| 2007-09-18 18:34:05 | *****DENIED***** |
| | |
| | |
| | 01.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE |
| | REFERENCED. |
| | |
| | 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL CDOMPLY WITH NFPA 241. |
| | |
| | 03.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS |
| | BELVEDERE ROAD, DISPLAY THE NUMERICAL ADDRESS ON THE |
| | BUILDING.AS PER WEST PALM BEACH CODE, THE ADDRESS |
| | NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS |
| | THAN 1" IN WIDTH. |
| | |
| | 04.SPECIFY THE NEW INTERIOR WALL AND CEILING FINISH |
| | MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C. |
| | SPECIFY THE INTERIOR FLOOR FINISH IN TERMS OF CLASS I |
| | OR CLASS II. |
| | |
| | 05.PROVIDE A LIFE SAFETY PLAN SHOWING THE TRAVEL |
| | DISTANCE TO THE EXITS.THE LOCATION OF THE 2A:10BC |
| | FIRE EXTINGUISHER(S) WHICH SATIFIES THE 75' TRAVEL |
| | DISTANCE CAN ALSO BE INCLUDED. |
| | |
| | 06.ALL FIRE RATED DOORS AND FIRE RATED WINDOWS SHALL |
| | COMPLY WITH NFPA 80. |
| | |
| | 07.VERIFY/SUBMIT THE PRESCRIPTIVE STRENGHT FOR THE |
| | HANDRAIL/GUARDRAIL FOR THE EXISTING/REMAINING EXIT |
| | STAIR AS CODE COMPLIANT. |
| | |
| | 08.THE EXISTING/REMAINING EXIT STAIR INSTALLATION AND |
| | DISCHARGE OCCURS ON WHICH LEGAL PROPERTY 740 BELVEDERE |
| | OR 736 BELVEDERE (ADULT ENTERTAINMENT CLUB).PLEASE |
| | PROVIDE A LEGAL SURVEY. |
| | |
| | 09.SPECIFY THE HAZARD OF THE CONTENTS OF THE STORAGE |
| | ROOM IN TERMS OF LOW, ORDINARY, OR HIGH. |
| | |
| | 10.PLEASE PROVIDE THE CRITERIA/SPECIFICATIONS FOR THE |
| | PROPOSED SPIRAL STAIRS COMPLYING WITH 7.2.2.2.3 OF THE |
| | LIFE SAFETY CODE -NFPA 101. |
| | |
| | 11.COMMERCIAL COOKING EQUIPMENT SHALL BE IN |
| | ACCORDANCE WITH NFPA 96 - 2001 EDITION.SEPARATE PLANS |
| | AND PERMIT WILL BE REQUIRED FOR THE BOTH THE |
| | INSTALLATION OF THE COOKING HOOD AND THE COOKING HOOD'S |
| | SUPPRESSION SYSTEM. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |