Date Text
2007-07-31 15:08:59 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THERE IS NO RECORD OF THE GENERATOR AND TRANSFER
 SWITCH, INCLUDED ON THE RISER DIAGRAM, HAVING BEEN
 PERMITTED. IT APPEARS THAT THE PAD ON THE PLAN DOES NOT
 MEET SETBACK REQUIREMENTS, MANUFACTURERS, NEC OR
 MECHANICAL. A SEPARATE PERMIT IS REQUIRED FOR THIS
 EQUIPMENT.
  
 2} INDICATE THE LOCATION OF THE ?RELOCATED? 200 AMP
 MAIN DISCONNECT. THE LOCATION SHOWN ON THE PLAN READS
 "EXISTING". PLEASE CLARIFY.
  
 3} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT. THIS IS NECESSARY AS THE EQUIPMENT
 HAS BEEN MOVED AND FPL WIRE SIZE AND DISTANCE FROM THE
 TRANSFORMER CHANGE THE EQUATION.
  
 4} THE EQUIPMENT GROUND BETWEEN THE METER AND
 DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH
 TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN
 ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN
 FROM THE FIRST MEANS OF DISCONNECT. 250.6.
  
 5} PANEL "G" IS NOT SHOWN ON THE RISER DIAGRAM. PROVIDE
 CONDUCTOR AND CONDUIT SIZE AND TYPE.
  
 6} THE DISHWASHER RECEPTACLE IS MISMARKED "G 11", THE
 GARAGE DOOR CIRCUIT.
  
 7} CIRCUIT "G 12" IN THE PANTRY IS NOT ON THE PANEL
 SCHEDULE.
  
 8} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN
 INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS
 SHALL BE INTERCONNECTED AND HARD WIRED. ALSO SEE THE
 DEFINITION OF "SMOKE DETECTORS" 11.8.2.1 NFPA-72,
 CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID
 CONFUSION IN THE FIELD. SEE 210.12 FOR AFCI
 CIRCUITING.
  
 9} THE DISCONNECT FOR THE ?EXISTING? CONDENSER DOES NOT
 APPEAR TO MEET THE CLEARANCE REQUIREMENTS OF 110.26
 NEC, IF THE GENERATOR PAD GETS LOCATED WHERE SHOWN.
  
 10} CIRCUIT "A 13" APPEARS TO BE IN THE KITCHEN AND
 THEREFORE IS SUBJECT TO ARTICLE 210.52(B)(1) FOR SMALL
 APPLIANCES.
  
 11} THE DISCONNECT CIRCUIT AT THE NEW CONDENSER IS
 MISMARKED ON THE RANGE CIRCUIT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DEPARTMENT
 561) 805-6718