| 2007-11-01 14:46:17 | SINGLE FAMILY RESIDENCE ADDITION AND RENOVATION |
| | BUILDING REVIEW SECOND CHECKLIST. |
| | REVIEW DONE UNDER EXISTING BUILDING 2004 CODE, FLORIDA |
| | RESIDENTIAL CODE 2004 AND FBC 2004 WITH 2007 |
| | REVISIONS. |
| | |
| | 1- SHEET A7.0:REVISE TOP CHORD DEAD LOADS. IF |
| | INSTALLING CONCRETE ROOF TILE , THEN10PSF TOP CHORD |
| | DEAD LOAD IS INCORRECT.REVISE AS REQUIRED BY SEC. |
| | R301.4 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 2- PERSON PREPARING ENERGY ENERGY CALCULATIONS NOW |
| | STATES THAT USING ICYNENE INSULATION.THIS IS NEW |
| | INFORMATION, THEREFORE, THE FOLLOWING IS REQUIRED: |
| | A) PROVIDE COMPLETE SPECIFICATIONS FOR ICYNENE |
| | INSULATION TO VERIFY COMPLIANCE WITH R VALUES STATED IN |
| | THE ENERGY CALCULATIONS AT CEILINGS AND WALLS |
| | (SPECIALLY IN CONCRETE BLOCK WALLS), SEC. R314.3 FOR |
| | BURNING CHARACTERISTICS AND SEC. R314.4 OF 2004 FLORIDA |
| | RESIDENTIAL CODE FOR THERMAL BARRIER REQUIREMENTS. |
| | |
| | B) ALL ARCHITECTURAL DRAWINGS NEED TO BE REVISED TO |
| | INCORPORATE THE ICYNENE INSULATION AS PART OF THE |
| | SPECIFICATIONS FOR COMPLIANCE WITH CHAPTER 13 OFF FBC |
| | 2004. ARCHITECT TO REVIEW ALL ICYNENE SPECS AND |
| | SECTIONSR314.3,SEC. R314.4 OF 2004 FLORIDA |
| | RESIDENTIAL CODE AND REVISE ALL WALL SECTIONS AS |
| | REQUIRED. SEC. 106.1.2 CIT6Y AMENDMENTS TO FBC 2004. |
| | |
| | C) ARCHITECT TO PROVIDE SPECIFICATIONS FOR ICYNENE |
| | INSULATION BETWEEN EXISTING BUILDING AND NEW ADDITION |
| | TO SHOW HOWTHE BUILDING ENVELOPE WILL BE SEALED TO |
| | AVOID HAVING ATTICVENTILATION TO VERIFY COMPLIANCE |
| | WITH SEC. R806 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | C) R VALUES SHOWN ON ARCHITECTURAL PLANS AND ENERGY |
| | CALCULATIONS NEED TO MATCH. INCLUDING BUILDING SECTIONS |
| | SHOWN ON SHEET A5.0. |
| | |
| | 3-ENERGY CALCULATIONS WERE REVISED TO HAVE NO CEILING |
| | FAN CREDIT, THEREFORE CEILING FANS ARE NOT REQUIRED. |
| | BUT, IF CEILING FAN CREDIT IS REINSTATED, THEN |
| | ARCHITECT TO SEE TABLE 13-607.1.A.1 FBC 2004 FOR |
| | MINIMUM CEILING FAN SIZE REQUIRED.SIZES SHOWN ON SOME |
| | ROOMS DON'T COMPLY. |
| | |
| | 4- ENERGY CALCULATIONS: |
| | A) MISSING ADJACENT WALL AT GARAGE AREA. PERSON |
| | PREPARING THE ENERGY CALCULATIONS NEEDS TO REVIEW |
| | ARCHITECTURAL PLANS TO SEE COMPLETE SCOPE OF WORK. |
| | PLANS CALL FOR NEW ADDITIONSAND RENOVATIONS TO THE |
| | EXISTING HOUSE.THERE ARE NEW OPENINGS IN THE EXTERIOR |
| | WALL AND SOME OPENINGS ARE CLOSED. IN ADDITION THERE IS |
| | A NEW ADJACENT WALL IN GARAGE AREA.ENERGY |
| | CALCULATIONS TO COMPLY WITH SEC. 13-600.1.C.1 AND SEC. |
| | 13-600.1.C.2 OF FBC 2004. |
| | |
| | B) OWNER/AGENT TO DATE THE ENERGY CALCULATIONS. |
| | (REPEAT COMMENT. IT WAS SIGNED, BUT NO DATED). |
| | |
| | C) R VALUES IN CEILINGS AND WALLS NED TO MATCH |
| | ARCHITECTURAL PLANS. |
| | |
| | 5- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| | 9B-72 FOR: |
| | A) POLYPRO ADHESIVE ROOF TILE AS SPECIFIED ON TILE |
| | PRODUCT APPROVAL AND ARCHITECTURAL PLANS. |
| | |
| | B) ALL SIMPSON ANDUSP STRUCTURAL CONNECTORS |
| | SPECIFIED ON PLANS. NEED TO PROVIDE THE 2004 CODE |
| | VERSION. SOME OF THE PRODUCT APPROVALS SUBMITTED ARE |
| | FOR 2001 CODE VERSION. (SEE FL503 AND FL474 SUBMITTED). |
| | GO TO WWW.FLORIDABUILDING.ORG TO DOWNLOAD CURRENT |
| | PRODUCT APPROVALS. |
| | ALSO,NEED TO PROVIDE PAGE WHERE SPECIFIC CONNECTOR IS |
| | SHOWN. (REPEAT COMMENT). ONLY THE COVER PAGE WAS |
| | SUBMITTED. THIS APPLIES TO ALL CONNECTOR SUBMITTED. |
| | |
| | C) BAHAMA SHUTTERS. FL8523-R1 SUBMITTEDIS NOT |
| | APPROVED YET. APPLICATION STATUS SAYS "PENDING FBC |
| | APPROVAL".NEED ONE WITH APPROVED STATUS. |
| | |
| | 6- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ALL REVISED/RE-SUBMITTED PRODUCT APPROVALS AS REQUIRED |
| | BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 7- NOTICE OF COMMENCEMENT WAS RECORDED ON 07/02/2007. |
| | ACCORDING TO SEC. 713.13 FLORIDA STATUTENOTICE OF |
| | COMMENCEMENTS ISEXPIRED IF WORK IS NOT STARTED WITHIN |
| | 90 DAYS OF RECORDING IT. NEED RE-RECORDED NOTICE OF |
| | COMMENCEMENT. |
| | |
| | 8- REVISE/CLARIFYROOF SHEATHING MATERIALS. |
| | INFORMATION ON TYPICAL WALL SECTION "C"ON SHEET A9.0, |
| | TYPICALROOF TILE ATTACHMENT DETAIL ON SHEET A8.0 AND |
| | ROOF SHEATHING & NAILING NOTE ON SHEET A7.0 DON'T |
| | MATCH. REVISE AS REQUIRED. |
| | |
| | 9- PROVIDE COPY OF THE PAID RECEIPT OF THE IMPACT FEES. |
| | NEED COPY TO BE FILED WITH THE CITY FILE. |
| | |
| | 10- ARCHITECT TODATE DRAWINGS WHEN THE SEAL IS |
| | IMPRESSED AS REQUIRED BY SEC. 61G1-16.004(5) OF FLORIDA |
| | ADMINISTRATIVE CODE. (REPEAT COMMENT). |
| | |