2007-08-20 12:53:03*****DENIED*****
  
  
 01.PLEASE INDICATE THE EXISTING AS WELL AS THE
 PROJECTED USE AND OCCUPANCY CLASSIFICATION.
  
 02.PROVIDE THE OCCUPANT LOAD AS DETERMINED BASED UPON
 THE CHARACTERISTICS OF THE OCCUPANCY.
  
 03.NFPA 101-LIFE SAFETY CODE-2003 EDITION,NFPA 70 -
 2005 EDITION,NFPA 72 - 2002 EDITION,NFPA 90A - 2002
 EDITION SHALL BE REFERENCED.(AMEND SHEET E2)
  
 04.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 05.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER
 EMERGENCY ACCESS TO THE SAID PROPERTY OR THE VICINITY
 THEREOF.
  
 06.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 07.ON THE APPROPIATE EXTERIOR ELEVATION, DISPLAY THE
 NUMERICAL ADDRESS ON THE BUILDING FRONTING BELVEDERE
 ROAD.AS PER WEST PALM BEACH CODE, THE NUMBERS SHALL
 BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN
 WIDTH.
  
 08.PROVIDE A LIFE SAFETY PLAN WHICH SHOWS TRAVEL
 DISTANCE TO REACH AN EXIT AND THELOCATION OF FIRE
 EXTINGUISHER(S) WHICH SATISFY THE 75' TRAVEL DISTANCE.
  
 09.COOKING EQUIPMENT SHALL BE PROTECTED IN ACCORDANCE
 WITH NFPA 96 - 2001 EDITION.SEPARATE PLANS AND PERMIT
 WILL BE REQUIRED FOR THE HOOD INSTALLATION AND THE
 HOOD'S SUPPRESSION SYSTEM.
  
 10.SPECIFY THE INTERIOR FINISH MATERIAL MATERIALS FOR
 THE WALLS AND CEILINGS IN TERMS OF CLASS A, CLASS B, OR
 CLASS C.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE IN THE PLANS EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722