| Date |
Text |
| 2007-11-29 09:20:59 | SECONDBUILDING REVIEW CHECKLIST FOR NEW RESIDENTIAL |
| | ADDITION. |
| | REVIEW DONE UNDERFBC 2004 WITH 2007 REVISIONS. |
| | |
| | 1- SOIL TEST REPORT TO HAVE ENGINEERING FIRM |
| | CERTIFICATE OF AUTHORIZATION NUMBER AS REQUIRED BY |
| | FLORIDA ADMINISTRATIVE CODE SEC. 61G15-23.002(2). |
| | |
| | 2- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| | 9B-72 FOR: |
| | A) FLAT ROOF ASSEMBLY TO BE USED. SEE ATTACHED COPY |
| | OF CITY POLICY FOR ROOFING PERMITS AND REQUIRED |
| | INFORMATION. |
| | CLEARLYCIRCLE SPECIFIC APPROVED ASSEMBLY TO BE |
| | INSTALLED AND SPECIFIC FASTENING OPTION IF MORE THAN |
| | ONE OPTION IS LISTED.IN ADDITION,IF SELECTED |
| | ASSEMBLY IS LIMITED BY GENERAL LIMITATION #7, THEN |
| | PROVIDE THE REQUIRED RAS 117 CALCULATIONS FOR NAIL |
| | ENHANCING AT PERIMETER AND CORNER AREAS.THESE |
| | CALCULATIONS MAY BE REQUIRED TO BE PERFORMED ONLY BY |
| | ARCHITECT, ENGINEER OR REGISTERED ROOF CONSULTANT. SEE |
| | LAST PAGE OF PRODUCT APPROVAL TO SEE WHO'S MUST DO THE |
| | CALCULATIONS. |
| | ON THE OTHER HAND IF SELECTED ASSEMBLY IS LIMITED BY |
| | GENERAL LIMITATION #9, THEN, IT CAN'T BE USED IN THIS |
| | AREA BECAUSE NAIL ENHANCING IT'S NOT ALLOWED TO |
| | INCREASE THE UPLIFT CAPACITY OF THE ROOF ASSEMBLY. SEE |
| | GENERAL LIMITATION #9.(REPEAT COMMENT. INFORMATION |
| | WAS NOT PROVIDED AT ALL). |
| | |
| | B) ALL STRUCTURAL SIMPSON CONNECTORS SPECIFIED ON |
| | PLANS AND DETAILS. PROVIDE FLORIDA PRODUCT APPROVAL |
| | COVER PAGE AND PAGE WHERE CONNECTOR IS SHOWN ONLY. GO |
| | TO WWW.FLORIDA BUILDING.ORG TO DOWNLOAD CORRESPONDING |
| | INFORMATION. (REPEAT COMMENT. INFORMATION WAS NOT |
| | PROVIDED AT ALL). |
| | |
| | C)"INSWING" DOOR EXTERIOR DOOR AS SHOWN ON NEW |
| | UTILITY FLOOR PLAN . PRODUCT APPROVAL SUBMITTED IS FOR |
| | AN "OUTSWING" DOOR. |
| | |
| | ***NOTE: IF DOOR IS CHANGED FOR AN "OUTSWING" DOOR, |
| | THEN KEEP IN MIND THAT COMPLIANCE WITH SECTION R311.4.3 |
| | OF 2004 FLORIDA RESIDENTIAL CODE IS REQUIRED. |
| | |
| | |
| | 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | (REPEAT COMMENT. NOT ADDRESSED BY THE ENGINEER OF |
| | RECORD). |
| | |
| | 4- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | 13-600.1.C.1. |
| | NOTE: MAKE SURE CORRECT 2006 REVISED FORM IS USED. |
| | (REPEAT COMMENT.INFORMATION WAS NOT SUBMITTED AT |
| | ALL). |
| | |
| | 5- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| | SEC. 713.13 FLORIDA STATUTE. (REPEAT COMMENT. NOT |
| | PROVIDED). |
| | |
| | 6- SPECIFY HOW ROOFCROSS VENTILATION IS ACHIEVED TO |
| | COMPLY WITH SEC. R806 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | (REPEAT COMMENT. NOT ADDRESSED). |
| | |
| | 7- IF ENGINEERINGSHEETS ARE REVISED, THEN PLEASE |
| | REMOVEOLD SHEETSAND INSERT NEW SHEETS. |
| | |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |