| 2007-07-27 09:42:02 | *** DENIED *** |
| | 1) BUILDING PLANS, THE TITLE BLOCK IS MISSING THE |
| | ARCHITECT'S PRINTED NAME AND THE DATE IS MISSING AT THE |
| | SEAL, SEE FAC 61G1-16.003 AND 61G1-16.004. |
| | |
| | 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT |
| | ALSO, PER 2004 FBC 13-600.3.ABC.2. |
| | |
| | 3) ENERGY CALCULATIONS LINE 11A STATES THE SUPPLY AND |
| | RETURN AIR DUCTS IN A CONDITIONED SPACE, MECHANICAL |
| | PLANS SHOW THE DUCTS IN THE ATTIC, PLEASE CORRECT THE |
| | ENERGY CAL'S. |
| | |
| | 4) ENERGY CAL'S. STATE THE AIR HANDLER IS IN THE |
| | INTERIOR, THE MECHANICAL PLANS SHOW THE AIR HANDLER IS |
| | IN THE ATTIC, PLEASE CORRECT ENERGY CAL'S. |
| | |
| | 5) ENERGY CAL'S. LINE 15 IS TAKING CREDITS FOR |
| | MULTIZONE COOLING AND HEATING, AS THE CALCULATIONS ARE |
| | FOR THE ADDITION ONLY AND ONLY ONE SYSTEM IS SERVING |
| | THAT AREA THEN IT CAN NOT BE MULTIZONE, CORRECT ENERGY |
| | CAL'S. |
| | |
| | 6) COMMENT FOR THE MECHANICAL PLANS, ALL INFORMATION, |
| | DRAWINGS, SPECIFICATIONS AND ACCOMPANYING DATA SHALL |
| | BEAR THE PRINTED NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN. PER FBC 104.2.1. |
| | |
| | 7) MECHANICAL PLANS NEED TO SHOW THE SIZE OF THE RETURN |
| | AIR DUCT (FLEX) TO THE MASTER BEDROOM. |
| | |
| | 8) MECHANICAL PLANS NEED TO SHOW THE EXHAUST FANS IN |
| | ALL THE BATHROOMS, SEE ELECTRICAL PLANS. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |