Plan Review Notes
Plan Review Notes For Permit 07071001
Permit Number 07071001
Review Stop E
Sequence Number 1
Notes
Date Text
2007-08-25 18:12:452007-08-25 18:12:45
  
 *** DENIED ***
  
  
 ** PLEASE KNOW AS THERE ARE SOME ITEMS NOT YET
 SUBMITTED FOR REVIEW THERE MAY VERY WELL BE NEW
 COMMENTS ONCE SUBMITTED.
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
 2) NOTE: PLEASE SEE FBC EXISTING BUILDING CODE FOR
 ELECTRICAL WHICH REFERENCES CHAPTER 27 OF THE FBC.
 PLEASE SEE THE SCOPE OF WORK WELL EXCEEDS THE VALUE OF
 THE 30% AS DEFINED FOR RENOVATIONS.
 PLEASE SUBMIT THE COMPLETED ENERGY CALCULATIONS. PLEASE
 SEE THE CERTIFICATION SHEET EVENS STATES NOT VALID WITH
 OUT THE INPUT DATA REPORT.
 PLEASE KNOW AT THIS TIME NOT REVIEW FOR LIGHTING
 COMPLIANCE CAN BE DONE FOR INTERIOR AND EXTERIOR
 LIGHTING POWER ALLOWANCES. PLEASE SEE 13-415.1.A,
 13-415.2, 13-415.2.ABC.1.2, 13-415.2.ABC.1.3,
 13-415.2.ABC.1.1
  
 3) NOTE: PLEASE SEE THE PLANS AND RISER ARE SHOWING A
 NEW SERVICE FOR THIS PORTION OF THE BUILDING HOWEVER
 THE AS THE PLANS INDICATE THIS A ONE BUILDING ALONG
 WITH THE ADJACENT STRUCTURE ONE PROPERTY THE NEW
 SERVICE AS SHOWN IS NOT GRANTED.
 PLEASE PROVIDE STRUCTURAL INFORMATION FOR THE CONNECTED
 TENANTS.
 PLEASE SEE THIS WOULD REQUIRE A *FIRE WALL* AS DEFINED
 IN THE BUILDING CODE WHICH NOT ONLY CONTAINS A FIRE
 RATING BUT ALLOWS STRUCTURAL COLLAPSE ON ONE SIDE OR
 THE OTHER WITHOUT AFFECT THE STRUCTURAL INTEGRITY OF
 THE OTHER STRUCTURE. AS NO INFORMATION ON THE BUILDING
 AND ADJACENT TENANT IS PROVIDED, UNABLE TO MAKE THE
 DETERMINATION IF MEETING 230.2.
 PLEASE SEE THE PLANS ALSO INDICATE ITEMS LOCATED ON THE
 ADJACENT TENANT ROOF WHICH IS ACTUALLY FOR THIS
 BUILDING??
 PLEASE KNOW THAT IF THIS IS CONSIDERED ONE BUILDING AND
 IS ONLY FED FROM SERVICE THEN THIS IS OK, HOWEVER BASED
 ON PLANS REQUESTED A SEPARATE SERVICE ALL ELECTRICAL
 WHICH IS LOCATED ON THE ADJACENT STRUCTURE WOULD NOT BE
 PERMITTED.
 PLEASE ALSO SEE ONE OF THE COMMENTS BELOW WITH RESPECT
 TO THE EGRESS STAIRS.
  
 4) NOTE: PLEASE SEE NO DISCONNECT FOR MINI-SPLIT CU
 SHOWN ON ROOF IS INDICATED ON PLANS.
 PLEASE SHOW 440.1.
  
 5) NOTE: PLEASE SEE MISSING ROOF TOP GFI AS REQUIRED
 PER 210.63, 210.8B3
  
 6) NOTE: PLEASE SEE MISSING SHOW WINDOW RECEPTACLES FOR
 WINDOWS AT THE FRONT OF THE STORE.
 210.62
 PLEASE BE SURE TO ADJUST LOAD CALCULATIONS PER 220.43
  
 7) NOTE: PLEASE SEE 600.5 AS THE MINIMUM VA FOR THE
 SIGN CIRCUIT IS REQUIRED TO BE 1200 VA. BASED ON THE
 AMPERAGE SHOWN ON PANEL SCHEDULE AT 120V THIS DOES NOT
 SHOW THE MINIMUM LOAD AS NEEDED.
  
 8) NOTE: PLEASE CLARIFY THE PANELS. THESE ARE SHOWN AS
 200MLO, YET THESE ARE SHOWN AS 42SPACES.
 PLEASE VERIFY THE AVAILABILITY OF THESE TYPES OF
 PANELS. THIS IS OK, HOWEVER IF THESE PANELS SHOWN AT 42
 SPACES ARE INDEED 225AMP RATED, THAN PLEASE REVISE
 PLANS TO SHOW THIS.
 ** THIS WOULD ALLEVIATE AND REVISIONS NEEDED AT A LATER
 DATE.
  
 9) NOTE: PLEASE CLARIFY THE COOLER AS THERE IS NO
 LIGHTING PROVIDED ON PLANS.,
 FBC 106.1.2 (ADDITIONAL INFORMATION).
  
 10) NOTE: PLEASE SEE MISSING INFORMATION ON THE TITLE
 BLOCKS FOR THE ARCHITECT AS REQUIRED PER FAC
 61G1-16.004.
  
 11) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR STAIR AREAS
 UNDER NORMAL AND UNDER EMERGENCY.
 PLEASE SEE THAT THIS NEEDS TO INCLUDE THE EXTERIOR
 STAIR TO THE PUBLIC RIGHT OF WAY. PLEASE PROVIDE
 LIGHTING FIXTURES AND ALSO BATTERY BACK UP AS REQUIRED
 UNDER THE MINIMUM REQUIREMENTS OF THE LIFE SAFETY
 CODE.
 PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.2
  
 12) NOTE: PLEASE SEE 210.8B2 AS ALL 15 AND 20 AMP 120
 RECEPTACLES IN KITCHEN AND FOOD PREP AREAS ARE REQUIRED
 TO BE GFI OR GFI PROTECTED. THIS DOES NOT MATTER IF
 THESE FEED COUNTER SPACES OR NOT.
  
 13) NOTE: PLEASE SUBMIT ELECTRICAL FOR THE 2ND FLOOR.
 DUE TO THE SCOPE OF WORK, THIS AREA WOULD BE REQUIRED
 TO MEET CODE.
 PLEASE SEE ANY POSSIBLE COMMENTS FROM THE FIRE MARSHAL
 AND BUILDING REVIEWER FOR REQUIRED SMOKE ALARMS OR
 SMOKE DETECTORS.
 AS SHOWN ON PLANS, THIS AREA IS NOT PERMITTED TO BE
 USED FOR SLEEPING/APARTMENT/RESIDENCE. IF SO, THEN
 MINIMUM REQUIRED CIRCUITS AND ARC FAULT PROTECTION
 WOULD BE REQUIRED.
 FBC 106.1.2, 106.3.5.1.2
 NEC 2005.
  
 14) NOTE: PLEASE INDICATE THE SIZE OF THE METER CAN.
 FBC 106.1.2.
  
 15) NOTE: PLANS INDICATE THERE IS GOING TO BE LANDSCAPE
 LIGHTING HOWEVER NO ELECTRICAL SITE PLANS ARE SUBMITTED
 SHOWING THE CIRCUITS, LIGHTING LOCATIONS ETC. PLEASE
 COMPLETE.
 FBC 106.1.2, 106.3.5.1.2
  
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]