Plan Review Notes
Plan Review Notes For Permit 07070777
Permit Number 07070777
Review Stop E
Sequence Number 3
Notes
Date Text
2007-12-04 12:32:44 
 APPLICATION # 07070777
 ELECTRICAL PLAN REVIEW
 795 BELVEDERE ROAD
 12/4/07
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE
 NOTED.
  
 THE FOLLOWING COMMENTS ARE REPEAT COMMENTS FROM
 8/16/07 REVIEW.
  
 3} 250.24(A)(5) LOAD-SIDE GROUNDING CONNECTIONS A
 GROUNDING CONNECTION SHALL NOT BE MADE TO ANY GROUNDED
 CONDUCTOR ON THE LOAD SIDE OF THE SERVICE DISCONNECTING
 MEANS EXCEPT AS OTHERWISE PERMITTED IN THIS ARTICLE.
 THE RISER HAS GROUNDING AT THE PANELS, IN VIOLATION OF
 THIS ARTICLE AND CREATING PARALLEL GROUNDING PATHS WITH
 THE NEUTRAL.
  
 11} THERE IS NO FIXTURE SCHEDULE TO CONFIRM LIGHTING
 DENSITIES PER CHAPTER 13, TABLE 13-415.2.C.1.
  
 12} INDICATE COMPLIANCE WITH 13-415.1ABC.1.2, FBC FOR
 SPACE CONTROLS FOR LIGHTING." STANDARD SWITCHES ARE
 SHOWN ON THE PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]