| Plan Review Notes For Permit 07070777 |
| Permit Number |
07070777 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-11-26 09:10:08 | DENIED; | | | 1.CHANGE 2 # SYSTEM TO .5 # . NO REGULATORS REQUIRED. | | | 2.SHOW SEDIMENT TRAP ON GAS RISER DIAGRAM TO COMPLY | | | WITH FBC FUEL GAS SECTION 408.4. | | | 3. GAS RISER DIAGRAM SHOWFIRE SAFTY VALVE OUT SIDE, | | | DRAWINGS BY FLAMEGUARD FIRE EQUIPMENT SHOWS VALVE TO | | | THE RIGHT OF THE HOOD. IF THE F.S.V. IS TO BE INSTALLED | | | OUTSIDE SUBMIT INSTALLATION INSTRUCTIONS. | | | GAS PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|