Plan Review Notes
Plan Review Notes For Permit 07071001
Permit Number 07071001
Review Stop E
Sequence Number 2
Notes
Date Text
2007-11-26 09:33:43** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW STILL
 NEED TO BE ADDRESSED ALONG WITH SOME NEW COMMENTS DUE
 TO CHANGES ON PLANS.
 NOTE FROM PREVIOUS REVIEW MENTIONED THERE MAY BE NEW
 COMMENTS AS THERE WAS INFORMATION NOT SUBMITTED FOR
 REVIEW.
  
 1) NOTE: PLEASE SEE NOTE #1 FROM PREVIOUS REVIEW WHICH
 REQUESTED THE CODES ON ELECTRICAL PLANS.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** IT WAS NOTED THAT THESE WERE ADDED TO A-1, HOWEVER
 NEEDS TO BE ON ELECTRICAL PLANS ALSO.
  
  
 2) NOTE: PLEASE SEE PREVIOUS NOTE #2 AS THE LIGHTING
 PERFORMANCE CALCULATIONS FOR INTERIOR AND EXTERIOR ARE
 NOT COMPLETE.
 PLEASE SEE NO INFORMATION WAS SHOWN FOR EXTERIOR AND
 THE INFORMATION FOR INTERIOR CAN NOT BE VERIFIED AS THE
 FIXTURE LEGEND IS NOT COMPLETE WITH FIXTURE
 INFORMATION.
 PREVIOUSLY SUBMITTED METHOD *A* AND NOW SUBMITTING
 *C*.
 PLEASE SEE 13-415.1.A, 13-415.2, 13-415.2.ABC.1.2,
 13-415.2.ABC.1.3, 13-415.2.ABC.1.1
  
 3) NOTE: PLEASE PROVIDE NOTES ON PLANS PER
 13-413.1.ABC.2.1, .2.2
  
 4) NOTE: PLEASE SEE THE PLANS STILL SHOW A *J-BOX* FOR
 FUTURE GENERATOR YET NO INFORMATION WAS LOCATED ON
 RISER OR PLANS. HOW WILL TRANSFER TAKE PLACE:? HOW WILL
 THIS CONNECTION BE MADE?
 PLEASE PROVIDE MORE INFORMATION.
 702.6, 110.3, 90.7
 FBC 106.1.2
  
 5) NOTE: PLEASE CLARIFY WHERE AND HOW LOADS WERE
 FIGURED FOR SHOW WINDOWS. PLEASE BE SURE TO ADJUST LOAD
 CALCULATIONS PER 220.43
  
 6) NOTE: PLEASE SEE RISER NOW SHOWS *EQUIPMENT
 GROUNDING CONDUCTORS* FROM METER TO THE FIRST MEANS OF
 DISCONNECT.
 PLEASE SEE 250.6, 250.24 AS THIS IS NOT PERMITTED.
 EQUIPMENT GROUNDING CONDUCTORS ARE ONLY INSTALLED AFTER
 THE FIRST MEANS OF DISCONNECTS.
  
 7) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR STAIR AREAS
 UNDER NORMAL AND UNDER EMERGENCY. RESPONSE FROM
 ARCHITECT MENTIONS TO SEE FBC 1006.1.1 EXCEPT #4,
 HOWEVER PLEASE SEE THE LATEST CODE AS THIS SECTION
 COULD NOT BE FOUND. PLEASE KNOW IN EITHER CASE AS THE
 LIFE SAFETY CODE AND FLORIDA ADMINISTRATIVE CODE IS
 MORE RESTRICTIVE, PLEASE SUBMIT AS PREVIOUSLY
 REQUESTED. THESE ARE REQUIRED. FAC 61G15-33.004
 PLEASE SEE THAT THIS NEEDS TO INCLUDE THE EXTERIOR
 STAIR TO THE PUBLIC RIGHT OF WAY. PLEASE PROVIDE
 LIGHTING FIXTURES AND ALSO BATTERY BACK UP AS REQUIRED
 UNDER THE MINIMUM REQUIREMENTS OF THE LIFE SAFETY
 CODE.
 PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.2
  
 8) NOTE: PLEASE SEE AS ELECTRICAL FOR SECOND FLOOR IS
 NOW BEING SUBMITTED AND SHOWN, PLEASE CLARIFY WHAT IS
 NEW AND WHAT IS EXISTS? PLANS CONTAIN A NOTE WHICH
 MENTIONS *ALL* IS EXISTING, YET THIS IS NOT POSSIBLE
 WHEN THERE ARE NEW STAIRS AND NEW RECEPTACLES BEING
 INSTALLED.THE ORIGINAL STAIR LOCATION IS NOT THE SAME
 AND THE FLOOR LOCATION IS BEING CLOSED. PLEASE INDICATE
 NEW AND EXISTING.
 10) NOTE: PLEASE SEE HAND DRAWN CHANGES ON PLANS ARE
 NOT PERMITTED. PLEASE BE SURE TO MAKE CHANGES ON
 REVISED PLANS.
 FBC 106.3.
  
 11) NOTE: PLEASE SUBMIT ELECTRICAL FOR SITE
 LIGHTING/LANDSCAPE AS PREVIOUSLY NOTED. RESPONSE
 MENTIONS CIRCUIT PROVIDE, HOWEVER AS NOTED ABOVE FOR
 FBC CHAPTER 13 AND ELECTRICAL FOR FIXTURES, OVER
 CURRENT PROTECTION ETC, NOT ENOUGH INFORMATION IS
 SHOWN.
 FIXTURE LOCATIONS ETC.
 FBC 106.1.2, 106.3.5.1.2
 NEC240.4, 310.16,
  
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  