2007-08-21 16:37:55REVIEW #: 1
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. A LEVEL OF ALTERATION IS TO BE DECLARED IN
 ACCORDANCE WITH FBC,EB 301.5. INCLUDE THIS INFORMATION
 IN THE BUILDING DATA ON A-1. THIS APPEARS TO BE A LEVEL
 3 ALTERATION.
  
 2. THIS BUILDING IS CONSIDERED A RENOVATION UNDER THE
 DEFINITION OF A RENOVATION IN FBC 13-202 AS THE VALUE
 OF THE PROPOSED IMPROVEMENT IS ABOVE THE THRESHOLD OF
 30% OF THE STRUCTURES VALUE OF $220,746. SEE PROPERTY
 APPRAISER DATA (ATTACHED). RENOVATED BUILDINGS SHALL
 COMPLY WITH THE PRESCRIPTIVE REQUIREMENTS CONTAINED IN
 FORM 400C OR WITH METHOD B OF SUBCHAPTER 13-4 FOR
 INSULATION, HVAC SYSTEMS, LIGHTING, WATER HEATING
 SYSTEMS AND EXTERIOR ENVELOPE COMPONENTS BEING
 RETROFITTED OR REPLACED. FBC 13-101.1.3. PROVIDE FORM
 400C OR 400B TO SHOW COMPLIANCE. FORM 400A IS NOT AN
 OPTION FOR THIS TYPE OF PROJECT.
  
 3. ALL VENTILATION REQUIREMENTS OF FBC,M CHAPTER 4 AND
 THE EXHAUST REQUIREMENTS OF FBC,M CHAPTER 5 SHALL BE
 MET PER FBC, EB 609.1. PROVIDE OUTDOOR AIR CALCULATIONS
 SHOWING OCCUPANCY CLASSIFICATION, OCCUPANT LOAD AND CFM
 OF OUTDOOR AIR REQUIRED/PROVIDED FOR ALL AREAS PER
 FBC,M TABLE 403.3.
  
 4. PROVIDE A TYPE II COMMERCIAL KITCHEN EXHAUST HOOD
 OVER THE OVENS PER FBC,M 507.2.
  
 5. OUTDOOR WALL LOUVERS ARE SUBJECT TO FAC RULE 9B-72
 AND AS SUCH. PRODUCT APPROVAL IS REQUIRED. PROVIDE
 SPECIFIC PRODUCT APPROVAL FOR THE MANUFACTURER AND
 MODEL OF LOUVERS TO BE USED. FOR MORE INFORMATION ON
 THE FLORIDA PRODUCT APPROVAL SYSTEM PLEASE VISIT:
 WWW.FLORIDABUILDING.ORG
  
 6. SHOW ON PLANS THE MEANS AND LOCATION OF CONDENSATE
 DISPOSAL. THE LOCATION SHALL COMPLY WITH FBC,M 307.2.1
 AND FBC 1503.6. IT SHALL NOT DISCHARGE ONTO ASPHALT AS
 DESCRIBED IN PLUMBING GENERAL NOTE #18.
  
 7. SHOW MEANS OF AUXILIARY OR SECONDARY DRAIN
 PROTECTION IN ACCORDANCE WITH FBC,M 307.2.3. A WATER
 LEVEL DETECTION DEVICE I(FLOAT SWITCH) N THE SECONDARY
 DRAIN PAN WILL MET THIS REQUIREMENT.
  
 8. SECOND FLOOR HVAC PLAN STATES "SEE NOTE #1" BUT NO
 NOTE COULD BE FOUND RELATED TO THIS AREA. PLEASE
 CLARIFY.
  
 NOTE: SEPARATE PERMITS ARE REQUIRED FOR THE HOODS, HOOD
 SUPPRESSION SYSTEM(S) AND THE WALK-IN COOLERS.
  