Plan Review Notes
Plan Review Notes For Permit 07070741
Permit Number 07070741
Review Stop B
Sequence Number 2
Notes
Date Text
2007-11-01 14:46:17SINGLE FAMILY RESIDENCE ADDITION AND RENOVATION
 BUILDING REVIEW SECOND CHECKLIST.
 REVIEW DONE UNDER EXISTING BUILDING 2004 CODE, FLORIDA
 RESIDENTIAL CODE 2004 AND FBC 2004 WITH 2007
 REVISIONS.
  
 1- SHEET A7.0:REVISE TOP CHORD DEAD LOADS. IF
 INSTALLING CONCRETE ROOF TILE , THEN10PSF TOP CHORD
 DEAD LOAD IS INCORRECT.REVISE AS REQUIRED BY SEC.
 R301.4 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 2- PERSON PREPARING ENERGY ENERGY CALCULATIONS NOW
 STATES THAT USING ICYNENE INSULATION.THIS IS NEW
 INFORMATION, THEREFORE, THE FOLLOWING IS REQUIRED:
 A) PROVIDE COMPLETE SPECIFICATIONS FOR ICYNENE
 INSULATION TO VERIFY COMPLIANCE WITH R VALUES STATED IN
 THE ENERGY CALCULATIONS AT CEILINGS AND WALLS
 (SPECIALLY IN CONCRETE BLOCK WALLS), SEC. R314.3 FOR
 BURNING CHARACTERISTICS AND SEC. R314.4 OF 2004 FLORIDA
 RESIDENTIAL CODE FOR THERMAL BARRIER REQUIREMENTS.
  
 B) ALL ARCHITECTURAL DRAWINGS NEED TO BE REVISED TO
 INCORPORATE THE ICYNENE INSULATION AS PART OF THE
 SPECIFICATIONS FOR COMPLIANCE WITH CHAPTER 13 OFF FBC
 2004. ARCHITECT TO REVIEW ALL ICYNENE SPECS AND
 SECTIONSR314.3,SEC. R314.4 OF 2004 FLORIDA
 RESIDENTIAL CODE AND REVISE ALL WALL SECTIONS AS
 REQUIRED. SEC. 106.1.2 CIT6Y AMENDMENTS TO FBC 2004.
  
 C) ARCHITECT TO PROVIDE SPECIFICATIONS FOR ICYNENE
 INSULATION BETWEEN EXISTING BUILDING AND NEW ADDITION
 TO SHOW HOWTHE BUILDING ENVELOPE WILL BE SEALED TO
 AVOID HAVING ATTICVENTILATION TO VERIFY COMPLIANCE
 WITH SEC. R806 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 C) R VALUES SHOWN ON ARCHITECTURAL PLANS AND ENERGY
 CALCULATIONS NEED TO MATCH. INCLUDING BUILDING SECTIONS
 SHOWN ON SHEET A5.0.
  
 3-ENERGY CALCULATIONS WERE REVISED TO HAVE NO CEILING
 FAN CREDIT, THEREFORE CEILING FANS ARE NOT REQUIRED.
 BUT, IF CEILING FAN CREDIT IS REINSTATED, THEN
 ARCHITECT TO SEE TABLE 13-607.1.A.1 FBC 2004 FOR
 MINIMUM CEILING FAN SIZE REQUIRED.SIZES SHOWN ON SOME
 ROOMS DON'T COMPLY.
  
 4- ENERGY CALCULATIONS:
 A) MISSING ADJACENT WALL AT GARAGE AREA. PERSON
 PREPARING THE ENERGY CALCULATIONS NEEDS TO REVIEW
 ARCHITECTURAL PLANS TO SEE COMPLETE SCOPE OF WORK.
 PLANS CALL FOR NEW ADDITIONSAND RENOVATIONS TO THE
 EXISTING HOUSE.THERE ARE NEW OPENINGS IN THE EXTERIOR
 WALL AND SOME OPENINGS ARE CLOSED. IN ADDITION THERE IS
 A NEW ADJACENT WALL IN GARAGE AREA.ENERGY
 CALCULATIONS TO COMPLY WITH SEC. 13-600.1.C.1 AND SEC.
 13-600.1.C.2 OF FBC 2004.
  
 B) OWNER/AGENT TO DATE THE ENERGY CALCULATIONS.
 (REPEAT COMMENT. IT WAS SIGNED, BUT NO DATED).
  
 C) R VALUES IN CEILINGS AND WALLS NED TO MATCH
 ARCHITECTURAL PLANS.
  
 5- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) POLYPRO ADHESIVE ROOF TILE AS SPECIFIED ON TILE
 PRODUCT APPROVAL AND ARCHITECTURAL PLANS.
  
 B) ALL SIMPSON ANDUSP STRUCTURAL CONNECTORS
 SPECIFIED ON PLANS. NEED TO PROVIDE THE 2004 CODE
 VERSION. SOME OF THE PRODUCT APPROVALS SUBMITTED ARE
 FOR 2001 CODE VERSION. (SEE FL503 AND FL474 SUBMITTED).
 GO TO WWW.FLORIDABUILDING.ORG TO DOWNLOAD CURRENT
 PRODUCT APPROVALS.
 ALSO,NEED TO PROVIDE PAGE WHERE SPECIFIC CONNECTOR IS
 SHOWN. (REPEAT COMMENT). ONLY THE COVER PAGE WAS
 SUBMITTED. THIS APPLIES TO ALL CONNECTOR SUBMITTED.
  
 C) BAHAMA SHUTTERS. FL8523-R1 SUBMITTEDIS NOT
 APPROVED YET. APPLICATION STATUS SAYS "PENDING FBC
 APPROVAL".NEED ONE WITH APPROVED STATUS.
  
 6- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL REVISED/RE-SUBMITTED PRODUCT APPROVALS AS REQUIRED
 BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 7- NOTICE OF COMMENCEMENT WAS RECORDED ON 07/02/2007.
 ACCORDING TO SEC. 713.13 FLORIDA STATUTENOTICE OF
 COMMENCEMENTS ISEXPIRED IF WORK IS NOT STARTED WITHIN
 90 DAYS OF RECORDING IT. NEED RE-RECORDED NOTICE OF
 COMMENCEMENT.
  
 8- REVISE/CLARIFYROOF SHEATHING MATERIALS.
 INFORMATION ON TYPICAL WALL SECTION "C"ON SHEET A9.0,
 TYPICALROOF TILE ATTACHMENT DETAIL ON SHEET A8.0 AND
 ROOF SHEATHING & NAILING NOTE ON SHEET A7.0 DON'T
 MATCH. REVISE AS REQUIRED.
  
 9- PROVIDE COPY OF THE PAID RECEIPT OF THE IMPACT FEES.
 NEED COPY TO BE FILED WITH THE CITY FILE.
  
 10- ARCHITECT TODATE DRAWINGS WHEN THE SEAL IS
 IMPRESSED AS REQUIRED BY SEC. 61G1-16.004(5) OF FLORIDA
 ADMINISTRATIVE CODE. (REPEAT COMMENT).
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER