDE THE RECONFIGURATION OF SPACE, THE
 ADDITION OR ELIMINATION OF ANY DOOR OR WINDOW PER FBC,
 EB 304.1. SHOW HOW OUTSIDE AIR REQUIREMENTS FOR THESE
 AREAS ARE TO BE MET IN ACCORDANCE WITH FBC, M 403.3.
  
 4. OK. VENTING INSTALLATION INSTRUCTIONS REQUIRED ON
 SITE FOR INSPECTION.
  
 5. RUSKIN SUBMITTAL FOUND IN PACKAGE. PRODUCT APPROVAL
 OR NOA WAS NOT PROVIDED IN PACKAGE. THE NOA FOR THIS
 LOUVER WAS PRINTED BY THIS OFFICE AND ADDED TO THE
 PACKAGE. THIS WILL NOT BE DONE IN THE FUTURE. THIS
 INFORMATION SHALL BE PROVIDED BY THE DESIGNER OR
 CONTRACTOR.
  
 6. OK
  
 7. OK
  
 8. OK. SEE COMMENT 3 ABOVE REGARDING 2ND FLOOR.
  
 NEW COMMENTS:
 THE FOLLOWING COMMENTS HAVE BEEN GENERATED AS A RESULT
 OF CHANGES TO THE PLANS AND/OR NEW INFORMATION WHICH
 WAS NOT PART OF PREVIOUS SUBMITTAL.
  
 A. DETAIL #2 ON MP-1 SHOWS TWO ROOF CONDENSERS SITTING
 ON CONCRETE PADS. HAS THERE BEEN AN ENGINEERING
 ANALYSIS OF THE ROOF FRAMING TO VERIFY THAT IT IS
 SUITABLE FOR THE ADDITIONAL DEAD LOADS OF THE EQUIPMENT
 AND SIZEABLE 4 INCH THICK CONCRETE PADS?
  
 B. THERE IS NO DETAIL FOR HOW THE CONDENSING UNITS ARE
 TO BE FASTENED TO THE CONCRETE PADS TO MEET 140 MPH
 WIND LOADS IN ACCORDANCE WITH FBC, M 301.13 AND FBC
 1609. PLEASE NOTE THAT THE PRESCRIPTIVE METHOD SHOWN IN
 FBC, M 301.13.1 IS FOR R-3 OCCUPANCY ONLY. ENGINEERING
 IS REQUIRED.
  
 C. PG S-3 SHOWS A CONNECTION DETAIL FOR ROOFTOP
 CONDENSERS WHICH IS IN CONFLICT WITH DETAIL #2 ON MP-1.
 WHICH METHOD IS TO BE USED? ALSO, DETAIL ON S-3 REFERS
 TO A PRODUCT APPROVAL FOR AN A/C STAND. NO SUCH PRODUCT
 APPROVAL WAS FOUND IN THE SUBMITTAL PACKAGE FOR THIS
 PERMIT. DETERMINE WHICH METHOD IS TO BE USED AND
 PROVIDE ALL REQUIRED DOCUMENTATION TO SHOW COMPLIANCE
 WITH THESE SECTIONS.
  
 NOTE: DOCUMENTATION FOR TYPE I KITCHEN HOOD AND DUCT
 SYSTEM HAVE NOT BEEN PROVIDED. FULL DOCUMENTATION FOR
 HOOD PERMIT WILL BE REQUIRED.