| Plan Review Notes For Permit 07070800 |
| Permit Number |
07070800 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-09-28 11:51:50 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) AS REQUESTED IN LAST REVIEW 8-2-07 NOTE #2. PLEASE | | | SUBMIT COOLING LOAD CALCULATIONS, SEE 2004 FBC | | | 13-407.1.ABC.1. WHAT WAS SUBMITTED WERE ENERGY | | | CALCULATIONS NOT COOLING LOAD CALCULATIONS. | | | | | | 2) PAGE AC-2 ON ONE SET OF PLANS WERE NOT SEALED BY THE | | | ENGINEER, SEE F.A.C. 61G15-23.002, PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|