| Plan Review Notes For Permit 07070744 |
| Permit Number |
07070744 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-08-29 10:37:29 | COMMERCIAL SCREEN ENCLOSURE BUILDING REVIEW FIRST | | | CHECKLIST. | | | REVIEW DONE UNDER FBC 2004 WITH 2007 REVISIONS. | | | | | | 1- PROVIDE COMPLETE ENGINEERED DRAWINGSAS REQUIRED BY | | | SEC. 2002.1 FBC 2004. | | | PLEASE MAKE SURE ENGINEER SIGNING AND SEALING DRAWINGS | | | PROVIDES ALL HIS INFORMATION AS REQUIRED BY SEC. | | | 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE AND CHAPTER | | | 471 FLORIDA STATUTES. | | | | | | 2- CLEARLY IDENTIFY WHAT'S NEW AND WHAT'S EXISTING. | | | CLARIFY IF CHANGING DOOR SIZES OR NUMBER OF DOORS. NEED | | | TO VERIFY THAT EGRESS REQUIREMENTS ARE NOT CHANGED. | | | SPECIFY ON PLANS. SEC. 106.1.2 CITY AMENDMENTS TO FBC | | | 2004. | | | | | | 3- PLANS TO SPECIFY ALL WIND DESIGN DATA THAT APPLIES | | | TO THIS JOB AS REQUIRED BY SEC. 1603.1.4 FBC 2004. | | | ALSO,SPECIFYCODE BY WHICH STRUCTURE IS DESIGNED. | | | FBC 2004. | | | | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712. |
|