| Plan Review Notes For Permit 07070946 |
| Permit Number |
07070946 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-08-07 13:21:50 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS,2005 | | | NEC, AND FOUND NONE COMPLIANT WITH THE FOLLOWING: | | | | | | | | | 1} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS, | | | CONDUIT AND CONDUCTOR SIZE AND TYPE, AND THE LOCATION | | | FOR EQUIPMENT BEING WIRED UNDER THIS PERMIT .106.5 FBC | | | AS AMENDEED. | | | | | | 2} INDICATE COMPLIANCE WITH 600.6 FOR THE DISCONNECTING | | | MEANS. | | | | | | 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. | | | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417 | | | FS, RESPECTIVELY | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|