| 2007-11-13 14:50:12 | BUILDING REVIEW THIRD CHECKLIST. |
| | REVIEW UNDER EXISTING BUILDING CODE 2004, FLORIDA |
| | RESIDENTIAL CODE 2004 AND FBC 2004 WITH 2007 |
| | REVISIONS. |
| | |
| | 1- PROVIDE COMPLETE ENGINEERING PACKAGE FOR CHANCE |
| | HELICAL PIER FOUNDATION SYSTEM TO BE APPLIED TO THIS |
| | HOUSE AS REQUIRED ON SHEET S-1 BY ENGINEER OF RECORD |
| | AND BY ICC-ES LISTED REPORT ER-5110.(REPEAT COMMENT). |
| | INFORMATION SUBMITTED DOESN'T PROVIDE THIS |
| | INFORMATION. |
| | |
| | |
| | ***NOTE: ENGINEERING REQUIREMENTS WHERE DISCUSSED OVER |
| | THE PHONE WITH LADY FROM THE COMPANY SUPPLYING THE |
| | CHANCE HELICAL FOUNDATION SYSTEM. SHE CALLED ME TO |
| | CLARIFYTHAT PRODUCT APPROVAL WAS NOT REQUIRED. SHE |
| | TOLD ME THAT THE COMPANY'SENGINEER WILL BE PROVIDING |
| | THE REQUIRED ENGINEERING, BUT IT WAS NOT SUBMITTED THIS |
| | TIME. |
| | |
| | 2- ENGINEER OF RECORD LETTER APPROVING THE FOUNDATION |
| | SYSTEM NEEDS TO HAVE ENGINEER'S ORIGINAL SEAL AND |
| | SIGNATURE AS REQUIRED BY CHAPTER 471 FLORIDA STATE AND |
| | SEC. 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE. |
| | |
| | 3- SOIL TEST REPORT SUBMITTED: |
| | A) ENGINEER NEEDS TO SIGN AND SEAL THE REPORT AND |
| | PROVIDE HIS INFORMATION AS REQUIRED BY SEC. |
| | 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE. REPORT |
| | SUBMITTED WAS SIGNED ONLY BY THE PROJECT COORDINATOR, |
| | DAVID ALKER. |
| | |
| | B) ENGINEERING FIRM NEEDS TO PROVIDE THE FIRM'S |
| | CERTIFICATE OF AUTHORIZATION NUMBER AS REQUIRED BY SEC. |
| | 61G15-23.002. |
| | |
| | 4- TYPICAL STAIR DETAIL 4/A3 DOESN'T MATCH STRUCTURAL |
| | PLANS. (REPEAT COMMENT).STRUCTURAL PLANS DON'T SHOW |
| | WOOD POSTS. THERE IS NOT 2X6LANDING. REVISE AS |
| | REQUIRED. |
| | |
| | 5-PLEASE MAKE SURE ALL PRODUCT APPROVALS SUBMITTED |
| | ARE REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD AS REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO |
| | FBC 2004. SOME OF THE PRODUCT APPROVALS WERE NOT |
| | STAMPED WITH THE REVIEW STAMP. |
| | |