Plan Review Notes
Plan Review Notes For Permit 07070732
Permit Number 07070732
Review Stop B
Sequence Number 2
Notes
Date Text
2007-08-30 18:16:01BUILDING PLAN REVIEW
 PERMIT: 07070732
 ADD: 206 CLEMATIS STREET
 CONT: BRIAN J STRNAD CONST. INC.
 TEL: (407)760-3651
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST.
 ACTION: DENIED
  
 1)ROOFING PERMIT; ONLY CHECKED ITEMS APPLY
  
 _XX___1.)A NOTICE OF COMMENCEMENT MUST BE FILED
 WITH THE CLERK OF COURTS PRIOR TO PERMIT PICKUP,
 FS713.13.
  
 _XX___2.)CONTRACTOR IS TO PROVIDE THE FOLLOWING
 INFORMATION ON THE APPLICATION, SEE ATTACHED
 POLICY:MEAN ROOF HEIGHT/ ROOF PITCH / ROOF DECK TYPE /
 AREA OF EACH ROOF TYPE
 **RESPONSE NOTE BUT**: THE MEAN ROOF HEIGHT ON THE
 APPLICATION SHOWS 15 FEET. THERE IS A PROJECT IN
 PROGRESS AT THIS ADDRESS WHICH INDICATE THE MEAN ROOF
 HEIGHT AT 76 FEET. STATE CLEARLY WHERE THE 15 FEET
 SECTION OF THE ROOF IS LOCATED.
  
 _XX___3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED IN ADDITION TO THE EVALUATION REPORT
 SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG
 **NO RESPONSE**
  
 ____4.)FOR THE FLAT DECK, SELECT THE APPROVED
 ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER
 IF THE OPTIONS HAVE DIFFERENT PRESSURE LIMITATIONS.
  
 _XX___5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED
 FASTENING FOR CORNER AND PERIMETER ZONES.
 ** NO RESPONSE** IF THE BUILDING IS OVER 60 FEET, THE
 WIND PRESSURES SHALL BE DESIGNED BY A PROFESSIONAL
 ENGINEER, REGISTERED ARCHITECT OR ROOFING CONSULTANT.
 FBC 1609.1.1
  
 ____ 6.)ON THE TILE PRODUCT APPROVAL, INDICATE WHICH
 METHOD OF ATTACHMENT YOU ARE USING.
  
 _XX___ 7.)SEE PRODUCT LIMITATION #7.CALCULATIONS
 PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF
 CONSULTANT REQUIRED FOR ENHANCED FASTENING.
 ** NO RESPONSE** PROVIDE THE CALCULATIONS FOR THE
 ENHANCED UPLIFT PRESSURE AS STATED IN THE PRODUCT
 APPROVAL.
  
 2)FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 ADDITIONAL FEES ARE DUE $77.48
  
 ***NEW***
 A)THE DESIGN CRITERIA INFORMATION SUBMITTED BY JAMES
 CANTWELL STATES THE BASIC WIND SPEED AS 120 MPH AND THE
 ESPOSURE CATEGORY=B. THE BASIC WIND SPEED FOR THE CITY
 OF WEST PALM BEACH IS 140 MPH.
  
 B)THERE IS ANOTHER PROJECT INPROGRESS AT AT THIS
 ADDRESS WITH DIFFERENT DESIGN CRITERIA INFORMATION. THE
 PERMIT NUMBER FOR THE PROJECT IS #07050024 THE DESIGNER
 OF RECORD IS DAVID LAWRANCE. I SUGGEST BOTH DESIGNERS
 MEET AND RESOLVE THE CONFLICT OF INFORMATION.
  
 C)106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE RGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OFF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]