2008-02-25 14:10:54DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 ******FROM PREVIOUS REVIEW:
  
 ********NEW COMMENTS**********
 (MISSED THE GAS REVIEW THE FIRST TIME THROUGH)
  
 1B. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE
 FOLLOWING INFORMATION:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. RISER DOES NOT SHOW THE CUT LENGTH
 SECTIONS, NOR DOES IT REFLECT THE FLOOR PLAN.
 ******RESPONSE NOTED, BUT THE RISER STILL DOES NOT
 REFLECT THE FLOOR PLAN, NOR DOES THE RISER SHOW ALL THE
 CUT LENGTH SECTIONS. SEE THE SECTIONS THAT COME OFF THE
 METER VERTICALLY, TURN HORIZONTAL, DROP DOWN
 UNDERGROUND THEN TURN HORIZONTAL. ALSO THE SECTIONS OF
 PIPE THAT TURNS TOWARD THE BUILDING, UP PAST THE SHUT
 OFF VALVE, HORIZONTALL, THEN DROPS DOWN TO 4 FEET ABOVE
 THE FLOOR FOR THE KITCHEN APPLIANCES. ALSO SEE THE CUT
 SECTIONS OFF THE MAIN TO THE DOUBLE RACH OVEN AND THE
 CUT SECTIONS TO THE WATER HEATER.
  
 B. OK
 C. OK
 D. OK
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). (TO BE VERIFIED WHEN
 COMMENT A IS SUBMITTED).
 ******RESPONSE NOTED, BUT AS INDICATED IN THE LAST
 REVIEW, THIS WILL BE VERIFIED WHEN ALL CUT SECTIONS ARE
 GIVEN FOR COMMENT "A".
  
 F. OK
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ******RESPONSE NOTED, BUT NO MANUFACTURE SHEETS WERE
 SUBMITTED FOR THE STEAMER OR THE WATER HEATER.
  
 H. N/A
 I. N/A
  
 J. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ******RESPONSE NOTED, BUT AN EMERGENCY HOOD SHUT DOWN
 SHUT OFF VALVE IS REQUIRED AS WELL AS A UNION EITHER
 BETEWEEN THE SHUT OFF VALVE AND THE EMERGNECY HOOD SHUT
 OFF VALVE OR DOWN STREAM OF THE EMERGENCY SHUT OFF
 VALVE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  