Plan Review Notes
Plan Review Notes For Permit 07070777
Permit Number 07070777
Review Stop E
Sequence Number 1
Notes
Date Text
2007-08-15 17:49:12 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS,2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
 THE CODE CYCLES REFERENCED ON SHEET E2 ARE INCORRECT,
 SEE ABOVE.
  
 1} VERIFY THE SERVICE DISCONNECT RATING ( AMPS, VOLTS
 AND NUMBER OF PHASES) ON THE RISER DIAGRAM. 215.5 NEC.
  
 2} INDICATE THE CONDUIT AND CONDUCTOR SIZES FOR THE
 SERVICE, METER, DISCONNECT AND TO THE 400 AMP PANEL.
  
 3} 250.24(A)(5) LOAD-SIDE GROUNDING CONNECTIONS A
 GROUNDING CONNECTION SHALL NOT BE MADE TO ANY GROUNDED
 CONDUCTOR ON THE LOAD SIDE OF THE SERVICE DISCONNECTING
 MEANS EXCEPT AS OTHERWISE PERMITTED IN THIS ARTICLE.
 THE RISER HAS GROUNDING AT THE PANELS, IN VIOLATION OF
 THIS ARTICLE AND CREATING PARRALLEL GROUNDING PATHS
 WITH THE NUETRAL.
  
 4} PROVIDE A PANEL SCHEDULE FOR EP2.
  
 5} VERIFY THAT CIRCUIT EP-1,22 IS 120 VOLLTS AS LISTED
 ON THE SCHEDULE (SINGLE POLE BREAKER), 220 VOLTS AS
 LISTED ON THE RECEPTALE, AND COMPLIES WITH 422.16 FOR
 USE WITH A CORD. ALSO SEE 422.31(B).
  
 6} SEE 210.8(B)(2) FOR GFCI REQUIREMENTS IN THE
 KITCHEN, INDICATE SAME ON PLANS.
  
 7} SEE ARTICLE 210.23 FOR CORD AND PLUG CONNECTED
 EQUIPMENT.
  
 8} THE "EQUIPMENT LIST " ON SHEET A1 DOES NOT LIST THE
 NAMEPLATE RATINGS OF ALL ELECTRICAL EQUIPMENT TO BE
 INSTALLED.
  
 9} THE OUTSIDE LIGHTS ARE NOT SHOWN ON SHEET E1. THE
 NOTE ON SHEET A1 INDICATES A TOTAL OF 4000 WATTS, THE
 CIRCUIT ON SHEET E1 INDICATES 1800 WATTS, SHEET 5 ON
 THE ENERGY CALCS SHOWS 1500 WATTS. CORRELATE ALL
 LIGHTING.
  
 10} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN.
 ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14,RECEPTACLE PER 210.63, LIGHT PER 210.70(A)
 (3).
  
 11} THERE IS NO FIXTURE SCHEDULE TO CONFIRM LIGHTING
 DENSITIES PER CHAPTER 13, TABLE 13-415.2.C.1.
  
 12} INDICATE COMPLIANCE WITH 13-415.1ABC.1.2, FBC FOR
 SPACE CONTROLS FOR LIGHTING." STANDARD SWITCHES ARE
 SHOWN ON THE PLAN.
  
 13} INDICATE COMPLIANCE WITH 220.43 FOR SHOW WINDOW
 LIGHTING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]