Plan Review Notes
Plan Review Notes For Permit 07070910
Permit Number 07070910
Review Stop M
Sequence Number 1
Notes
Date Text
2007-07-31 14:44:46*** DENIED ***
 1) ENERGY CALCULATIONS LINE 9A-1 SHOWS R-4.5, SEE
 SECOND PAGE OF ENERGY CAL'S. TABLE 6C-1 MINIMUM IS R-5,
 PLEASE CORRECT PER 2004 FBC 13-600.1.C.
  
 2) ENERGY CAL'S. LINE 9B-2 SHOWS R-13, SEE TABLE 6C-1
 MINIMUM IS R-11 FOR ALL 2X4 FRAME WALLS (EXTERIOR AND
 ADJACENT), PLEASE CORRECT PER 2004 FBC 13-602.1.C.
  
 3) PLANS PAGE FOR TYPICAL WALL SECTION SHOWS R-19 BATT
 INSULATION FOR KNEE WALLS. KNEEWALLS ARE CEILING AREA
 AND NEED R-30 INSULATION, PLEASE CORRECT PER 2004 FBC
 13-604.1.A.2.
  
 4) PLANS PAGE FOR TYPICAL WALL SECTION SHOWS R-3
 INSULATION BETWEEN FURRING STRIPS. TABLE 6C-1 MINIMUM
 IS R-5, PLEASE CORRECT PER 2004 FBC 13-600.1.C.
  
 5) PLANS PAGE MECHANICAL PLAN SHOWS R-11 INSULATION SEE
 FRONT PAGE OF ENERGY CALCULATIONS LINE 9B-2 SHOWS R-13,
 PLEASE CORRECT.
  
 6) INFORMATION MISSING IN TITLE BLOCK FOR ARCHITECT (
 ARCHITECT LICENSE NUMBER) SEE FAC 61G1-16.004 TITLE
 BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT. ("JOB ADDRESS"
 SEE CITY WPB AMEND. 106.1.1).
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  