Plan Review Notes
Plan Review Notes For Permit 07070920
Permit Number 07070920
Review Stop B
Sequence Number 2
Notes
Date Text
2007-11-29 09:20:59SECONDBUILDING REVIEW CHECKLIST FOR NEW RESIDENTIAL
 ADDITION.
 REVIEW DONE UNDERFBC 2004 WITH 2007 REVISIONS.
  
 1- SOIL TEST REPORT TO HAVE ENGINEERING FIRM
 CERTIFICATE OF AUTHORIZATION NUMBER AS REQUIRED BY
 FLORIDA ADMINISTRATIVE CODE SEC. 61G15-23.002(2).
  
 2- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) FLAT ROOF ASSEMBLY TO BE USED. SEE ATTACHED COPY
 OF CITY POLICY FOR ROOFING PERMITS AND REQUIRED
 INFORMATION.
 CLEARLYCIRCLE SPECIFIC APPROVED ASSEMBLY TO BE
 INSTALLED AND SPECIFIC FASTENING OPTION IF MORE THAN
 ONE OPTION IS LISTED.IN ADDITION,IF SELECTED
 ASSEMBLY IS LIMITED BY GENERAL LIMITATION #7, THEN
 PROVIDE THE REQUIRED RAS 117 CALCULATIONS FOR NAIL
 ENHANCING AT PERIMETER AND CORNER AREAS.THESE
 CALCULATIONS MAY BE REQUIRED TO BE PERFORMED ONLY BY
 ARCHITECT, ENGINEER OR REGISTERED ROOF CONSULTANT. SEE
 LAST PAGE OF PRODUCT APPROVAL TO SEE WHO'S MUST DO THE
 CALCULATIONS.
 ON THE OTHER HAND IF SELECTED ASSEMBLY IS LIMITED BY
 GENERAL LIMITATION #9, THEN, IT CAN'T BE USED IN THIS
 AREA BECAUSE NAIL ENHANCING IT'S NOT ALLOWED TO
 INCREASE THE UPLIFT CAPACITY OF THE ROOF ASSEMBLY. SEE
 GENERAL LIMITATION #9.(REPEAT COMMENT. INFORMATION
 WAS NOT PROVIDED AT ALL).
  
 B) ALL STRUCTURAL SIMPSON CONNECTORS SPECIFIED ON
 PLANS AND DETAILS. PROVIDE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE WHERE CONNECTOR IS SHOWN ONLY. GO
 TO WWW.FLORIDA BUILDING.ORG TO DOWNLOAD CORRESPONDING
 INFORMATION. (REPEAT COMMENT. INFORMATION WAS NOT
 PROVIDED AT ALL).
  
 C)"INSWING" DOOR EXTERIOR DOOR AS SHOWN ON NEW
 UTILITY FLOOR PLAN . PRODUCT APPROVAL SUBMITTED IS FOR
 AN "OUTSWING" DOOR.
  
 ***NOTE: IF DOOR IS CHANGED FOR AN "OUTSWING" DOOR,
 THEN KEEP IN MIND THAT COMPLIANCE WITH SECTION R311.4.3
 OF 2004 FLORIDA RESIDENTIAL CODE IS REQUIRED.
  
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
 (REPEAT COMMENT. NOT ADDRESSED BY THE ENGINEER OF
 RECORD).
  
 4- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 13-600.1.C.1.
 NOTE: MAKE SURE CORRECT 2006 REVISED FORM IS USED.
 (REPEAT COMMENT.INFORMATION WAS NOT SUBMITTED AT
 ALL).
  
 5- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE. (REPEAT COMMENT. NOT
 PROVIDED).
  
 6- SPECIFY HOW ROOFCROSS VENTILATION IS ACHIEVED TO
 COMPLY WITH SEC. R806 OF 2004 FLORIDA RESIDENTIAL CODE.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 7- IF ENGINEERINGSHEETS ARE REVISED, THEN PLEASE
 REMOVEOLD SHEETSAND INSERT NEW SHEETS.
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712