| 2007-08-08 15:04:22 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER |
| | 1 CITY OF WEST PALM BEACH AMENDMENTS. |
| | |
| | *** DENIED *** |
| | 1) ENERGY CALCULATIONS STATE THE A/C SYSTEM AS DESIGN |
| | EFF 13.00, THE MECHANICAL PLANS SHOW AN EXISTING SYSTEM |
| | 8.7 SEER. IF THE A/C SYSTEM IS NOT TO BE CHANGED THEN |
| | YOU MAY WANT TO USE FORM 400C-04 FOR ENERGY |
| | CALCULATIONS LISTING ONLY THE ITEMS BEING INSTALLED, OR |
| | YOU MAY USE FORM 400A-04R AND REPLACE THE A/C SYSTEM. |
| | SEE 2004 FBC 13-400 ENERGY EFFICIENCY. |
| | |
| | 2) THE PLAN FOR SHOP DRAWING HOOD "HVAC HOOD 1 OF 1" |
| | DOES NOT STATE IF THE HOOD IS U.L LISTED OR WHO THE |
| | MANUFACTURER IS. PLEASE PROVIDE THAT INFORMATION OR |
| | SHOW ON PLANS THAT THE HOOD COMPLIES WITH 2004 FBC/M |
| | SECTION 506 THROUGH 508. |
| | |
| | 3) PLEASE CORRECT PLAN PAGE MP-1 "HVAC PLAN (EXISTING)" |
| | DETAIL TO SHOW ONLY THE EXISTING CONDITIONS WHICH WOULD |
| | NOT INCLUDE THE KITCHEN HOOD (ONLY EXISTING |
| | CONDITIONS). THEN ADD A DETAIL SHOWING PURPOSED |
| | CONDITIONS WITH THE KITCHEN HOOD. |
| | |
| | 4) IN THE PURPOSED CONDITIONS SHOW THE A/C SUPPLY AIR |
| | CFM'S AT ALL SUPPLY AIR GRILLS AND THE BATHROOM EXHAUST |
| | CFM'S.. PLEASE BE AWARE WHEW CALCULATING THE AIR |
| | BALANCING OF 2004 FBC 13-409.1.ABC.3.6.1 NONRESIDENTIAL |
| | KITCHEN SPACES. |
| | NONRESIDENTIAL KITCHEN SPACE AND AREAS IN DINING ROOMS |
| | OR OPEN MALLS WHERE A KITCHEN EXHAUST HOOD IS REQUIRED |
| | BY NFPA 96 SHALL COMPLY WITH THE FOLLOWING |
| | REQUIREMENTS: |
| | 1.BE DESIGNED WITH AN EXHAUST AIR AND MAKE UP AIR |
| | BALANCE SUCH THAT THE SPACE IS NEVER UNDER A POSITIVE |
| | PRESSURE, AND NEVER UNDER A NEGATIVE PRESSURE EXCEEDING |
| | 0.02 INCH W.G. RELATIVE TO ALL INDOOR SPACES |
| | SURROUNDING THE KITCHEN SPACE, DURING ALL COOKING |
| | HOURS. |
| | |
| | 5) PLEASE SHOW ON THE PLAN THE MEANS OF VENTILATION |
| | (OUT DOOR AIR). PROVIDE CALCULATION IF NATURAL, SEE |
| | 2004 FBC/M 402.2, OR IF MECHANICAL MEAN SEE 403.2.. |
| | |
| | 6) PLEASE SHOW ON PLANS ALL NEW MECHANICAL WORK TO BE |
| | DONE AS NEW AND EXISTING AS EXISTING. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729 |
| | E-MAIL: [email protected]. |