| Plan Review Notes For Permit 07070777 |
| Permit Number |
07070777 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-12-04 12:32:44 | | | | APPLICATION # 07070777 | | | ELECTRICAL PLAN REVIEW | | | 795 BELVEDERE ROAD | | | 12/4/07 | | | WEST PALM BEACH, FL. | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND | | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE | | | NOTED. | | | | | | THE FOLLOWING COMMENTS ARE REPEAT COMMENTS FROM | | | 8/16/07 REVIEW. | | | | | | 3} 250.24(A)(5) LOAD-SIDE GROUNDING CONNECTIONS A | | | GROUNDING CONNECTION SHALL NOT BE MADE TO ANY GROUNDED | | | CONDUCTOR ON THE LOAD SIDE OF THE SERVICE DISCONNECTING | | | MEANS EXCEPT AS OTHERWISE PERMITTED IN THIS ARTICLE. | | | THE RISER HAS GROUNDING AT THE PANELS, IN VIOLATION OF | | | THIS ARTICLE AND CREATING PARALLEL GROUNDING PATHS WITH | | | THE NEUTRAL. | | | | | | 11} THERE IS NO FIXTURE SCHEDULE TO CONFIRM LIGHTING | | | DENSITIES PER CHAPTER 13, TABLE 13-415.2.C.1. | | | | | | 12} INDICATE COMPLIANCE WITH 13-415.1ABC.1.2, FBC FOR | | | SPACE CONTROLS FOR LIGHTING." STANDARD SWITCHES ARE | | | SHOWN ON THE PLAN. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|