Plan Review Notes
Plan Review Notes For Permit 07070741
Permit Number 07070741
Review Stop P
Sequence Number 1
Notes
Date Text
2007-08-13 15:25:35DENIED;
 1. ADD NOTE TO DEMO PAGE. " NO DEAD ENDS PERMITED IN
 THE DRAINAGE SYSTEM, INSPECTION REQUIRED". SEE FBC-2004
 SECTION 704.5
 2. SANITARY RISER DIAGRAM, BATHROOM 2 AND 3 , SHOWER IN
 2 IS NOT VENTED AND TUB IN BATHROOM 3 IS NOT VENTED.
 3. W/M STACK IS TO FAR AWAY FROM KIT. SINK TO RUN A
 WASTE ARM STUB UP UNDER SINK WITH A MECHANICAL VENT.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695