| 2007-11-26 09:33:43 | ** DENIED 2ND REVIEW ** |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW STILL |
| | NEED TO BE ADDRESSED ALONG WITH SOME NEW COMMENTS DUE |
| | TO CHANGES ON PLANS. |
| | NOTE FROM PREVIOUS REVIEW MENTIONED THERE MAY BE NEW |
| | COMMENTS AS THERE WAS INFORMATION NOT SUBMITTED FOR |
| | REVIEW. |
| | |
| | 1) NOTE: PLEASE SEE NOTE #1 FROM PREVIOUS REVIEW WHICH |
| | REQUESTED THE CODES ON ELECTRICAL PLANS. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | ** IT WAS NOTED THAT THESE WERE ADDED TO A-1, HOWEVER |
| | NEEDS TO BE ON ELECTRICAL PLANS ALSO. |
| | |
| | |
| | 2) NOTE: PLEASE SEE PREVIOUS NOTE #2 AS THE LIGHTING |
| | PERFORMANCE CALCULATIONS FOR INTERIOR AND EXTERIOR ARE |
| | NOT COMPLETE. |
| | PLEASE SEE NO INFORMATION WAS SHOWN FOR EXTERIOR AND |
| | THE INFORMATION FOR INTERIOR CAN NOT BE VERIFIED AS THE |
| | FIXTURE LEGEND IS NOT COMPLETE WITH FIXTURE |
| | INFORMATION. |
| | PREVIOUSLY SUBMITTED METHOD *A* AND NOW SUBMITTING |
| | *C*. |
| | PLEASE SEE 13-415.1.A, 13-415.2, 13-415.2.ABC.1.2, |
| | 13-415.2.ABC.1.3, 13-415.2.ABC.1.1 |
| | |
| | 3) NOTE: PLEASE PROVIDE NOTES ON PLANS PER |
| | 13-413.1.ABC.2.1, .2.2 |
| | |
| | 4) NOTE: PLEASE SEE THE PLANS STILL SHOW A *J-BOX* FOR |
| | FUTURE GENERATOR YET NO INFORMATION WAS LOCATED ON |
| | RISER OR PLANS. HOW WILL TRANSFER TAKE PLACE:? HOW WILL |
| | THIS CONNECTION BE MADE? |
| | PLEASE PROVIDE MORE INFORMATION. |
| | 702.6, 110.3, 90.7 |
| | FBC 106.1.2 |
| | |
| | 5) NOTE: PLEASE CLARIFY WHERE AND HOW LOADS WERE |
| | FIGURED FOR SHOW WINDOWS. PLEASE BE SURE TO ADJUST LOAD |
| | CALCULATIONS PER 220.43 |
| | |
| | 6) NOTE: PLEASE SEE RISER NOW SHOWS *EQUIPMENT |
| | GROUNDING CONDUCTORS* FROM METER TO THE FIRST MEANS OF |
| | DISCONNECT. |
| | PLEASE SEE 250.6, 250.24 AS THIS IS NOT PERMITTED. |
| | EQUIPMENT GROUNDING CONDUCTORS ARE ONLY INSTALLED AFTER |
| | THE FIRST MEANS OF DISCONNECTS. |
| | |
| | 7) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR STAIR AREAS |
| | UNDER NORMAL AND UNDER EMERGENCY. RESPONSE FROM |
| | ARCHITECT MENTIONS TO SEE FBC 1006.1.1 EXCEPT #4, |
| | HOWEVER PLEASE SEE THE LATEST CODE AS THIS SECTION |
| | COULD NOT BE FOUND. PLEASE KNOW IN EITHER CASE AS THE |
| | LIFE SAFETY CODE AND FLORIDA ADMINISTRATIVE CODE IS |
| | MORE RESTRICTIVE, PLEASE SUBMIT AS PREVIOUSLY |
| | REQUESTED. THESE ARE REQUIRED. FAC 61G15-33.004 |
| | PLEASE SEE THAT THIS NEEDS TO INCLUDE THE EXTERIOR |
| | STAIR TO THE PUBLIC RIGHT OF WAY. PLEASE PROVIDE |
| | LIGHTING FIXTURES AND ALSO BATTERY BACK UP AS REQUIRED |
| | UNDER THE MINIMUM REQUIREMENTS OF THE LIFE SAFETY |
| | CODE. |
| | PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.2 |
| | |
| | 8) NOTE: PLEASE SEE AS ELECTRICAL FOR SECOND FLOOR IS |
| | NOW BEING SUBMITTED AND SHOWN, PLEASE CLARIFY WHAT IS |
| | NEW AND WHAT IS EXISTS? PLANS CONTAIN A NOTE WHICH |
| | MENTIONS *ALL* IS EXISTING, YET THIS IS NOT POSSIBLE |
| | WHEN THERE ARE NEW STAIRS AND NEW RECEPTACLES BEING |
| | INSTALLED.THE ORIGINAL STAIR LOCATION IS NOT THE SAME |
| | AND THE FLOOR LOCATION IS BEING CLOSED. PLEASE INDICATE |
| | NEW AND EXISTING. |
| | 10) NOTE: PLEASE SEE HAND DRAWN CHANGES ON PLANS ARE |
| | NOT PERMITTED. PLEASE BE SURE TO MAKE CHANGES ON |
| | REVISED PLANS. |
| | FBC 106.3. |
| | |
| | 11) NOTE: PLEASE SUBMIT ELECTRICAL FOR SITE |
| | LIGHTING/LANDSCAPE AS PREVIOUSLY NOTED. RESPONSE |
| | MENTIONS CIRCUIT PROVIDE, HOWEVER AS NOTED ABOVE FOR |
| | FBC CHAPTER 13 AND ELECTRICAL FOR FIXTURES, OVER |
| | CURRENT PROTECTION ETC, NOT ENOUGH INFORMATION IS |
| | SHOWN. |
| | FIXTURE LOCATIONS ETC. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | NEC240.4, 310.16, |
| | |
| | |
| | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |