Plan Review Notes
Plan Review Notes For Permit 07070780
Permit Number 07070780
Review Stop B
Sequence Number 2
Notes
Date Text
2007-10-05 09:30:41RESIDENTIAL SCREEN ENCLOSURE BUILDING REVIEW SECOND
 CHECKLIST.
 REVIEW DONE UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- IF USING THE AAF GUIDE TO ALUMINUM CONSTRUCTION IN
 HIGH WIND AREAS, THEN CORRECT DESIGN
 PROCEDURE/CHECKLIST SHALL BE USED.FORM SUBMITTED IS
 FOR CHAPTER 5/ATTACHED COVER. CORRECT FORM TO BE USED
 IS FOR CHAPTER 2/ SCREEN ROOMS (WITH SOLID ROOF).ALL
 DETAILS AND TABLES SUBMITTED ARE FROM CHAPTER 2, WHILE
 DESIGN FORM SUBMITTED IS FOR CHAPTER 5.MISMATCHING
 INFORMATION IS NOT ALLOWED.
  
 2- DESIGN PROCEDURE/ CHECKLIST FORM MUST BE COMPLETE IN
 ITS ENTIRETY.FORM SUBMITTED IS MISSING A LOT OF
 INFORMATION. PROVIDE CORRECT FORM WITH ALL BLANKS
 FILLED. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 3- DESIGN PROCEDURE/CHECKLIST SUBMITTED STATES THAT THE
 DESIGNER IS "AAF". THIS IS INCORRECT. NEED TO WRITE
 NAME OF THE ACTUAL DESIGNER WHO IS USING THIS MANUAL.
  
 4- SPECIFY ROOF PITCH. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 5- PRODUCT APPROVAL SUBMITTED IS FOR 4" OR 6" ROOF
 PANELS.DESIGN PROCEDURE/CHECKLIST SUBMITTED STATES 3"
 PANELS. MAKE SURE INFORMATION ON THE DESIGN
 PROCEDURE/CHECKLIST FORMIS COORDINATED WITH THIS
 PRODUCT APPROVAL AND RESPECTIVE TABLES IN CHAPTER 2 OF
 THE DESIGN MANUAL.
  
 6- DRAWINGS TO CLEARLY INDICATE SCREEN ROOM DIMENSIONS
 AND ROOF OVERHANG DIMENSIONS TO VERIFY COMPLIANCE WITH
 PRODUCT APPROVAL AND CHAPTER 2 OF THE ALUMINUM DESIGN
 MANUAL. DRAWINGS SUBMITTED ARE MISSING THESE
 DIMENSIONS. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 7- CLEARLY IDENTIFY ROOM TYPE (I OR II) TO MAKE SURE
 CORRECT TABLES ARE USED.SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004.
  
 8- SPECIFY COLUMN SPACING ON SIDE WALLS OF SCREEN
 ENCLOSURE. DIMENSIONS NO GIVEN IN THE SUBMITTED
 DRAWINGS.
  
 9- SPECIFY SIZE OF DOORS. INFORMATION NO GIVEN IN
 SUBMITTED DRAWINGS. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 10 SPECIFY THE DESIGN WIND PRESSURES FOR ALUMINUM
 SCREEN ENCLOSURES AS REQUIRED BY TABLE 2002.4 OF FBC
 2004.
  
 11- MAKE SURE CORRECT FOOTING SIZE IS USED. DESIGN
 PROCEDURE/CHECKLIST SUBMITTED STATES 8"X8" FOOTING,
 WHILECOPY OF PAGE 2-7 SUBMITTED SHOWS 8"X12" FOOTING
 HIGHLIGHTED. COORDINATE ALL INFORMATION AS REQUIRED TO
 AVOID CONFLICTS. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 12- VALUE DECLARED IN THE PERMIT APPLICATION ($8950.00)
 IS TOO LOW. UPDATE AS REQUIRED BY SEC. 108.3 CITY
 AMENDMENTS TO FBC 2004(REPEAT COMMENT). ADDITIONAL
 FEES WILL BE ACCESSED ACCORDINGLY.
 NOTE: CLARIFY IF DOING COMPLETE CONCRETE SLAB WITH
 CONCRETE EDGE FOOTING FOR SCREEN WALL OR JUST THE
 PERIMETER FOOTING.CONTRACT COPY CALLS FOR 12"X12"
 FOOTER, WHILE ALUMINUM MANUAL PAGE 2-7 SUBMITTED CALLS
 FOR CONCRETE SLAB FOUNDATION & MONOLITHIC FOOTING. ALL
 THIS INFORMATION MUST BE COORDINATED TO AVOID
 CONFLICTS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712