Plan Review Notes
Plan Review Notes For Permit 07070777
Permit Number 07070777
Review Stop G
Sequence Number 1
Notes
Date Text
2007-08-13 09:37:41DENIED;
 1. FBC-2004 BUILDING CHAPTER 1 ADMINISTRATION CODE
 SECTION 106.1.1 CONSTUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED.
 2. BTU'S FOR EQUIPMENT DO NOT MATCH EQUIPMENT LIST
 SHOWN ON PAGE A1 OF ALTERATION PLANS.
 3. SHOW A FLAT DRAWING OF GAS PIPING ON PLANS WITH
 LOCATION OF EMERGENCY AND SHUTOFF VALVES.
 4. A UNION IS REQUIRED DOWN STREAM OF THE MANUAL
 SHUTOFF VALVE SO EMERGENCYSHUTOFF VALVE NEEDS TO BE
 REPLACED.
 5.SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 6. TYPE OF GAS, (LP OR NATURAL)
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695