Plan Review Notes
Plan Review Notes For Permit 07070800
Permit Number 07070800
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-08-20 12:16:21*****DENIED*****
  
  
 1.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER
 ACCESS TO/EGRESS FROM THE OTHER TENANT SPACES ON THE
 FLOOR, THE BUILDING, OR THE VICINITY THEREOF.
  
 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 5.SPECIFY THE INTERIOR FINISH MATERIALS FOR THE NEW
 WALLS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 6.ON SHEET E-2, AMEND FIRE ALARM SYSTEM NOTE #13 TO
 REFLECT THAT DUCT SMOKE DETECTORS SHALL INITIATE A
 GENERAL FIRE ALARM (AS PER LOCAL CODES).
  
 7.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR FIRE
 ALARM AND/OR FIRE SPRINKLER REMODEL.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722