Plan Review Notes
Plan Review Notes For Permit 07070741
Permit Number 07070741
Review Stop E
Sequence Number 2
Notes
Date Text
2007-10-09 11:28:46 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 ALL COMMENTS RELATE TO SHEET A6.0,UNLESS OTHERWISE
 NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 THESE COMMENTS ARE FROM THE PREVIOUS REVIEW, THE * IS
 FURTHER COMMENTARY IN AN ATTEMT TO CLARIFY THE
 PREVIOUS.
  
 5} PANEL "G" IS NOT SHOWN ON THE RISER DIAGRAM. PROVIDE
 CONDUCTOR AND CONDUIT SIZE AND TYPE.* PANEL "G" IS NOT
 LOCATED ON THE PLAN.
  
 10} CIRCUIT "A 13" APPEARS TO BE IN THE KITCHEN AND
 THEREFORE IS SUBJECT TO ARTICLE 210.52(B)(1) FOR SMALL
 APPLIANCES.* THIS CONDITION STILL EXISTS, WAS NOT
 CORRECTED BY ADDING CIRCUIT #38.
  
 THIS IS A NEW COMMENT FOR THIS REVIEW
  
 1} A RECEPTACLE NEEDS TO BE ADDED TO THE KITCHEN
 COUNTERTOP FOR SPACING REQUIREMENTS OF 210.52(C)(1).
 SEE REVIEWED PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DEPARTMENT
 561) 805-6718