Plan Review Notes
Plan Review Notes For Permit 07070741
Permit Number 07070741
Review Stop M
Sequence Number 2
Notes
Date Text
2007-11-02 12:13:06PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) A NOTE WAS SENT BACK WITH THE PLANS STATING ICYNENE
 IS TO BE INSTALLED, PLEASE SEE BUILDING REVIEW NOTES
 REGARDING ICYNENE AND COMPLY.
  
 2) ENERGY CALCULATIONS LINE 15 IS TAKING THE CROSS
 VENTILATION CREDIT, PLEASE SEE 2004 FBC 13-607.1.A.3
 AND SHOW HOW THIS ADDITION COMPLIES WITH ALL AND HOW
 SOUTH FLORIDA COMPLIES WITH THE LAST NOTE.
  
 2004 FBC 13-607.1.A.3.1 CROSS VENTILATION CREDIT.
 HOUSES FOR WHICH CREDIT IS CLAIMED FOR CROSS
 VENTILATION IN ACCORDANCE WITH THE CRITERIA IN SECTION
 13-607.2.A.3.3 SHALL HAVE PROVIDED OPERABLE APERTURE
 AREAS TOTALING A MINIMUM OF 12 PERCENT OF THE FLOOR
 AREA OF THE ROOM FOR ALL PRIMARY LIVING AREAS AND MAIN
 BEDROOMS.
 INSECT SCREENS SHALL BE PROVIDED FOR ALL WINDOWS AND
 DOORS TO BE CONSIDERED OPERABLE APERTURE AREA. ALL
 SCREENED ENTRY DOORS AND INTERIOR DOORS IN THE
 VENTILATED AREAS SHALL BE PROVIDED WITH EITHER (1)
 MECHANICALLY ATTACHED DOOR STOPS (OR SIMILAR DEVICES)
 TO HOLD THE DOOR IN AN OPEN POSITION OR (2) OPERABLE
 LOUVERS.
 THE TOTAL APERTURE AREA SHALL BE PROVIDED BY A MINIMUM
 OF TWO DISTINCT WINDOWS. EACH WINDOW SHALL PROVIDE NOT
 MORE THAN 70 PERCENT OF THE TOTAL APERTURE AREA. THE
 WINDOWS (OR SLIDING GLASS DOORS) SHALL BE PLACED IN
 ADJACENT OR OPPOSITE WALLS. THE WINDOWS MAY BE PLACED
 ON A SINGLE OUTSIDE WALL IF WING WALLS ARE USED. WHERE
 WING WALLS ARE INCLUDED IN THE BUILDING DESIGN FOR
 VENTILATION PURPOSES, THEY SHALL BE PLACED BETWEEN
 WINDOWS TO CREATE A HIGH-PRESSURE AND A LOW-PRESSURE
 ZONE ON EACH WINDOW. WING WALLS SHALL EXTEND FROM THE
 GROUND TO EVE HEIGHT, BE LOCATED ON THE WINDWARD SIDE
 OF THE BUILDING, AND EXTEND OUTWARD FROM THE BUILDING A
 DISTANCE AT LEAST EQUAL TO ONE-HALF THE WIDTH OF THE
 WINDOW.
 NOTE: THIS TECHNIQUE IS EFFECTIVE ONLY FOR AREAS WHICH
 EXPERIENCE SIGNIFICANT AND CONTINUOUS WINDS DURING THE
 COOLING MONTHS.
  
 3) AS NOTED IN LAST REVIEW 7-27-07 NOTE #5. THE ENERGY
 CALCULATIONS LINE 15 IS TAKING MULTIZONE HEATING
 CREDIT, AS THE CALCULATIONS ARE FOR THE ADDITION ONLY
 AND ONLY ONE SYSTEM IS SERVING THAT AREA THEN IT CAN
 NOT BE MULTIZONE, CORRECT ENERGY CAL'S. SEE 2004 FBC
 13-2 DEFINITIONS.
  