| 2007-09-18 14:36:10 | *****DENIED***** |
| | |
| | |
| | 01.NFPA 101 - 2003 EDITION AND THE FLORIDA FIRE |
| | PREVENTION CODE - 2004 EDITION SHALL BE REFERENCED. |
| | |
| | 02.INDEX TO DRAWINGS SHOWN ON SHEET A-000 SHOW NO |
| | REFERENCE TO ELECTRICAL, PLUMBING, OR MECHANICAL |
| | SHEETS. |
| | |
| | 03.THE SUITE NUMBER SHALL BE INCLUDED WITH THE |
| | NUMERICAL ADDRESS LOCATED IN THE TITLE BLOCK OF EACH |
| | SUBMITTED PLAN SHEET. |
| | |
| | 04.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 05.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER |
| | ACCESS TO OR EGRESS FROM THE PROPERTY OR VICINITY |
| | THEREOF (INCLUDING FIRE LANES). |
| | |
| | 06.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS |
| | SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT |
| | OR MORE FREQUENLTLY AS NECESSARY FOR SAFE OPERATIONS. |
| | |
| | 07.SPECIFY THE INTERIOR FINISH MATERIAL |
| | CLASSIFICATION FOR THE EXITS, EXIT AISLE CORRIDORS, AND |
| | ALL OTHER SPACES IN TERMS OF CLASS A, CLASS B, OR CLASS |
| | C. |
| | |
| | 08.PLEASE AMEND OR CLARIFY DISCREPANCIES SHOWN IN THE |
| | ESCAPE PLAN (SHEET A-000) AS COMPARED TO OTHER PLAN |
| | SHEETS' EXIT DOORS (I.E. SHEET A-102, E-2). |
| | A. EXIT DOOR 108A (A-102) NOT SHOWN AS AN EXIT ON |
| | ESCAPE PLAN (A-000) B.DOOR 145A (A-102) IS SHOWN |
| | AS A MEANS OF EGRESS (A-100) BUT NOT MARKED AS AN EXIT |
| | (E-2). C.A MEANS OF EGRESS THROUGH THE WAITING |
| | AREA #100 (A-000) BUT NO EXIT DOOR IS SHOWN (E-102). D. |
| | DOOR 130B (A-102) IS SHOWN AS A MEANS OF EGRESS (A-100) |
| | BUT NOT MARKED AS AN EXIT (E-2) |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE ON THE PLAN EACH ITEM WAS |
| | ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |
| | |
| | |