| 2007-07-31 14:44:46 | *** DENIED *** |
| | 1) ENERGY CALCULATIONS LINE 9A-1 SHOWS R-4.5, SEE |
| | SECOND PAGE OF ENERGY CAL'S. TABLE 6C-1 MINIMUM IS R-5, |
| | PLEASE CORRECT PER 2004 FBC 13-600.1.C. |
| | |
| | 2) ENERGY CAL'S. LINE 9B-2 SHOWS R-13, SEE TABLE 6C-1 |
| | MINIMUM IS R-11 FOR ALL 2X4 FRAME WALLS (EXTERIOR AND |
| | ADJACENT), PLEASE CORRECT PER 2004 FBC 13-602.1.C. |
| | |
| | 3) PLANS PAGE FOR TYPICAL WALL SECTION SHOWS R-19 BATT |
| | INSULATION FOR KNEE WALLS. KNEEWALLS ARE CEILING AREA |
| | AND NEED R-30 INSULATION, PLEASE CORRECT PER 2004 FBC |
| | 13-604.1.A.2. |
| | |
| | 4) PLANS PAGE FOR TYPICAL WALL SECTION SHOWS R-3 |
| | INSULATION BETWEEN FURRING STRIPS. TABLE 6C-1 MINIMUM |
| | IS R-5, PLEASE CORRECT PER 2004 FBC 13-600.1.C. |
| | |
| | 5) PLANS PAGE MECHANICAL PLAN SHOWS R-11 INSULATION SEE |
| | FRONT PAGE OF ENERGY CALCULATIONS LINE 9B-2 SHOWS R-13, |
| | PLEASE CORRECT. |
| | |
| | 6) INFORMATION MISSING IN TITLE BLOCK FOR ARCHITECT ( |
| | ARCHITECT LICENSE NUMBER) SEE FAC 61G1-16.004 TITLE |
| | BLOCK. |
| | A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR |
| | INTERIOR DESIGN DRAWINGS AND SPECIFICATION |
| | IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A |
| | MINIMUM, CONTAIN THE FOLLOWING INFORMATION: |
| | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. |
| | (2) FIRM LICENSE NUMBER. |
| | (3) NAME OR IDENTIFICATION OF PROJECT. ("JOB ADDRESS" |
| | SEE CITY WPB AMEND. 106.1.1). |
| | (4) DATE PREPARED. |
| | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. |
| | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING |
| | THE DOCUMENT. |
| | |