| 2007-10-04 15:06:55 | BUILDING PLAN REVIEW |
| | PERMIT: 07070800 |
| | ADD: 1700 PBL BLVD #130 |
| | CONT: HOLT LEE CONST. INC. |
| | TEL: (954)725-4881 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 2ND |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) OK |
| | |
| | 3) OK |
| | |
| | 4)SHEETS D1 AND D2 IS MISSING THE PRINTED NAME AND |
| | NUMBER OF THE PERSON SEALING THE PLANS. |
| | FAC. 61G1-16.004 |
| | |
| | 5)OK |
| | |
| | 6)OK |
| | |
| | 7)OK |
| | |
| | 8)OK |
| | |
| | 9)OK |
| | |
| | 10)IF THERE IS A RECEPTIONIST COUNTER, IT SHALL MEET |
| | THE REQUIREMENTS OF FBC. 11-7 WHEREA PORTION OF THE |
| | MAIN COUNTER IS A MINIMUM OF 36 INCHES IN LENGTH AND A |
| | MAXIMUM HEIGHT OF 36 INCHES. |
| | **NOTED** |
| | IF THERE IS A WINDOW NEXT TO THE WAITING ROOM WHERE |
| | CUSTOMERS HAVE TO USE, IT SHALL MEET THE REQUIREMENTS |
| | OF SECTION 11-7. WALL TYPE ?C? ON SHEET D1 SHALL BE A |
| | MAXIMUM HEIGHT OF 36 INCHES. THE DESIGN OF ALL AREAS |
| | USED FOR BUSINESS TRANSACTIONS WITH THE PUBLIC SHALL |
| | COMPLY WITH SECTION 11-7. PROVIDE AN ELEVATION DETAIL |
| | DRAWING OF THE AREA WHERE THE WINDOW OR OPENING WILL BE |
| | INSTALLED. ANY GLASS USED IN THIS AREA SHALL BE |
| | SAFETY/TEMPERED GLASS. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |