| 2007-08-08 18:17:17 | FIRST BUILDING REVIEW CHECKLIST FOR NEW RESIDENTIAL |
| | ADDITION. |
| | REVIEW DONE UNDER FBC 2004 RESIDENTIAL CODEAND FBC |
| | 2004. |
| | |
| | 1- PROVIDE SOIL TEST REPORT AS REQUIRED ON ENGINEER |
| | FOUNDATION NOTE #3 ON SHEET 2 OF 19. |
| | |
| | 2- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| | 9B-72 FOR: |
| | A) FLAT ROOF ASSEMBLY TO BE USED. SEE ATTACHED COPY |
| | OF CITY POLICY FOR ROOFING PERMITS AND REQUIRED |
| | INFORMATION. |
| | CLEARLYCIRCLE SPECIFIC APPROVED ASSEMBLY TO BE |
| | INSTALLED AND SPECIFIC FASTENING OPTION IF MORE THAN |
| | ONE OPTION IS LISTED.IN ADDITION,IF SELECTED |
| | ASSEMBLY IS LIMITED BY GENERAL LIMITATION #7, THEN |
| | PROVIDE THE REQUIRED INFORMATION. SEE LAST PAGE OF |
| | PRODUCT APPROVAL TO SEE WHAT'S THE REQUIRED |
| | INFORMATION. |
| | ON THE OTHER HAND IF SELECTED ASSEMBLY IS LIMITED BY |
| | GENERAL LIMITATION #9, THEN, IT CAN'T BE USED IN THIS |
| | AREA BECAUSE NAIL ENHANCING IT'S NOT ALLOWED TO |
| | INCREASE THE UPLIFT CAPACITY OF THE ROOF ASSEMBLY. |
| | |
| | B) ALL STRUCTURAL SIMPSON CONNECTORS SPECIFIED ON |
| | PLANS AND DETAILS. |
| | |
| | |
| | 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 4- PLANS TO SPECIFY CONSTRUCTIONTYPE AS REQUIRED BY |
| | SEC. 602.1 FBC 2004. |
| | |
| | 5- PROVIDE COMPLETE SPECS AND DETAILS FOR HANDRAILS AND |
| | STEPSTO VERIFY COMPLIANCE WITH SECTION R311.5OF |
| | 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 6- ARCHITECTURAL PLANS AND ENGINEER'S PLANS DON'T |
| | MATCH.EG:SEE STEPS,FOOTINGS,ETC. REVISE AS |
| | REQUIRED TO MATCH. |
| | ALSO, PROVIDE ALL DIMENSIONS. |
| | |
| | 7- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | 13-600.1.C.1. |
| | NOTE: MAKE SURE CORRECT 2006 REVISED FORM IS USED. |
| | |
| | 8- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD |
| | (561)233-5115)TO VERIFY IF IMPACT FEES ARE DUE OR |
| | NOT. BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT |
| | IF IMPACT FEES ARE DUE. |
| | |
| | 9- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| | SEC. 713.13 FLORIDA STATUTE. |
| | |
| | 10- SPECIFY HOW ROOFCROSS VENTILATION IS ACHIEVED TO |
| | COMPLY WITH SEC. R806 OF 2004 FLORIDA RESIDENTIAL |
| | CODE. |
| | |
| | 11- ARCHITECTURAL PLANS ARE WRONG. WEST ELEVATIONS IS |
| | SHOWN AS A PARTIAL BUILDING SECTION, NOT AS AN |
| | ELEVATION.SAME THING APPLIES TO SOUTH ELEVATION. |
| | CLARIFY DRAWINGS AS REQUIRED. |
| | |
| | 12- PROVIDE COMPLETE SPECIFICATIONS FOR ROOF EAVE |
| | CONSTRUCTION. SEC. 106.1.2 CITY AMENDMENTS TO FBC |
| | 2004. |
| | |
| | 13- SPECIFY ROOF SLOPE AS REQUIRED BY SEC. R905.11.1 OF |
| | 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 14- ROOF SHEATHING SIZE SHOWN ON ARCHITECTURAL PLANS |
| | DON'T MATCH SPECIFICATIONS SHOWN ON ENGINEERING PLANS |
| | SHEET 14 OF 19. REVISE AS REQUIRED. |
| | |
| | 15- ARCHITECTURAL PLANS AND NOTES AND ENGINEERING PLANS |
| | AND NOTES NEED TO BE COORDINATED TO AVOID CONFLICT OR |
| | CONFUSION. REVISE AS REQUIRED BOTH SETS OF PLANS TO |
| | MATCH. |
| | |
| | 16- ARCHITECTURAL PLANS TO HAVE DESIGNER NAME AND |
| | SIGNATURE AS REQUIRED BY SEC. 106.1.3 CITY AMENDMENTS |
| | TO FBC 2004. |
| | |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |