| 2007-08-13 12:10:03 | BUILDING PLAN REVIEW |
| | PERMIT: O7070777 |
| | ADD: 795 BELVEDERE RD |
| | CONT:RICHARD LAWRLE INC |
| | TEL: (561)656-1128 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) 2004 FBC EXISTING |
| | 301.5A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE |
| | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 303, 304 AND 305 OF THIS CODE. |
| | |
| | 3)SUBMIT AN EXISTING FLOOR PLAN OF THE EXISTING |
| | STRUCTURE AND INDICATE THE WALLS WHICH SHALL BE |
| | ALTERED. THEN, THE PROPOSED DRAWINGS SHALL INDICATE THE |
| | NEW WALL ON THE THE FLOOR PLAN. CONSTRUCTION DOCUMENTS |
| | SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED. FBC |
| | 106.1.1 |
| | |
| | 4)110.2* W. P. B. ADMINISTRATIVE |
| | CODE, INFORMATION THAT IS REQUIRED FOR |
| | RECORD KEEPING. |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PROJECT IS DESIGNED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. |
| | D) THE OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED |
| | F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. |
| | G) ANY SPECIAL STIPULATIONS & CONDITIONS |
| | OF THE BUILDING PERMIT |
| | . ------------------------------------- |
| | ) NUMBER OF ROOMS |
| | ) SQ. FT. FOOTPRINT |
| | |
| | 5)SUBMIT A FINISH SCHEDULE INDICATINGTHE FLAME |
| | SPREAD/SMOKE DEVELOPMENT OF EACH ROOM IN ACCORDANCE |
| | WITH FBC SEC. 803/ 804 AND 805. |
| | |
| | 6)NOTE:ANY STRUCTURAL ALTERATION SHALL COMPLY WITH |
| | FLORIDA EXISTING BUILDING CODE SECTION 707 AND CH.8. |
| | |
| | 7)PROVIDE TWO SETS PRODUCT APPROVALS FOR THE NEW |
| | SERVICE WINDOW. FBC. 106.3.3* PRODUCT APPROVALS- 2004 |
| | THOSE PRODUCTS THAT ARE RGULATED BY DCA RULE 9B-72 |
| | SHALL BE REVIEWED AND APPROVED IN WRITTING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 8)THE TABLES IN THE DINING AREA AND AT THE COUNTER |
| | SHALL MEET ALL REQUIREMENTS OF FBC. SEC. 11-5. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |