| 2007-08-21 13:16:45 | SINGLE FAMILY RESIDENCE ADDITIONAND RENOVATION |
| | BUILDING FIRST REVIEW CHECKLIST. |
| | REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE AND FBC |
| | 2004 WITH 2006/2007 REVISIONS. |
| | |
| | 1- DRAWINGS TITLE BLOCK NEEDS THE NAME OF ARCHITECT |
| | SIGNING AND SEALING THE PLANS AND DATE WHEN PLANS ARE |
| | SEALED AS REQUIRED BY SEC. 61G1-16.004 OF FLORIDA |
| | ADMINISTRATIVE CODE. |
| | |
| | 2- SHEET A1.0 SAYS WIND EXPOSURE "C",WHILE SHEET A2.0 |
| | SAYSWIND EXPOSURE "B". REVISE AS REQUIRED TO MATCH. |
| | |
| | 3- INTERNAL PRESSURE COEFFICIENT SPECIFIED ON SHEET |
| | A1.0 IS DIFFERENT THAN THAT SHOWN ON SHEET A2.0. REVISE |
| | AS REQUIRED. IS THIS STRUCTURE DESIGNED AS OPEN OR |
| | ENCLOSED?.SPECIFY CORRECT INTERNAL PRESSURE |
| | COEFFICIENT. |
| | |
| | 4- SITE PLAN ON SHEET A1.0 SHOWSARROWS FOR DRAINAGE |
| | THAT LEAD TO THE NEIGHBOR'S PROPERTY.WATER NEEDS TO |
| | BE DIVERTED TO A STORM SEWER CONVEYANCE OR OTHER |
| | APPROVED POINT OF COLLECTION.OR WATER TO BE RETAINED |
| | IN THE SAME LOT.SEE SEC. R401.3 OF 2004 FLORIDA |
| | RESIDENTIAL CODE AND REVISE SITE PLAN AS REQUIRED. |
| | |
| | 5- PROVIDE WINDOW CUT SHEETS SHOWING HOW SPECIFIED |
| | CASEMENT WINDOWS ON BEDROOMS 2 AND 3 COMPLY WITHTHE |
| | WIDTHEGRESS REQUIREMENTS OF SEC. R310 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | 6- AREA CALCULATIONS ON SHEET A3.0 DON'T ADD UP |
| | CORRECTLY. REVISE AS REQUIRED. |
| | |
| | 7- SPECIFY ALL DEAD AND LIVE LOADS ANDINCLUDETHE |
| | ATTIC LIVE LOADS AS REQUIRED BY TABLE R301.5 OF 2004 |
| | FLORIDA RESIDENTIAL CODE. |
| | |
| | 8- SOIL TEST REPORT: |
| | A) PROJECT DESCRIPTION IS TO RAZE EXISTING HOUSE TO |
| | BUILD A NEW ONE.ARCHITECTURAL PLANS CALL FOR NEW |
| | ADDITIONS TO EXISTING HOUSE. REVISE/CLARIFY AS |
| | REQUIRED. |
| | |
| | B) NEED THE ENGINEERING FIRM CERTIFICATE OF |
| | AUTHORIZATION NUMBERIN ALL SHEETS AS REQUIRED BY SEC. |
| | 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE. |
| | |
| | 9- ARCHITECT TO REVIEWSOIL TEST REPORT FOR FOOTING |
| | RECOMMENDATIONS. PROVIDE RESPONSE STATING THAT SOIL |
| | TEST REPORTAND RECOMMENDATIONS WAS REVIEWED AND |
| | DESIGN CONFORMS TO PROPOSED RECOMMENDATIONS. SEC. |
| | 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 10- ARCHITECT TO SPECIFY ROOF TILE FASTENING AS |
| | REQUIRED BY SEC. 106.1.1.2 CITY AMENDMENTS TO FBC 2004. |
| | IF USING NAIL OR SCREWS SPECIFY SIZE AND NUMBER. IF |
| | USING ADHESIVES SPECIFY SPECIFIC TYPE AND PROVIDE |
| | PRODUCT APPROVAL AS REQUIRED BY DCA RULE 9B-72. |
| | |
| | 11- ENERGY CALCULATIONS: |
| | A) CLARIFY WHY THERE IS NOT INFORMATION GIVEN FOR |
| | WATER HEATER IF NEW BATHROOMS ARE ADDED. SEC. 106.1.2 |
| | CITY AMENDMENTS TO FBC 2004. |
| | |
| | B) INSULATION ON WALLS AND CEILING DON'T MATCH |
| | ARCHITECTURAL PLANS. |
| | |
| | C) MISSING ADJACENT WALL AT GARAGE AREA. |
| | |
| | D) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. |
| | |
| | 12- IF ENERGY CALCULATIONS ARE TAKING THE CEILING FAN |
| | CREDIT, THENNEED TO SPECIFY CEILING FAN SIZE IN FLOOR |
| | PLANS AS REQUIRED BY TABLE 13-607.1.A.1 FBC 2004. |
| | |
| | 13- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| | 9B-72 FOR: |
| | A) ALL STRUCTURAL SIMPSON OR USP CONNECTORS |
| | SPECIFIED ON PLANS. |
| | ***NOTE: PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL |
| | COVER PAGE AND THE SPECIFIC PAGE SHOWING THE CONNECTOR |
| | TO SAVE PAPER. |
| | |
| | B) WINDOW MULLIONS AND CLEARLY IDENTIFY ANCHORING TO |
| | VERIFY COMPLIANCE WITH THE DESIGN PRESSURES CALCULATED |
| | BY THE ARCHITECT. SEC. 106.1.2 CITY AMENDMENTS TO FBC |
| | 2004. |
| | |
| | C) FIXED WINDOWS WITH SIZES AS SHOWN ON PLANS. |
| | |
| | D) ENTRY DOOR ASSEMBLY AS SHOWN ON PLANS. SEE SIZE |
| | ON ARCHITECTURAL PLANS. |
| | |
| | E) WOOD LOUVERED DOORS SHOWN ON FRONT ELEVATION. |
| | |
| | F) DECORATIVE BAHAMA SHUTTERS AND CLEARLY IDENTIFY |
| | FASTENING. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 14- SHEET A7.0: |
| | A) REVISE RAKED BEAM DETAIL.UPDATEALL SEMCO |
| | CONNECTORS. COMPANY IS OUT OF BUSINESS. |
| | |
| | B) SIMPSON ARCHITECTURAL SERIES CONNECTOR CB46PC |
| | SPECIFIED TO HOLD HEAVY TIMBER TRUSSES AT ENTRANCE IS A |
| | COLUMN BASE CONNECTOR. REVISE CONNECTOR AS REQUIRED AND |
| | PROVIDE COMPLETE DETAIL WITH SPECS. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | 15- SHEET A3.0: REVISE EGRESS NOTE #4 OF FIRE RATING & |
| | LIFE SAFETY NOTES.WINDOWS MUST MEET MINIMUM WIDTH AND |
| | HEIGHT DIMENSIONS, NOT WIDTH OR HEIGHT. REVISE AS |
| | REQUIRED TO COMPLY WITH SEC. R310 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | 16- SHEET A5.0: PROVIDE COMPLETE SPECS/DETAILSAND |
| | LOAD VALUES FOR SIMPSON ARCHITECTURAL SERIES CUSTOM |
| | GUSSET PLATES. SIMPSON DOESN'T PROVIDE THIS |
| | INFORMATION. THIS IS THE RESPONSIBILITY OF THE DESIGNER |
| | OF RECORD.SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 17- SHEET A9.0: |
| | A) UPDATE GENERAL CONSTRUCTION NOTE #11. SEE FBC |
| | 2004 FOR CORRECT CODE SECTION TO BE REFERENCED. |
| | |
| | B) REVISE GENERAL CONSTRUCTION NOTE #17.SEE SEC. |
| | R606.4 OF 2004 FLORIDA RESIDENTIAL CODE FOR CORRECT |
| | CONCRETE MASONRYMINIMUM NET AREA COMPRESSIVE |
| | STRENGTH. |
| | ALSO, UPDATE REFERENCED STANDARDS AND YEAR. SEE SEC. |
| | R606AND CHAPTER 43 OF 2004 FLORIDA RESIDENTIAL CODE |
| | FOR ADOPTED STANDARDS AND YEAR TO BE USED. |
| | |
| | C) REVISE GENERAL CONSTRUCTION NOTE #38. SEE ASTM |
| | C926 AND ASTMC1063 FOR CORRECT FASTENERS AND SPACING TO |
| | BE USED ACCORDING TO THE SPECIFIC INSTALLATION AND |
| | MATERIALS TO BE USED. |
| | |
| | D) UPDATE ALL GENERAL NOTES. SEE CHAPTER 35 OF FBC |
| | 2004 AND CHAPTER 43 OF 2004 RESIDENTIAL CODE FOR |
| | CORRECT ADOPTED STANDARDS AND YEAR TO BE USED AND |
| | REVISE/UPDATE NOTES AS REQUIRED. |
| | |
| | E) REVISE/CLARIFYSPECS ON TYPICAL 1-STORYWALL |
| | SECTION. ROOF SHEATHING NOTE CALLS FOR 19/32" CD GRADE |
| | WOOD, WHILE TYPICAL FASCIA CONSTRUCTION CALLS FOR 1X6 |
| | T&G SHEATHING. |
| | |
| | |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |