| 2007-07-31 15:08:59 | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} THERE IS NO RECORD OF THE GENERATOR AND TRANSFER |
| | SWITCH, INCLUDED ON THE RISER DIAGRAM, HAVING BEEN |
| | PERMITTED. IT APPEARS THAT THE PAD ON THE PLAN DOES NOT |
| | MEET SETBACK REQUIREMENTS, MANUFACTURERS, NEC OR |
| | MECHANICAL. A SEPARATE PERMIT IS REQUIRED FOR THIS |
| | EQUIPMENT. |
| | |
| | 2} INDICATE THE LOCATION OF THE ?RELOCATED? 200 AMP |
| | MAIN DISCONNECT. THE LOCATION SHOWN ON THE PLAN READS |
| | "EXISTING". PLEASE CLARIFY. |
| | |
| | 3} PER 110.9 AND 110.10: OBTAIN THE |
| | AVAILABLE FAULT CURRENT AT THE UTILITY |
| | AND CALCULATE THE SAME AT THE EQUIPMENT. |
| | INDICATE THE AIC RATING FOR THE |
| | EQUIPMENT IS EQUAL TO OR GREATER THAN |
| | THE AVAILABLE FAULT. THIS IS NECESSARY AS THE EQUIPMENT |
| | HAS BEEN MOVED AND FPL WIRE SIZE AND DISTANCE FROM THE |
| | TRANSFORMER CHANGE THE EQUATION. |
| | |
| | 4} THE EQUIPMENT GROUND BETWEEN THE METER AND |
| | DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH |
| | TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN |
| | ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN |
| | FROM THE FIRST MEANS OF DISCONNECT. 250.6. |
| | |
| | 5} PANEL "G" IS NOT SHOWN ON THE RISER DIAGRAM. PROVIDE |
| | CONDUCTOR AND CONDUIT SIZE AND TYPE. |
| | |
| | 6} THE DISHWASHER RECEPTACLE IS MISMARKED "G 11", THE |
| | GARAGE DOOR CIRCUIT. |
| | |
| | 7} CIRCUIT "G 12" IN THE PANTRY IS NOT ON THE PANEL |
| | SCHEDULE. |
| | |
| | 8} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN |
| | INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS |
| | SHALL BE INTERCONNECTED AND HARD WIRED. ALSO SEE THE |
| | DEFINITION OF "SMOKE DETECTORS" 11.8.2.1 NFPA-72, |
| | CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID |
| | CONFUSION IN THE FIELD. SEE 210.12 FOR AFCI |
| | CIRCUITING. |
| | |
| | 9} THE DISCONNECT FOR THE ?EXISTING? CONDENSER DOES NOT |
| | APPEAR TO MEET THE CLEARANCE REQUIREMENTS OF 110.26 |
| | NEC, IF THE GENERATOR PAD GETS LOCATED WHERE SHOWN. |
| | |
| | 10} CIRCUIT "A 13" APPEARS TO BE IN THE KITCHEN AND |
| | THEREFORE IS SUBJECT TO ARTICLE 210.52(B)(1) FOR SMALL |
| | APPLIANCES. |
| | |
| | 11} THE DISCONNECT CIRCUIT AT THE NEW CONDENSER IS |
| | MISMARKED ON THE RANGE CIRCUIT. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | WILLIAM R. TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | 561) 805-6718 |