2007-08-08 15:04:22PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER
 1 CITY OF WEST PALM BEACH AMENDMENTS.
  
 *** DENIED ***
 1) ENERGY CALCULATIONS STATE THE A/C SYSTEM AS DESIGN
 EFF 13.00, THE MECHANICAL PLANS SHOW AN EXISTING SYSTEM
 8.7 SEER. IF THE A/C SYSTEM IS NOT TO BE CHANGED THEN
 YOU MAY WANT TO USE FORM 400C-04 FOR ENERGY
 CALCULATIONS LISTING ONLY THE ITEMS BEING INSTALLED, OR
 YOU MAY USE FORM 400A-04R AND REPLACE THE A/C SYSTEM.
 SEE 2004 FBC 13-400 ENERGY EFFICIENCY.
  
 2) THE PLAN FOR SHOP DRAWING HOOD "HVAC HOOD 1 OF 1"
 DOES NOT STATE IF THE HOOD IS U.L LISTED OR WHO THE
 MANUFACTURER IS. PLEASE PROVIDE THAT INFORMATION OR
 SHOW ON PLANS THAT THE HOOD COMPLIES WITH 2004 FBC/M
 SECTION 506 THROUGH 508.
  
 3) PLEASE CORRECT PLAN PAGE MP-1 "HVAC PLAN (EXISTING)"
 DETAIL TO SHOW ONLY THE EXISTING CONDITIONS WHICH WOULD
 NOT INCLUDE THE KITCHEN HOOD (ONLY EXISTING
 CONDITIONS). THEN ADD A DETAIL SHOWING PURPOSED
 CONDITIONS WITH THE KITCHEN HOOD.
  
 4) IN THE PURPOSED CONDITIONS SHOW THE A/C SUPPLY AIR
 CFM'S AT ALL SUPPLY AIR GRILLS AND THE BATHROOM EXHAUST
 CFM'S.. PLEASE BE AWARE WHEW CALCULATING THE AIR
 BALANCING OF 2004 FBC 13-409.1.ABC.3.6.1 NONRESIDENTIAL
 KITCHEN SPACES.
 NONRESIDENTIAL KITCHEN SPACE AND AREAS IN DINING ROOMS
 OR OPEN MALLS WHERE A KITCHEN EXHAUST HOOD IS REQUIRED
 BY NFPA 96 SHALL COMPLY WITH THE FOLLOWING
 REQUIREMENTS:
 1.BE DESIGNED WITH AN EXHAUST AIR AND MAKE UP AIR
 BALANCE SUCH THAT THE SPACE IS NEVER UNDER A POSITIVE
 PRESSURE, AND NEVER UNDER A NEGATIVE PRESSURE EXCEEDING
 0.02 INCH W.G. RELATIVE TO ALL INDOOR SPACES
 SURROUNDING THE KITCHEN SPACE, DURING ALL COOKING
 HOURS.
  
 5) PLEASE SHOW ON THE PLAN THE MEANS OF VENTILATION
 (OUT DOOR AIR). PROVIDE CALCULATION IF NATURAL, SEE
 2004 FBC/M 402.2, OR IF MECHANICAL MEAN SEE 403.2..
  
 6) PLEASE SHOW ON PLANS ALL NEW MECHANICAL WORK TO BE
 DONE AS NEW AND EXISTING AS EXISTING.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL: [email protected].