| Plan Review Notes For Permit 07070800 |
| Permit Number |
07070800 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-08-20 12:16:21 | *****DENIED***** | | | | | | | | | 1.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 3.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER | | | ACCESS TO/EGRESS FROM THE OTHER TENANT SPACES ON THE | | | FLOOR, THE BUILDING, OR THE VICINITY THEREOF. | | | | | | 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR | | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | | | 5.SPECIFY THE INTERIOR FINISH MATERIALS FOR THE NEW | | | WALLS IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | 6.ON SHEET E-2, AMEND FIRE ALARM SYSTEM NOTE #13 TO | | | REFLECT THAT DUCT SMOKE DETECTORS SHALL INITIATE A | | | GENERAL FIRE ALARM (AS PER LOCAL CODES). | | | | | | 7.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR FIRE | | | ALARM AND/OR FIRE SPRINKLER REMODEL. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|