| 2007-09-07 17:07:53 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FBC-2004 EXISTING BUILDING CODE |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. ARCHITECTURAL SHEETS. THE PRINTED NAME OF THE PERSON |
| | SEALING THE DOCUMENT SHALL BE INDICATED IN THE TITLE |
| | BLOCK PER FAC 61G1-16.004(6) & FS 481.2055. |
| | |
| | 2. SHT A-2 DETAIL 1/A-2 CUSTOMERS, PATRONS & VISITORS |
| | SHALL BE PROVIDED WITH PUBLIC TOILET FACILITIES IN |
| | STRUCTURES & TENANT SPACES INTENDED FOR PUBLIC |
| | UTILIZATION. PLEASE PROVIDE TOILET FACILITIES. SECTION |
| | 403.6. |
| | |
| | 3. TABLE 403.1 REQUIRES A DRINKING FOUNTAIN. PLEASE |
| | INDICATE THE LOCATION OF THE DRINKING FOUNTAIN AND |
| | SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION 11-4.15 |
| | AND ALL SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A) |
| | PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR |
| | STOOPING. |
| | |
| | 4. INDICATE THE ALTERATION LEVEL PER SECTIONS 303, 304 |
| | OR 305 OF THE EXISTING BUILDING CODE. |
| | |
| | 5. SHT A-2DETAIL 1/A-2, THE TOILET ROOM SHALL BE |
| | ACCESSIBLE PER SECTION 806.1 OF THE EXISTING BUILDING |
| | CODE. SUBMIT DETAILS/ELEVATIONS SHOWING COMPLIANCE WITH |
| | SECTION 11-4.22 & ALL SUBSECTIONS. |
| | |
| | 6. SHT A-2DETAIL 2/A-2 THE BATHROOM, (RM 201), SHALL |
| | BE ACCESSIBLE. PER SECTION 806.1 OF THE EXISTING |
| | BUILDING CODE. SUBMIT DETAILS/ELEVATIONS SHOWING |
| | COMPLIANCE WITH SECTION 11-4.23 AND ALL SUBSECTIONS. |
| | |
| | 7. SUBMIT A ROOF DETAIL. SINCE THERE HAS BEEN ADDED |
| | VERTICAL WALLS AND ROOF AREA DRAINING ONTO THE ROOF |
| | FROM ABOVE, THE ROOF DRAINAGE REQUIREMENTS SHALL BE |
| | REVIEWED. SHOW THE LOCATIONS FOR ALL THE PRIMARY AND |
| | SECONDARY ROOF DRAINS AND INDICATE THE SIZE OF ALL |
| | DRAINS. INDICATE THE SLOPE OF THE ROOF TO THE ROOF |
| | DRAINS. SUBMIT CALCULATIONS FOR THE PRIMARY AND |
| | SECONDARY ROOF DRAINS. SHOW THE SQUARE FOOTAGE BEING |
| | DRAINED AT EACH ROOF DRAIN ALONG WITH 1/2 AREA OF ALL |
| | VERTICAL WALLS INCLUDING PARAPETS AS WELL AS ANY ROOF |
| | AREA THAT DRAINS ONTO THE ROOF FROM ABOVE FOR EACH |
| | AREA. SECTIONS 1106 & 1107 WITH ALL SUBSECTIONS AND |
| | TABLES. SECTION 106.1.2. |
| | |
| | 8. SHT A-4 FINISH SCHEDULE, ROOM 201 SHALL MEET THE |
| | REQUIREMENTS OF SECTION 1210.1 & 1210.2. PLEASE SHOW ON |
| | THE FINISH SCHEDULE. |
| | |
| | 9. SHTS S-1 THRU S-4 THE ENGINEER SHALL LEGIBLY |
| | INDICATE THEIR ADDRESS AS WELL AS THE ADDRESS OF THE |
| | ENGINEERING BUSINESS IN THE TITLE BLOCKS. FAC |
| | 61G15-23.002(2) & FS 471.025. |
| | |
| | 10. SHT MP-1 NOTES FOR GREASE INTERCEPTOR: NOTE 3 PER |
| | SECTION 90-124(7)(F) GREASE INTERCEPTORS SHALL BE STEEL |
| | REINFORCED CONCRETE AND FIBERGLASS INTERCEPTORS ARE NOT |
| | APPROVED. PLEASE INDICATE ON PLANS. |
| | |
| | 11. SHT MP-1 NOTES FOR GREASE INTERCEPTOR: NOTE 6. |
| | GREASE INTERCEPTORS ARE TO BE SIZED BY ENVIRONMENTAL |
| | COMPLIANCE SECTION OF THE UTILITY DEPT. PLEASE CONTACT |
| | RODNEY COMPO, (561) 822-2272, E-MAIL [email protected], OR |
| | CALVIN WILLIAMS, (561) 822-2284, E-MAIL |
| | [email protected]. THEIR FAX NUMBER IS (561) 822-2287. |
| | A WRITTEN VERIFICATION FROM ENVIRONMENTAL COMPLIANCE |
| | SHALL BE SUBMITTED WITH PLANS FOR GREASE INTERCEPTOR |
| | APPROVAL. |
| | |
| | 12. NOTE: FLOOR DRAINS ARE NOT APPROVED INDIRECT WASTE |
| | INTERCEPTORS. PER SECTIONS 802.3 & 802.3.2. |
| | |
| | 13. SHT MP-2 SANTITARY/GREASE ISOMETRIC RISER DIAGRAM. |
| | THE RISER DIAGRAM DOES NOT REFLECT THE FLOOR PLAN, NOR |
| | DOES IT MEET CODE REQUIREMENTS.--2-WAY CLEANOUTS |
| | ARE REQUIRED AT THE INLET AND THE OUTLET OF THE GREASE |
| | INTERCEPTOR AS WELL AS NEAR THE JUNCTION OF THE |
| | BUILDING DRAIN & BUILDING SEWER AS THE LINE EXITS THE |
| | BUILDING.--A VENT IS REQUIRED FOR THE CAN WASH.-- |
| | FLOOR DRAIN NOT APPROVED UNDER THE EXPRESS MACHINE #2, |
| | FLOOR SINK REQUIRED.--FLOOR SINK REQUIRED FOR THE 3 |
| | COMPARTMENT SINK IN THE FOOD PREP AREA.--2" FLOOR |
| | DRAIN SHOWN BETWEEN THE EXISTING LAV AND THE 3 |
| | COMPARTMENT SINK IS NOT SHOWN ON THE FLOOR PLAN.-- |
| | FLOOR SINK IS REQUIRED AT THE ICE MAKER.--THE 4" |
| | FLOOR DRAIN SHOWN BY THE EXISTING W/C IN THE 2ND FLOOR |
| | BATHROOM DOES NOT CONNECT TOSANITARY PIPING, NOR IS |
| | IT SHOWN ON THE FLOOR PLAN.--THE PIPING TO THE |
| | TRENCH DRAIN AND THE DRAIN CONNECTION DO NOT REFLECT |
| | THE FLOOR PLAN.PLEASE MAKE SURE THE RISER DIAGRAM |
| | CORRELATES WITH THE FLOOR PLAN AND MEETS CODE |
| | REQUIREMENTS. SECTIONS 1006.1.1,708.3.5,901.2.1 & |
| | 802.3, & UTILITY DEPT. STANDARDS. |
| | |
| | 14. SHT MP-2 HOT & COLD RISER DIAGRAMS. HOT WATER & |
| | BACKFLOW PROTECTION REQUIRED TO SUPPLY THE CAN WASH. |
| | SECTIONS 414.1, 601.7, 608.13.1 THRU 608.13.6 & |
| | 608.13.8. |
| | |
| | 15. THERMAL EXPANSION CONTROL IS REQUIRED PER SECTION |
| | 607.3.2. INDICATE METHOD ON THE WATER HEATER DETAIL. |
| | |
| | 16. SHT MP-2 PLUMBING GENERAL NOTE #7, AIR CHAMBERS ARE |
| | NOT APPROVED. PLEASE DELETE FROM NOTE. SECTION 604.9. |
| | WATER HAMMER ARRESTORS SHALL BE LOCATED NEAR THE |
| | FIXTURES, IN AN "EFFECTIVE RANGE" NOT IN THE CEILING. |
| | PDI-WH 201 AND MANUF. INSTALLATION INSTRUCTIONS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |