| 2007-08-15 17:49:12 | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS,2005 |
| | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, |
| | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | THE CODE CYCLES REFERENCED ON SHEET E2 ARE INCORRECT, |
| | SEE ABOVE. |
| | |
| | 1} VERIFY THE SERVICE DISCONNECT RATING ( AMPS, VOLTS |
| | AND NUMBER OF PHASES) ON THE RISER DIAGRAM. 215.5 NEC. |
| | |
| | 2} INDICATE THE CONDUIT AND CONDUCTOR SIZES FOR THE |
| | SERVICE, METER, DISCONNECT AND TO THE 400 AMP PANEL. |
| | |
| | 3} 250.24(A)(5) LOAD-SIDE GROUNDING CONNECTIONS A |
| | GROUNDING CONNECTION SHALL NOT BE MADE TO ANY GROUNDED |
| | CONDUCTOR ON THE LOAD SIDE OF THE SERVICE DISCONNECTING |
| | MEANS EXCEPT AS OTHERWISE PERMITTED IN THIS ARTICLE. |
| | THE RISER HAS GROUNDING AT THE PANELS, IN VIOLATION OF |
| | THIS ARTICLE AND CREATING PARRALLEL GROUNDING PATHS |
| | WITH THE NUETRAL. |
| | |
| | 4} PROVIDE A PANEL SCHEDULE FOR EP2. |
| | |
| | 5} VERIFY THAT CIRCUIT EP-1,22 IS 120 VOLLTS AS LISTED |
| | ON THE SCHEDULE (SINGLE POLE BREAKER), 220 VOLTS AS |
| | LISTED ON THE RECEPTALE, AND COMPLIES WITH 422.16 FOR |
| | USE WITH A CORD. ALSO SEE 422.31(B). |
| | |
| | 6} SEE 210.8(B)(2) FOR GFCI REQUIREMENTS IN THE |
| | KITCHEN, INDICATE SAME ON PLANS. |
| | |
| | 7} SEE ARTICLE 210.23 FOR CORD AND PLUG CONNECTED |
| | EQUIPMENT. |
| | |
| | 8} THE "EQUIPMENT LIST " ON SHEET A1 DOES NOT LIST THE |
| | NAMEPLATE RATINGS OF ALL ELECTRICAL EQUIPMENT TO BE |
| | INSTALLED. |
| | |
| | 9} THE OUTSIDE LIGHTS ARE NOT SHOWN ON SHEET E1. THE |
| | NOTE ON SHEET A1 INDICATES A TOTAL OF 4000 WATTS, THE |
| | CIRCUIT ON SHEET E1 INDICATES 1800 WATTS, SHEET 5 ON |
| | THE ENERGY CALCS SHOWS 1500 WATTS. CORRELATE ALL |
| | LIGHTING. |
| | |
| | 10} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN. |
| | ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER |
| | 440.14,RECEPTACLE PER 210.63, LIGHT PER 210.70(A) |
| | (3). |
| | |
| | 11} THERE IS NO FIXTURE SCHEDULE TO CONFIRM LIGHTING |
| | DENSITIES PER CHAPTER 13, TABLE 13-415.2.C.1. |
| | |
| | 12} INDICATE COMPLIANCE WITH 13-415.1ABC.1.2, FBC FOR |
| | SPACE CONTROLS FOR LIGHTING." STANDARD SWITCHES ARE |
| | SHOWN ON THE PLAN. |
| | |
| | 13} INDICATE COMPLIANCE WITH 220.43 FOR SHOW WINDOW |
| | LIGHTING. |
| | |