| 2008-02-26 16:59:26 | BUILDING REVISION SECOND CHECKLIST: |
| | |
| | 1- SIZE OF ATTIC ACCESS ON BEDROOM #3 WAS CHANGED. NOW, |
| | NEW SIZE (22X22) SHOWN ON SHEET A3.0DOESN'T COMPLY |
| | WITH SEC. R807.1 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | REVISE AS REQUIRED. |
| | |
| | 2-GARAGE SIDE DOOR PRODUCT APPROVAL NOA 01-1218.05 |
| | SUBMITTED EXPIRED ON AUGUST 15, 2007. NEED TO PROVIDE |
| | CURRENT PRODUCT APPROVALAS REQUIRED BY DCA RULE |
| | 9B-72. |
| | |
| | ***REMAINDER: ARCHITECT TO REVIEW AND APPROVE IN |
| | WRITING(NOT SIGNING AND SEALING))ALL PRODUCT |
| | APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS |
| | TO FBC 2004. THIS APPLIES TO NEWDOOR PRODUCT APPROVAL |
| | AND MAKE SURE IT'S NOT EXPIRED TO AVOID UNNECESSARY |
| | DELAYS. |
| | |
| | 3-REVISE ENERGY CALCULATIONS: |
| | A) CEILING INSULATION CAN'T BE 1848 S.F.IF THE |
| | EXISTING CONDITIONED AREA IS 1905S.F.. SEE |
| | ARCHITECTURAL PLANS AND REVISE AS REQUIRED. |
| | |
| | B) COMPLETE ALL INFORMATION IN THE FORM PROVIDED. |
| | NEED BUILDER'S NAME, COMPLETE ITEMS 1 THRU 7. AND, |
| | COMPLETE INFORMATION ON SECOND PAGE. |
| | |
| | 4- OWES $10.46 FOR RADON FEES.FILE WAS AUDITED AND |
| | FOUND THAT RADON FEES WERE NOT PAID. |
| | |
| | 5- NEED TO BRING PLANS TO PALM BEACH COUNTY(2300 N. |
| | JOG RD)TO UPDATE TOTAL SQUARE FOOTAGE FOR ADDITION. |
| | IMPACT FEES STAMP STATES 605S.F., WHILE ACTUAL ADDITION |
| | IS 1045S.F. SEE AREA CALCULATIONS ON SHEET A3.0. |
| | BRING BACK RE-STAMPED PLANS BY PALM BEACH COUNTY.AND, |
| | IF FEES ARE DUE, THEN BRING BACK COPY OF PAID RECEIPT. |
| | SEEATTACHED COPY OF IMPACT FEES STAMP. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |