| Date |
Text |
| 2007-08-25 18:12:45 | 2007-08-25 18:12:45 |
| | |
| | *** DENIED *** |
| | |
| | |
| | ** PLEASE KNOW AS THERE ARE SOME ITEMS NOT YET |
| | SUBMITTED FOR REVIEW THERE MAY VERY WELL BE NEW |
| | COMMENTS ONCE SUBMITTED. |
| | |
| | 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| | ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| | UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED |
| | FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS |
| | NOT MADE BY OTHER TRADE(S). |
| | |
| | 2) NOTE: PLEASE SEE FBC EXISTING BUILDING CODE FOR |
| | ELECTRICAL WHICH REFERENCES CHAPTER 27 OF THE FBC. |
| | PLEASE SEE THE SCOPE OF WORK WELL EXCEEDS THE VALUE OF |
| | THE 30% AS DEFINED FOR RENOVATIONS. |
| | PLEASE SUBMIT THE COMPLETED ENERGY CALCULATIONS. PLEASE |
| | SEE THE CERTIFICATION SHEET EVENS STATES NOT VALID WITH |
| | OUT THE INPUT DATA REPORT. |
| | PLEASE KNOW AT THIS TIME NOT REVIEW FOR LIGHTING |
| | COMPLIANCE CAN BE DONE FOR INTERIOR AND EXTERIOR |
| | LIGHTING POWER ALLOWANCES. PLEASE SEE 13-415.1.A, |
| | 13-415.2, 13-415.2.ABC.1.2, 13-415.2.ABC.1.3, |
| | 13-415.2.ABC.1.1 |
| | |
| | 3) NOTE: PLEASE SEE THE PLANS AND RISER ARE SHOWING A |
| | NEW SERVICE FOR THIS PORTION OF THE BUILDING HOWEVER |
| | THE AS THE PLANS INDICATE THIS A ONE BUILDING ALONG |
| | WITH THE ADJACENT STRUCTURE ONE PROPERTY THE NEW |
| | SERVICE AS SHOWN IS NOT GRANTED. |
| | PLEASE PROVIDE STRUCTURAL INFORMATION FOR THE CONNECTED |
| | TENANTS. |
| | PLEASE SEE THIS WOULD REQUIRE A *FIRE WALL* AS DEFINED |
| | IN THE BUILDING CODE WHICH NOT ONLY CONTAINS A FIRE |
| | RATING BUT ALLOWS STRUCTURAL COLLAPSE ON ONE SIDE OR |
| | THE OTHER WITHOUT AFFECT THE STRUCTURAL INTEGRITY OF |
| | THE OTHER STRUCTURE. AS NO INFORMATION ON THE BUILDING |
| | AND ADJACENT TENANT IS PROVIDED, UNABLE TO MAKE THE |
| | DETERMINATION IF MEETING 230.2. |
| | PLEASE SEE THE PLANS ALSO INDICATE ITEMS LOCATED ON THE |
| | ADJACENT TENANT ROOF WHICH IS ACTUALLY FOR THIS |
| | BUILDING?? |
| | PLEASE KNOW THAT IF THIS IS CONSIDERED ONE BUILDING AND |
| | IS ONLY FED FROM SERVICE THEN THIS IS OK, HOWEVER BASED |
| | ON PLANS REQUESTED A SEPARATE SERVICE ALL ELECTRICAL |
| | WHICH IS LOCATED ON THE ADJACENT STRUCTURE WOULD NOT BE |
| | PERMITTED. |
| | PLEASE ALSO SEE ONE OF THE COMMENTS BELOW WITH RESPECT |
| | TO THE EGRESS STAIRS. |
| | |
| | 4) NOTE: PLEASE SEE NO DISCONNECT FOR MINI-SPLIT CU |
| | SHOWN ON ROOF IS INDICATED ON PLANS. |
| | PLEASE SHOW 440.1. |
| | |
| | 5) NOTE: PLEASE SEE MISSING ROOF TOP GFI AS REQUIRED |
| | PER 210.63, 210.8B3 |
| | |
| | 6) NOTE: PLEASE SEE MISSING SHOW WINDOW RECEPTACLES FOR |
| | WINDOWS AT THE FRONT OF THE STORE. |
| | 210.62 |
| | PLEASE BE SURE TO ADJUST LOAD CALCULATIONS PER 220.43 |
| | |
| | 7) NOTE: PLEASE SEE 600.5 AS THE MINIMUM VA FOR THE |
| | SIGN CIRCUIT IS REQUIRED TO BE 1200 VA. BASED ON THE |
| | AMPERAGE SHOWN ON PANEL SCHEDULE AT 120V THIS DOES NOT |
| | SHOW THE MINIMUM LOAD AS NEEDED. |
| | |
| | 8) NOTE: PLEASE CLARIFY THE PANELS. THESE ARE SHOWN AS |
| | 200MLO, YET THESE ARE SHOWN AS 42SPACES. |
| | PLEASE VERIFY THE AVAILABILITY OF THESE TYPES OF |
| | PANELS. THIS IS OK, HOWEVER IF THESE PANELS SHOWN AT 42 |
| | SPACES ARE INDEED 225AMP RATED, THAN PLEASE REVISE |
| | PLANS TO SHOW THIS. |
| | ** THIS WOULD ALLEVIATE AND REVISIONS NEEDED AT A LATER |
| | DATE. |
| | |
| | 9) NOTE: PLEASE CLARIFY THE COOLER AS THERE IS NO |
| | LIGHTING PROVIDED ON PLANS., |
| | FBC 106.1.2 (ADDITIONAL INFORMATION). |
| | |
| | 10) NOTE: PLEASE SEE MISSING INFORMATION ON THE TITLE |
| | BLOCKS FOR THE ARCHITECT AS REQUIRED PER FAC |
| | 61G1-16.004. |
| | |
| | 11) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR STAIR AREAS |
| | UNDER NORMAL AND UNDER EMERGENCY. |
| | PLEASE SEE THAT THIS NEEDS TO INCLUDE THE EXTERIOR |
| | STAIR TO THE PUBLIC RIGHT OF WAY. PLEASE PROVIDE |
| | LIGHTING FIXTURES AND ALSO BATTERY BACK UP AS REQUIRED |
| | UNDER THE MINIMUM REQUIREMENTS OF THE LIFE SAFETY |
| | CODE. |
| | PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.2 |
| | |
| | 12) NOTE: PLEASE SEE 210.8B2 AS ALL 15 AND 20 AMP 120 |
| | RECEPTACLES IN KITCHEN AND FOOD PREP AREAS ARE REQUIRED |
| | TO BE GFI OR GFI PROTECTED. THIS DOES NOT MATTER IF |
| | THESE FEED COUNTER SPACES OR NOT. |
| | |
| | 13) NOTE: PLEASE SUBMIT ELECTRICAL FOR THE 2ND FLOOR. |
| | DUE TO THE SCOPE OF WORK, THIS AREA WOULD BE REQUIRED |
| | TO MEET CODE. |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM THE FIRE MARSHAL |
| | AND BUILDING REVIEWER FOR REQUIRED SMOKE ALARMS OR |
| | SMOKE DETECTORS. |
| | AS SHOWN ON PLANS, THIS AREA IS NOT PERMITTED TO BE |
| | USED FOR SLEEPING/APARTMENT/RESIDENCE. IF SO, THEN |
| | MINIMUM REQUIRED CIRCUITS AND ARC FAULT PROTECTION |
| | WOULD BE REQUIRED. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | NEC 2005. |
| | |
| | 14) NOTE: PLEASE INDICATE THE SIZE OF THE METER CAN. |
| | FBC 106.1.2. |
| | |
| | 15) NOTE: PLANS INDICATE THERE IS GOING TO BE LANDSCAPE |
| | LIGHTING HOWEVER NO ELECTRICAL SITE PLANS ARE SUBMITTED |
| | SHOWING THE CIRCUITS, LIGHTING LOCATIONS ETC. PLEASE |
| | COMPLETE. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | |
| | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |