| Plan Review Notes For Permit 07070893 |
| Permit Number |
07070893 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-09-18 12:24:50 | *****DENIED***** | | | | | | | | | 1.THE NUMERICAL ADDRESS OF THE PROJECT SITE SHALL BE | | | IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.SEE | | | SHEET C-1,L-1 AND L-2. | | | | | | 2.PLAN SHEETS L-1 AND L-2 REFER TO WAL-MART INSTEAD | | | OF SAM'S CLUB. | | | | | | 2.NO LEGEND TO CLEARLY IDENTIFY FIRE HYDRANTS.SHOW | | | THE LOCATION OF THE FIRE HYDRANTS. | | | | | | 3.PLEASE INDICATE IF THE SCOPE OF WORK WILL CAUSE | | | FIRE HYDRANT(S) TO BE RE-LOCATED. | | | | | | 4. THE EXISTING FUELING STATION ANDMCDONALD'S ARE | | | SHOWN ON SHEET C-1, BUT ARE NOT LOCATED ON SHEET C-2. | | | WILL OR HAVE THESE STRUCTURES BEEN REMOVED?DOES THE | | | PROPOSED RETENTION PONDOF 0.98 ACRES BE IN THE PLACE | | | WHERE MCDONALD'S IS/WAS? | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW EACH ITEM WAS ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|