| Date |
Text |
| 2007-12-03 10:49:46 | REVIEW #: 2ND |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| | RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| | |
| | 1. OK |
| | |
| | 2. OK |
| | |
| | 3. PREVIOUS COMMENT REQUESTED OUTSIDE AIR CALCULATIONS |
| | FOR ALL AREAS, NOT JUST CUSTOMER AREA. KITCHEN AREA AND |
| | 2ND FLOOR AREA CALCULATIONS ARE ALSO REQUIRED. |
| | NOTE: 2ND FLOOR AREA IS PART OF LEVEL 2 ALTERATION AS |
| | THERE ARE WINDOW OPENINGS BEING CLOSED. LEVEL 2 |
| | ALTERATIONS INCLUDE THE RECONFIGURATION OF SPACE, THE |
| | ADDITION OR ELIMINATION OF ANY DOOR OR WINDOW PER FBC, |
| | EB 304.1. SHOW HOW OUTSIDE AIR REQUIREMENTS FOR THESE |
| | AREAS ARE TO BE MET IN ACCORDANCE WITH FBC, M 403.3. |
| | |
| | 4. OK. VENTING INSTALLATION INSTRUCTIONS REQUIRED ON |
| | SITE FOR INSPECTION. |
| | |
| | 5. RUSKIN SUBMITTAL FOUND IN PACKAGE. PRODUCT APPROVAL |
| | OR NOA WAS NOT PROVIDED IN PACKAGE. THE NOA FOR THIS |
| | LOUVER WAS PRINTED BY THIS OFFICE AND ADDED TO THE |
| | PACKAGE. THIS WILL NOT BE DONE IN THE FUTURE. THIS |
| | INFORMATION SHALL BE PROVIDED BY THE DESIGNER OR |
| | CONTRACTOR. |
| | |
| | 6. OK |
| | |
| | 7. OK |
| | |
| | 8. OK. SEE COMMENT 3 ABOVE REGARDING 2ND FLOOR. |
| | |
| | NEW COMMENTS: |
| | THE FOLLOWING COMMENTS HAVE BEEN GENERATED AS A RESULT |
| | OF CHANGES TO THE PLANS AND/OR NEW INFORMATION WHICH |
| | WAS NOT PART OF PREVIOUS SUBMITTAL. |
| | |
| | A. DETAIL #2 ON MP-1 SHOWS TWO ROOF CONDENSERS SITTING |
| | ON CONCRETE PADS. HAS THERE BEEN AN ENGINEERING |
| | ANALYSIS OF THE ROOF FRAMING TO VERIFY THAT IT IS |
| | SUITABLE FOR THE ADDITIONAL DEAD LOADS OF THE EQUIPMENT |
| | AND SIZEABLE 4 INCH THICK CONCRETE PADS? |
| | |
| | B. THERE IS NO DETAIL FOR HOW THE CONDENSING UNITS ARE |
| | TO BE FASTENED TO THE CONCRETE PADS TO MEET 140 MPH |
| | WIND LOADS IN ACCORDANCE WITH FBC, M 301.13 AND FBC |
| | 1609. PLEASE NOTE THAT THE PRESCRIPTIVE METHOD SHOWN IN |
| | FBC, M 301.13.1 IS FOR R-3 OCCUPANCY ONLY. ENGINEERING |
| | IS REQUIRED. |
| | |
| | C. PG S-3 SHOWS A CONNECTION DETAIL FOR ROOFTOP |
| | CONDENSERS WHICH IS IN CONFLICT WITH DETAIL #2 ON MP-1. |
| | WHICH METHOD IS TO BE USED? ALSO, DETAIL ON S-3 REFERS |
| | TO A PRODUCT APPROVAL FOR AN A/C STAND. NO SUCH PRODUCT |
| | APPROVAL WAS FOUND IN THE SUBMITTAL PACKAGE FOR THIS |
| | PERMIT. DETERMINE WHICH METHOD IS TO BE USED AND |
| | PROVIDE ALL REQUIRED DOCUMENTATION TO SHOW COMPLIANCE |
| | WITH THESE SECTIONS. |
| | |
| | NOTE: DOCUMENTATION FOR TYPE I KITCHEN HOOD AND DUCT |
| | SYSTEM HAVE NOT BEEN PROVIDED. FULL DOCUMENTATION FOR |
| | HOOD PERMIT WILL BE REQUIRED. |