| Plan Review Notes For Permit 07070800 |
| Permit Number |
07070800 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-08-02 14:05:26 | *** DENIED *** | | | 1) INFORMATION MISSING FROM TITLE BLOCK. (MAG | | | ENGINEERING INC. CA# 70615 IS NOT LISTED WITH DBPR, | | | PLEASE CORRECT) | | | SEE FAC 61G15-23.002 (2)A TITLE BLOCK ON EACH SHEET | | | CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE | | | NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND | | | LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS | | | AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE | | | ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT. | | | | | | 2) PLEASE SUBMIT COOLING LOAD CALCULATIONS, SEE 2004 | | | FBC 13-407.1.ABC.1. | | | | | | 3) SHOW ON MECHANICAL PLAN HOW RETURN AIR IS GETTING BY | | | THE CEILING TO THE OPEN PLENUM ABOVE TO GET BACK TO HP | | | UNITS, SEE 2004 FBC/M 601.4. | | | | | | 4) THE EXHAUST DUCTS FOR EF-1 AND 2 CAN NOT BE IN THE | | | OPEN PLENUM, PER 2004 FBC/M 601.3 CONTAMINATION | | | PREVENTION. | | | EXHAUST DUCTS UNDER POSITIVE PRESSURE, CHIMNEYS, AND | | | VENTS SHALL NOT EXTEND INTO OR PASS THROUGH DUCTS OR | | | PLENUMS. PLEASE CORRECT. | | | | | | 5) PLEASE SHOW ON THE MECHANICAL PLANS IF THE EXISTING | | | EXHAUST DUCTS ARE POSITIVE OR NEGATIVE PRESSURE. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|