| 2008-02-06 16:54:35 | ****CORRECTIONS**** |
| | |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| | FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | COMMENTS FROM PREVIOUS REVIEW: |
| | |
| | 1.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED |
| | IN ADDITION TO THE EVALUATION REPORT SUBMITTED, |
| | FAC9B72.WWW.FLORIDABUILDING.ORG.THE PRODUCT |
| | APPROVAL PROVIDED IS FOR FBC2001; PLEASE GO TO THE |
| | WEBSITE AND PRINT A CURRENT APPROVAL (FBC2004). |
| | |
| | 2.)THE NOA PROVIDED IS INCOMPLETE.THE FIRST SHEETS |
| | LISTING COMPONENTS, THE LAST SHEET OR TWO LISTING THE |
| | PRODUCT GENERAL LIMITATIONS, AND THE PAGE WITH THE |
| | APPROVED ASSEMBLY YOU ARE USING ARE REQUIRED.IF YOU |
| | ARE UNSURE AS TO WHAT TO SUBMIT, PROVIDE THE COMPLETE |
| | PRODUCT APPROVAL AND MARK THE APPROVED ASSEMBLY YOU |
| | PROPOSE TO USE.COMPLIANCE WITH RAS117 CANNOT BE |
| | DETERMINED WITHOUT THIS INFORMATION AND ALSO DESIGN |
| | PRESSURES, SEE OTHER COMMENTS. |
| | |
| | 3.)THERE IS ANOTHER PROJECT IN PROGRESS AT THIS |
| | ADDRESS WITH DIFFERENT DESIGN CRITERIA INFORMATION. THE |
| | PERMIT NUMBER FOR THE PROJECT IS 07050024; THE DESIGNER |
| | OF RECORD IS DAVID LAWRENCE, ARCHITECT.IT WAS |
| | SUGGESTED THAT THE DESIGNERS MEET AND RESOLVE THE |
| | CONFLICT.HAS THIS BEEN DONE? |
| | |
| | NEW COMMENTS: |
| | |
| | 4.)THE PLAN MAKES REFERENCE TO "SOLID OR SPOT MOPPED |
| | IN HOT ASPHALT".PLEASE CLARIFY; IF THERE IS ANOTHER |
| | SUBSTRATE OTHER THAN WOOD, PROVIDE PRODUCT APPROVAL FOR |
| | THAT APPLICATION. |
| | |
| | 5.)NOTE THAT THE SHEET PROVIDED MARKED "ROOFING |
| | ASSEMBLY APPROVAL" IS NOT A SPECIFIC APPROVED ASSEMBLY. |
| | THIS PAGE IS A LISTING OF APPROVED COMPONENTS.THE |
| | APPROVED ASSEMBLY WILL BE FOUND BETWEEN SHEETS 5 AND |
| | 39.WITHOUT THIS INFORMATION, ALONG WITH DESIGN |
| | PRESSURES, I CANNOT DETERMINE CODE COMPLIANCE FOR |
| | ENHANCED FASTENING IN ACCORDANCE WITH RAS117. |
| | |
| | |
| | |
| | |
| | |
| | . |