| 2007-08-14 15:11:52 | 2004 FBC W/2007 REVISIONS |
| | LEVEL 2 / ADDITION |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| | MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) PLEASE NUMBER OR OTHERWISE IDENTIFY THE PLAN SHEETS. |
| | FBC* 106.1.3 AMENDED BY THE CITY OF WPB. |
| | |
| | 4) SPECIFY THE LEVEL OF ALTERATION ON THE PLANS. SEE |
| | 2004 FBC EXISTING BUILDING. |
| | |
| | 5) SHOW COMPLIANCE WITH R309.1 OPENING PROTECTION. |
| | OPENINGS FROM A PRIVATE GARAGE DIRECTLY INTO A ROOM |
| | USED FOR SLEEPING PURPOSES SHALL NOT BE PERMITTED. |
| | OTHER OPENINGS BETWEEN THE GARAGE AND RESIDENCE SHALL |
| | BE EQUIPPED WITH SOLID WOOD DOORS NOT LESS THAN 1 3 / 8 |
| | INCHES (35 MM) IN THICKNESS, SOLID OR HONEYCOMB CORE |
| | STEEL DOORS NOT LESS THAN 1 3 / 8 INCHES (35 MM) THICK, |
| | OR 20-MINUTE FIRE-RATED DOORS. SPECIFY ON THE PLANS |
| | THAT THE OFFICE IS NOT TO BE USED FOR SLEEPING PURPOSES |
| | AND INDICATE THE DOOR TYPE. |
| | |
| | 6) SPECIFY THE BOTTOM CORD LIVE LOAD FOR THE TRUSSES ON |
| | THE PLANS. SEE TABLE R301.5. |
| | |
| | 7) REVISE THE ROOF SHEATHING FASTENING NOTES TO REQUIRE |
| | 8D RING SHANK NAILS FOR ALL ROOF ZONES. SEE |
| | R803.2.3.1. |
| | |
| | 8) THE TRUSS ANCHOR IDS SPECIFIED ON THE ROOF TRUSS |
| | PLAN DO NOT CORRESPOND WITH THE SIMPSON TRUSS ANCHOR |
| | SCHEDULE, WHICH ONLY LISTS TRUSS HANGERS. PLEASE |
| | CLARIFY. |
| | |
| | 9) REVISE THE DESIGN DATA TO SPECIFY EXPOSURE CATEGORY |
| | 'C'. R301.2.1.4 EXPOSURE CATEGORY. 3. EXPOSURE C. 3. |
| | EXPOSURE C. OPEN TERRAIN WITH SCATTERED OBSTRUCTIONS, |
| | INCLUDING SURFACE UNDULATIONS OR OTHER IRREGULARITIES, |
| | HAVING HEIGHTS GENERALLY LESS THAN 30 FEET (9144 MM) |
| | EXTENDING MORE THAN 1,500 FEET (457.2 M) FROM THE |
| | BUILDING SITE IN ANY QUADRANT. THIS EXPOSURE SHALL ALSO |
| | APPLY TO ANY BUILDING LOCATED WITHIN EXPOSURE B-TYPE |
| | TERRAIN WHERE THE BUILDING IS DIRECTLY ADJACENT TO OPEN |
| | AREAS OF EXPOSURE C-TYPE TERRAIN IN ANY QUADRANT FOR A |
| | DISTANCE OF MORE THAN 600 FEET (182.9 M). SHORT-TERM |
| | (LESS THAN TWO YEAR) CHANGES IN THE PRE-EXISTING |
| | TERRAIN EXPOSURE, FOR THE PURPOSES OF DEVELOPMENT, |
| | SHALL NOT BE CONSIDERED OPEN FIELDS. WHERE DEVELOPMENT |
| | BUILD OUT WILL OCCUR WITHIN THREE YEARS AND THE |
| | RESULTANT CONDITION WILL MEET THE DEFINITION OF |
| | EXPOSURE B, EXPOSURE B SHALL BE REGULATING FOR THE |
| | PURPOSE OF PERMITTING. THIS CATEGORY INCLUDES FLAT OPEN |
| | COUNTRY, GRASSLANDS AND OCEAN OR GULF SHORELINES. THIS |
| | CATEGORY DOES NOT INCLUDE INLAND BODIES OF WATER THAT |
| | PRESENT A FETCH OF 1 MILE (1.61 KM) OR MORE OR INLAND |
| | WATERWAYS OR RIVERS WITH A WIDTH OF 1 MILE (1.61 KM) OR |
| | MORE (SEE EXPOSURE D). |
| | |
| | 10) REVISE THE WINDOW BUCK DETAIL TO COMPLY WITH FBC |
| | 1714.5.4.2, WHICH REQUIRES THE BUCK TO EXTEND BEYOND |
| | THE INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT |
| | FULL SUPPORT OF THE FRAME IS PROVIDED. |
| | |
| | 11) SPECIFY THE SIZE OF THE GARAGE DOOR ON THE PLANS. |
| | FBC* 106.1.2 AMENDED. |
| | |
| | 12)WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 13) THE MAXIMUM DOOR HEIGHT ALLOWED BY THE PREMDOR |
| | PRODUCT APPROVAL IS 6'-8" AND AN 8'-0" DOOR IS |
| | SPECIFIED ON THE PLANS. SUBMIT CORRECT PRODUCT |
| | APPROVAL. |
| | |
| | 14) SPECIFY WHICH ONE OF THE ATTACHMENT METHODS LISTED |
| | IN THE HANSON ROOF TILE NOA WILL BE USED FOR |
| | INSTALLATION. CIRCLE THE APPROPRIATE ITEM ON THE NOA. |
| | |
| | 15) SUBMIT PRODUCT APPROVALS FOR THE SIMPSON TRUSS AND |
| | WALL CONNECTORS AS REQUIRED BY FAC RULE 9B-72. |
| | |
| | 16) SUBMIT A KEY PLAN AND INSTALLATION SCHEDULE FOR THE |
| | STORM PANELS. SPECIFY THE MOUNT TYPE, FASTENER TYPE, |
| | FASTENER SPACING, SPANS, EDGE DISTANCE, GLASS |
| | SEPARATION DISTANCE, ETC. |
| | SEE ATTACHED SAMPLE INSTALLATION SCHEDULE. |
| | |