2008-07-02 11:50:27PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO ENERGY CALCULATIONS
 *** DENIED ***
  
 1) REVISED ENERGY CALCULATIONS LINE 12 SHOWS ONLY ONE
 A/C SYSTEM, ASTHE ENERGY CAL'S. ARE FOR THE WHOLE
 HOUSE BOTH A/C SYSTEMS NEED TO BE SHOWN, AND BOTH
 HEATERS, PER 2004 FBC/ 13-103.3.
  
 2) E-CAL'S LINE 10 IS TAKING THE WHITE ROOF CREDIT. PER
 2004 FBC 13-607.1.A.5 WHITE ROOF CREDIT.
 HOUSES FOR WHICH A WHITE ROOF CREDIT IS CLAIMED IN
 ACCORDANCE WITH SECTION 13-607.2.A.3.6 SHALL HAVE AN
 INSTALLED ROOF THAT MEETS THE FOLLOWING CRITERIA:
  
 1. ROOF TYPE MAY ONLY BE METAL, CONCRETE, TILE OR
 SINGLE-PLY MEMBRANE FOR RESIDENTIAL CONSTRUCTION.
  
 2. ROOF MUST BE WHITE WITH A TESTED TOTAL SOLAR
 REFLECTANCE OF 65 PERCENT OR GREATER WHEN EVALUATED IN
 ACCORDANCE WITH ASTM E 903. ROOF SHALL HAVE A SURFACE
 EMISSIVITY OF 80 PERCENT OR GREATER. TESTING OF A
 QUALIFYING SAMPLE OF THE ROOFING MATERIAL SHALL BE
 PERFORMED BY AN APPROVED INDEPENDENT LABORATORY AND
 PRODUCT LABELING COMMENSURATE WITH THESE RESULTS SHALL
 BE PROVIDED BY THE MANUFACTURER. PLEASE SUBMIT REQUIRED
 TEST REPORTS.
  
  