| 2007-08-21 16:37:55 | REVIEW #: 1 |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. A LEVEL OF ALTERATION IS TO BE DECLARED IN |
| | ACCORDANCE WITH FBC,EB 301.5. INCLUDE THIS INFORMATION |
| | IN THE BUILDING DATA ON A-1. THIS APPEARS TO BE A LEVEL |
| | 3 ALTERATION. |
| | |
| | 2. THIS BUILDING IS CONSIDERED A RENOVATION UNDER THE |
| | DEFINITION OF A RENOVATION IN FBC 13-202 AS THE VALUE |
| | OF THE PROPOSED IMPROVEMENT IS ABOVE THE THRESHOLD OF |
| | 30% OF THE STRUCTURES VALUE OF $220,746. SEE PROPERTY |
| | APPRAISER DATA (ATTACHED). RENOVATED BUILDINGS SHALL |
| | COMPLY WITH THE PRESCRIPTIVE REQUIREMENTS CONTAINED IN |
| | FORM 400C OR WITH METHOD B OF SUBCHAPTER 13-4 FOR |
| | INSULATION, HVAC SYSTEMS, LIGHTING, WATER HEATING |
| | SYSTEMS AND EXTERIOR ENVELOPE COMPONENTS BEING |
| | RETROFITTED OR REPLACED. FBC 13-101.1.3. PROVIDE FORM |
| | 400C OR 400B TO SHOW COMPLIANCE. FORM 400A IS NOT AN |
| | OPTION FOR THIS TYPE OF PROJECT. |
| | |
| | 3. ALL VENTILATION REQUIREMENTS OF FBC,M CHAPTER 4 AND |
| | THE EXHAUST REQUIREMENTS OF FBC,M CHAPTER 5 SHALL BE |
| | MET PER FBC, EB 609.1. PROVIDE OUTDOOR AIR CALCULATIONS |
| | SHOWING OCCUPANCY CLASSIFICATION, OCCUPANT LOAD AND CFM |
| | OF OUTDOOR AIR REQUIRED/PROVIDED FOR ALL AREAS PER |
| | FBC,M TABLE 403.3. |
| | |
| | 4. PROVIDE A TYPE II COMMERCIAL KITCHEN EXHAUST HOOD |
| | OVER THE OVENS PER FBC,M 507.2. |
| | |
| | 5. OUTDOOR WALL LOUVERS ARE SUBJECT TO FAC RULE 9B-72 |
| | AND AS SUCH. PRODUCT APPROVAL IS REQUIRED. PROVIDE |
| | SPECIFIC PRODUCT APPROVAL FOR THE MANUFACTURER AND |
| | MODEL OF LOUVERS TO BE USED. FOR MORE INFORMATION ON |
| | THE FLORIDA PRODUCT APPROVAL SYSTEM PLEASE VISIT: |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 6. SHOW ON PLANS THE MEANS AND LOCATION OF CONDENSATE |
| | DISPOSAL. THE LOCATION SHALL COMPLY WITH FBC,M 307.2.1 |
| | AND FBC 1503.6. IT SHALL NOT DISCHARGE ONTO ASPHALT AS |
| | DESCRIBED IN PLUMBING GENERAL NOTE #18. |
| | |
| | 7. SHOW MEANS OF AUXILIARY OR SECONDARY DRAIN |
| | PROTECTION IN ACCORDANCE WITH FBC,M 307.2.3. A WATER |
| | LEVEL DETECTION DEVICE I(FLOAT SWITCH) N THE SECONDARY |
| | DRAIN PAN WILL MET THIS REQUIREMENT. |
| | |
| | 8. SECOND FLOOR HVAC PLAN STATES "SEE NOTE #1" BUT NO |
| | NOTE COULD BE FOUND RELATED TO THIS AREA. PLEASE |
| | CLARIFY. |
| | |
| | NOTE: SEPARATE PERMITS ARE REQUIRED FOR THE HOODS, HOOD |
| | SUPPRESSION SYSTEM(S) AND THE WALK-IN COOLERS. |
| | |