2007-10-04 15:06:55BUILDING PLAN REVIEW
 PERMIT: 07070800
 ADD: 1700 PBL BLVD #130
 CONT: HOLT LEE CONST. INC.
 TEL: (954)725-4881
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) OK
  
 3) OK
  
 4)SHEETS D1 AND D2 IS MISSING THE PRINTED NAME AND
 NUMBER OF THE PERSON SEALING THE PLANS.
 FAC. 61G1-16.004
  
 5)OK
  
 6)OK
  
 7)OK
  
 8)OK
  
 9)OK
  
 10)IF THERE IS A RECEPTIONIST COUNTER, IT SHALL MEET
 THE REQUIREMENTS OF FBC. 11-7 WHEREA PORTION OF THE
 MAIN COUNTER IS A MINIMUM OF 36 INCHES IN LENGTH AND A
 MAXIMUM HEIGHT OF 36 INCHES.
 **NOTED**
 IF THERE IS A WINDOW NEXT TO THE WAITING ROOM WHERE
 CUSTOMERS HAVE TO USE, IT SHALL MEET THE REQUIREMENTS
 OF SECTION 11-7. WALL TYPE ?C? ON SHEET D1 SHALL BE A
 MAXIMUM HEIGHT OF 36 INCHES. THE DESIGN OF ALL AREAS
 USED FOR BUSINESS TRANSACTIONS WITH THE PUBLIC SHALL
 COMPLY WITH SECTION 11-7. PROVIDE AN ELEVATION DETAIL
 DRAWING OF THE AREA WHERE THE WINDOW OR OPENING WILL BE
 INSTALLED. ANY GLASS USED IN THIS AREA SHALL BE
 SAFETY/TEMPERED GLASS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]