Plan Review Notes
Plan Review Notes For Permit 07070800
Permit Number 07070800
Review Stop M
Sequence Number 1
Notes
Date Text
2007-08-02 14:05:26*** DENIED ***
 1) INFORMATION MISSING FROM TITLE BLOCK. (MAG
 ENGINEERING INC. CA# 70615 IS NOT LISTED WITH DBPR,
 PLEASE CORRECT)
 SEE FAC 61G15-23.002 (2)A TITLE BLOCK ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT.
  
 2) PLEASE SUBMIT COOLING LOAD CALCULATIONS, SEE 2004
 FBC 13-407.1.ABC.1.
  
 3) SHOW ON MECHANICAL PLAN HOW RETURN AIR IS GETTING BY
 THE CEILING TO THE OPEN PLENUM ABOVE TO GET BACK TO HP
 UNITS, SEE 2004 FBC/M 601.4.
  
 4) THE EXHAUST DUCTS FOR EF-1 AND 2 CAN NOT BE IN THE
 OPEN PLENUM, PER 2004 FBC/M 601.3 CONTAMINATION
 PREVENTION.
 EXHAUST DUCTS UNDER POSITIVE PRESSURE, CHIMNEYS, AND
 VENTS SHALL NOT EXTEND INTO OR PASS THROUGH DUCTS OR
 PLENUMS. PLEASE CORRECT.
  
 5) PLEASE SHOW ON THE MECHANICAL PLANS IF THE EXISTING
 EXHAUST DUCTS ARE POSITIVE OR NEGATIVE PRESSURE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.