| Plan Review Notes For Permit 07070844 |
| Permit Number |
07070844 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-08-31 13:18:53 | BUILDING REVIEW FIRST CHECKLIST. | | | REVIEW DONE UNDER FBC 2004 WITH 2007 REVISIONS. | | | | | | 1- SPECIFY WINDOW SIZES. SEC. 106.1.2 CITY AMENDMENTS | | | TO FBC 2004. | | | | | | 2-MEAN ROOF HEIGHT IS ABOVE 60'-0" THEREFORE NEED | | | PROVIDE ENGINEERED CALCULATIONS FOR THE DESIGN | | | PRESSURES AS REQUIRED BY SEC. 1603.1.4OF FBC 2004. | | | CALCULATIONS TO BE SIGNED AND SEALED AS REQUIRED BY | | | CHAPTER 471 OR CHAPTER 481 FLORIDA STATUTES. | | | | | | 3- A) PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE | | | 9B-72 FOR WINDOWS THAT MEET THE DESIGN PRESSURES | | | CALCULATED ON ITEM 2 ABOVE. NOA 04-0714.06 SUBMITTED | | | EXPIRED ON SEPTEMBER 30, 2006. NEED TO PROVIDE CURRENT | | | PRODUCT APPROVAL. | | | | | | B)IF THERE ARE ANY WINDOW MULLIONS TO BE | | | INSTALLED, THEN PRODUCT APPROVAL IS REQUIRED ALSO. | | | AND,CLEARLY MARK SPECIFIC MULLION SIZE AND FASTENING | | | TO VERIFY COMPLIANCE WITH THE CALCULATED DESIGN | | | PRESSURES ON ITEM TWO ABOVE. SEC. 106.1.2 CITY | | | AMENDMENTS TO FBC 2004. | | | | | | 4- DESIGN PROFESSIONAL TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|