| 2007-12-13 16:43:11 | |
| | |
| | APPLICATION #07070921 |
| | ELECTRICAL PLAN REVIEW |
| | 1100 N OLIVE AVE |
| | 12/13/07 |
| | WEST PALM BEACH, FL. |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND |
| | FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE |
| | NOTED. |
| | |
| | 1}SUBMIT FORMS, SHOW DEVICES REQUIRED, PROVIDE A |
| | FIXTURE SCHEDULE INDICATING DENSITY COMPLIANCE REQUIRED |
| | BY FBC 13-101.3 CHANGES OF OCCUPANCY TYPE, AND ALL |
| | RELATED ARTICLES OF CHAPTER 13. |
| | 13-101.3.1 BUILDINGS HAVING A CHANGE OF OCCUPANCY TYPE |
| | THAT WERE PERMITTED PRIOR TO MARCH 15, 1979, SHALL MEET |
| | THE REQUIREMENTS FOR RENOVATIONS IN SECTION 101.1.3 OR |
| | SECTION 101.2.3, AS APPROPRIATE, FOR THOSE COMPONENTS |
| | WHICH ARE BEING RETROFITTED OR REPLACED. |
| | |
| | 2} A TITLE BLOCK FOR THE ENGINEER WITH INFORMATION PER |
| | 61G15-23.002(2) FAC. IS REQUIRED. |
| | |
| | 3} PROVIDE EMERGENCY ILLUMINATION PER NFPA-101 7.8 |
| | (2003), AND CIRCUITED |
| | PER 700.12 NEC (F)(4). INDICATE SAME ON PLANS. |
| | |
| | 4} PROVIDE A RISER DIAGRAM AND LOAD CALCULATIONS |
| | INDICATING COMPLIANCE WITH ARTICLE 220 FOR A COMMERCIAL |
| | BUILDING. |
| | |
| | 5} INDICATE THE RATING OF THE EXISTING SERVICE. 215.5 |
| | NEC. SUBMIT A PANEL SCHEDULE PER 408.4 NEC AND |
| | 106.3.5.4(8) FBC. |
| | |
| | 6} LOCATE ALL SERVICE EQUIPMENT ON THE PLAN. 106.1.3 |
| | FBC AS AMENDED. |
| | |
| | 7} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR |
| | DEVICES.106.3.5 FBC. |
| | |
| | 8} NFPA 101-7.8.1.3* |
| | THE FLOORS AND OTHER WALKING SURFACES WITHIN AN EXIT |
| | AND WITHIN THE PORTIONS OF THE EXIT ACCESS AND EXIT |
| | DISCHARGE DESIGNATED IN 7.8.1.1 SHALL BE ILLUMINATED TO |
| | VALUES OF AT LEAST 1 FT-CANDLE (10 LUX) MEASURED AT THE |
| | FLOOR. INDICATE ON PLANS. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |