| 2007-08-17 13:25:45 | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| | NONE COMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} PAGE #2 OF THE THE INPUT DATA REPORT INDICATES 1 |
| | LUMINAIRE @ 3800 WATTS. PLEASE INDICATE COMPLIANCE WITH |
| | ALL FIXTURES TO BE USED. ALSO SUBMIT A LEGEND OF |
| | FIXTURE TYPES AND WATTAGES ON THE PLAN TO CORRELATE |
| | WITH THE ONES IN THE CALCULATIONS. |
| | |
| | 2} INDICATE COMPLIANCE WITH 13-415.1ABC.1.2, FBC FOR |
| | SPACE CONTROLS FOR LIGHTING." STANDARD SWITCHES ARE |
| | SHOWN ON THE PLAN.SHEET #2 OF THE ENERGY GAUGE ONLY |
| | LISTS 1 FLUORESCENT, AND NOTE THAT ALTHOUGH A MANUAL |
| | CONTROL IS LISTED, IT MUST AUTOMATICALLY TURN LIGHTS |
| | OFF WITHIN 30 MINUTES OF ALL OCCUPANTS LEAVING THE |
| | SPACE PER 13-415.1ABC.1.2(A). DESIGNATE WHICH |
| | MANUFACTURER AND MODELS ARE BEING SPECIFIED FOR THIS |
| | PROJECT BY THE ENGINEER. |
| | |
| | 3}PROVIDE EMERGENCY ILLUMINATION PER |
| | NFPA-101 7.8 (2003), AND CIRCUITED PER |
| | 700.12 NEC. INDICATE SAME ON PLANS. THE BATTERY PACKS |
| | ARE NOT CIRCUITED WITH THE LOCAL, OR ANY,CIRCUIT. |
| | |
| | FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN THE |
| | FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE INDICATE |
| | THE CODE CYCLES UNDER WHICH THIS PLAN WAS DESIGNED. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| | NONE COMPLIANT WITH THE FOLLOWING: |
| | |