| Date |
Text |
| 2007-08-20 12:53:03 | *****DENIED***** |
| | |
| | |
| | 01.PLEASE INDICATE THE EXISTING AS WELL AS THE |
| | PROJECTED USE AND OCCUPANCY CLASSIFICATION. |
| | |
| | 02.PROVIDE THE OCCUPANT LOAD AS DETERMINED BASED UPON |
| | THE CHARACTERISTICS OF THE OCCUPANCY. |
| | |
| | 03.NFPA 101-LIFE SAFETY CODE-2003 EDITION,NFPA 70 - |
| | 2005 EDITION,NFPA 72 - 2002 EDITION,NFPA 90A - 2002 |
| | EDITION SHALL BE REFERENCED.(AMEND SHEET E2) |
| | |
| | 04.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 05.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER |
| | EMERGENCY ACCESS TO THE SAID PROPERTY OR THE VICINITY |
| | THEREOF. |
| | |
| | 06.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS |
| | SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT |
| | OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| | |
| | 07.ON THE APPROPIATE EXTERIOR ELEVATION, DISPLAY THE |
| | NUMERICAL ADDRESS ON THE BUILDING FRONTING BELVEDERE |
| | ROAD.AS PER WEST PALM BEACH CODE, THE NUMBERS SHALL |
| | BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN |
| | WIDTH. |
| | |
| | 08.PROVIDE A LIFE SAFETY PLAN WHICH SHOWS TRAVEL |
| | DISTANCE TO REACH AN EXIT AND THELOCATION OF FIRE |
| | EXTINGUISHER(S) WHICH SATISFY THE 75' TRAVEL DISTANCE. |
| | |
| | 09.COOKING EQUIPMENT SHALL BE PROTECTED IN ACCORDANCE |
| | WITH NFPA 96 - 2001 EDITION.SEPARATE PLANS AND PERMIT |
| | WILL BE REQUIRED FOR THE HOOD INSTALLATION AND THE |
| | HOOD'S SUPPRESSION SYSTEM. |
| | |
| | 10.SPECIFY THE INTERIOR FINISH MATERIAL MATERIALS FOR |
| | THE WALLS AND CEILINGS IN TERMS OF CLASS A, CLASS B, OR |
| | CLASS C. |
| | |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE IN THE PLANS EACH ITEM WAS |
| | ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |