Plan Review Notes
Plan Review Notes For Permit 07071001
Permit Number 07071001
Review Stop P
Sequence Number 1
Notes
Date Text
2007-09-07 17:07:53DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 EXISTING BUILDING CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ARCHITECTURAL SHEETS. THE PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT SHALL BE INDICATED IN THE TITLE
 BLOCK PER FAC 61G1-16.004(6) & FS 481.2055.
  
 2. SHT A-2 DETAIL 1/A-2 CUSTOMERS, PATRONS & VISITORS
 SHALL BE PROVIDED WITH PUBLIC TOILET FACILITIES IN
 STRUCTURES & TENANT SPACES INTENDED FOR PUBLIC
 UTILIZATION. PLEASE PROVIDE TOILET FACILITIES. SECTION
 403.6.
  
 3. TABLE 403.1 REQUIRES A DRINKING FOUNTAIN. PLEASE
 INDICATE THE LOCATION OF THE DRINKING FOUNTAIN AND
 SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION 11-4.15
 AND ALL SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
  
 4. INDICATE THE ALTERATION LEVEL PER SECTIONS 303, 304
 OR 305 OF THE EXISTING BUILDING CODE.
  
 5. SHT A-2DETAIL 1/A-2, THE TOILET ROOM SHALL BE
 ACCESSIBLE PER SECTION 806.1 OF THE EXISTING BUILDING
 CODE. SUBMIT DETAILS/ELEVATIONS SHOWING COMPLIANCE WITH
 SECTION 11-4.22 & ALL SUBSECTIONS.
  
 6. SHT A-2DETAIL 2/A-2 THE BATHROOM, (RM 201), SHALL
 BE ACCESSIBLE. PER SECTION 806.1 OF THE EXISTING
 BUILDING CODE. SUBMIT DETAILS/ELEVATIONS SHOWING
 COMPLIANCE WITH SECTION 11-4.23 AND ALL SUBSECTIONS.
  
 7. SUBMIT A ROOF DETAIL. SINCE THERE HAS BEEN ADDED
 VERTICAL WALLS AND ROOF AREA DRAINING ONTO THE ROOF
 FROM ABOVE, THE ROOF DRAINAGE REQUIREMENTS SHALL BE
 REVIEWED. SHOW THE LOCATIONS FOR ALL THE PRIMARY AND
 SECONDARY ROOF DRAINS AND INDICATE THE SIZE OF ALL
 DRAINS. INDICATE THE SLOPE OF THE ROOF TO THE ROOF
 DRAINS. SUBMIT CALCULATIONS FOR THE PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW THE SQUARE FOOTAGE BEING
 DRAINED AT EACH ROOF DRAIN ALONG WITH 1/2 AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS AS WELL AS ANY ROOF
 AREA THAT DRAINS ONTO THE ROOF FROM ABOVE FOR EACH
 AREA. SECTIONS 1106 & 1107 WITH ALL SUBSECTIONS AND
 TABLES. SECTION 106.1.2.
  
 8. SHT A-4 FINISH SCHEDULE, ROOM 201 SHALL MEET THE
 REQUIREMENTS OF SECTION 1210.1 & 1210.2. PLEASE SHOW ON
 THE FINISH SCHEDULE.
  
 9. SHTS S-1 THRU S-4 THE ENGINEER SHALL LEGIBLY
 INDICATE THEIR ADDRESS AS WELL AS THE ADDRESS OF THE
 ENGINEERING BUSINESS IN THE TITLE BLOCKS. FAC
 61G15-23.002(2) & FS 471.025.
  
 10. SHT MP-1 NOTES FOR GREASE INTERCEPTOR: NOTE 3 PER
 SECTION 90-124(7)(F) GREASE INTERCEPTORS SHALL BE STEEL
 REINFORCED CONCRETE AND FIBERGLASS INTERCEPTORS ARE NOT
 APPROVED. PLEASE INDICATE ON PLANS.
  
 11. SHT MP-1 NOTES FOR GREASE INTERCEPTOR: NOTE 6.
 GREASE INTERCEPTORS ARE TO BE SIZED BY ENVIRONMENTAL
 COMPLIANCE SECTION OF THE UTILITY DEPT. PLEASE CONTACT
 RODNEY COMPO, (561) 822-2272, E-MAIL [email protected], OR
 CALVIN WILLIAMS, (561) 822-2284, E-MAIL
 [email protected]. THEIR FAX NUMBER IS (561) 822-2287.
 A WRITTEN VERIFICATION FROM ENVIRONMENTAL COMPLIANCE
 SHALL BE SUBMITTED WITH PLANS FOR GREASE INTERCEPTOR
 APPROVAL.
  
 12. NOTE: FLOOR DRAINS ARE NOT APPROVED INDIRECT WASTE
 INTERCEPTORS. PER SECTIONS 802.3 & 802.3.2.
  
 13. SHT MP-2 SANTITARY/GREASE ISOMETRIC RISER DIAGRAM.
 THE RISER DIAGRAM DOES NOT REFLECT THE FLOOR PLAN, NOR
 DOES IT MEET CODE REQUIREMENTS.--2-WAY CLEANOUTS
 ARE REQUIRED AT THE INLET AND THE OUTLET OF THE GREASE
 INTERCEPTOR AS WELL AS NEAR THE JUNCTION OF THE
 BUILDING DRAIN & BUILDING SEWER AS THE LINE EXITS THE
 BUILDING.--A VENT IS REQUIRED FOR THE CAN WASH.--
 FLOOR DRAIN NOT APPROVED UNDER THE EXPRESS MACHINE #2,
 FLOOR SINK REQUIRED.--FLOOR SINK REQUIRED FOR THE 3
 COMPARTMENT SINK IN THE FOOD PREP AREA.--2" FLOOR
 DRAIN SHOWN BETWEEN THE EXISTING LAV AND THE 3
 COMPARTMENT SINK IS NOT SHOWN ON THE FLOOR PLAN.--
 FLOOR SINK IS REQUIRED AT THE ICE MAKER.--THE 4"
 FLOOR DRAIN SHOWN BY THE EXISTING W/C IN THE 2ND FLOOR
 BATHROOM DOES NOT CONNECT TOSANITARY PIPING, NOR IS
 IT SHOWN ON THE FLOOR PLAN.--THE PIPING TO THE
 TRENCH DRAIN AND THE DRAIN CONNECTION DO NOT REFLECT
 THE FLOOR PLAN.PLEASE MAKE SURE THE RISER DIAGRAM
 CORRELATES WITH THE FLOOR PLAN AND MEETS CODE
 REQUIREMENTS. SECTIONS 1006.1.1,708.3.5,901.2.1 &
 802.3, & UTILITY DEPT. STANDARDS.
  
 14. SHT MP-2 HOT & COLD RISER DIAGRAMS. HOT WATER &
 BACKFLOW PROTECTION REQUIRED TO SUPPLY THE CAN WASH.
 SECTIONS 414.1, 601.7, 608.13.1 THRU 608.13.6 &
 608.13.8.
  
 15. THERMAL EXPANSION CONTROL IS REQUIRED PER SECTION
 607.3.2. INDICATE METHOD ON THE WATER HEATER DETAIL.
  
 16. SHT MP-2 PLUMBING GENERAL NOTE #7, AIR CHAMBERS ARE
 NOT APPROVED. PLEASE DELETE FROM NOTE. SECTION 604.9.
 WATER HAMMER ARRESTORS SHALL BE LOCATED NEAR THE
 FIXTURES, IN AN "EFFECTIVE RANGE" NOT IN THE CEILING.
 PDI-WH 201 AND MANUF. INSTALLATION INSTRUCTIONS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]