| Date |
Text |
| 2007-12-01 05:11:28 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | MUNICIPAL CODES |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. ALL ARCHITECTURAL SHEETS SHALL INCLUDE THE FIRM |
| | LICENSE NUMBER, (CERTIFICATE OF AUTHORIZATION), IN THE |
| | TITLE BLOCK OF EACH SHEET. FAC 61G1-16.004(2) & FS |
| | 481.219, 481.2055. |
| | ****NO RESPONSE, BUT ONLY THE SHEETS CHANGED OUT HAVE |
| | THE FIRM LICENSE NUMBER IN THE TITLE BLOCK. ALL SHEETS |
| | SHALL SHOW THE FIRM LICENSE NUMBER IN THE TITLE BLOCK. |
| | |
| | |
| | 2. SHT A-102 TOILET ROOM 116 INDICATES TWO TOILET |
| | STALLS, BUT ONLY ONE W/C IS SHOWN. PLEASE CLARIFY. |
| | SECTION 106.1.1. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 3. ST A-104 EQUIPMENT SCHEDULE #36, X-RAY FILM |
| | PROCESSOR. AN INTERCEPTOR AND/OR A NEUTRALIZER TANK MAY |
| | BE REQUIRED. PLEASE CONTACT RODNEY COMPO, (561) |
| | 822-2272, E-MAIL [email protected], OR CALVIN WILLIAMS, |
| | (561) 822-2284, E-MAIL [email protected]. THEIR FAX |
| | NUMBER IS (561) 822-2287. PLEASE SUBMIT A DETERMINATION |
| | FROM ENVIRONMENTAL COMPLIANCE INDICATING REQUIREMENTS, |
| | IF ANY, FOR FOR AN INTERCEPTOR OR A NEUTRALIZER TANK, |
| | OR A WAIVER. MUNICIPAL CODE ARTICLE III SECTION |
| | 90-125(B)(1)(2). |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 4. SHT A-105 FINISH LEGEND. CLARIFICATION REQUIRED. |
| | WILL ALL TOILET ROOMS HAVE A F3 SURFACE ON THE FLOORS? |
| | --ARE ALL WALLS IN THE NEW TOILET ROOMS TO BE |
| | GLASSBOARD? IF SO THE WALLS WITHIN 2' OF THE W/C'S |
| | SHALL HAVE A "SMOOTH, HARD, NONABSORBENT SURFACE". |
| | PLEASE SUBMIT MANUF. SPECIFICATIONS FOR THE GLASSBOARD. |
| | SHOW COMPLIANCE WITH SECTION 1210.2. |
| | ****NO RESPONSE, NOT ADDRESSED |
| | |
| | 5. SHT A-202 DETAIL 5E. THE GARBAGE DISPOSAL SHALL BE |
| | ADA APPROVED. PLEASE SUBMIT THE MANUF. SPECIFICATION |
| | SHEETS. GARBAGE DISPOSAL SHALL NOT INTRUDE INTO THE |
| | CLEAR FLOOR SPACE REQUIRED FOR THE SINK. |
| | ****NO RESPONSE, NOT ADDRESSED |
| | |
| | 6. OK |
| | |
| | 7. OK |
| | |
| | **********NEW COMMENT********** |
| | |
| | 1B. SEE ATTACHED SHEET CONCERNING THE DESIGN |
| | PROFESSIONAL AND FS 553.80(2)(B). THIS IS GIVEN ONLY AS |
| | A NOTICE AT THIS TIME. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE ONE |
| | SET OF THEM LOOSELY ON TOP OF THE COLLATED |
| | PLANS TO BE REVIEWED. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | ****NO RESPONSE, NOT ADDRESSED BY THE ARCHITECT. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |