2007-07-24 10:28:28BUILDING REVIEW CHECKLIST:
 1- SELECTED ASSEMBLY ON PAGE 30 OF NOA 05-0830.10
 SUBMITTED IS LIMITED TO -45PSF MAXIMUM DESIGN PRESSURE.
 THIS SYSTEM CAN'T BE USED IN THIS AREA BECAUSETHE
 DESIGN PRESSURES AT PERIMETER AND CORNER AREAS ARE
 HIGHER. SEE TABLE 1609..6.2.1.(2)FBC 2004.ALSO,
 THIS SYSTEM IS LIMITED BY GENERAL LIMITATION #9.THIS
 LIMITATION DOESN'T ALLOW NAIL ENHANCING TO PERIMETER
 AND CORNER AREAS. SEE GENERAL LIMITATION #9 ON LAST
 PAGE OF NOA SUBMITTED.
  
 2- NEED TO SPECIFY AN APPROVED ASSEMBLY THAT IS LIMITED
 BY GENERAL LIMITATION #7, WHICH IS THE LIMITATION THAT
 ALLOWS NAIL ENHANCING AT PERIMETER AND CORNERS AREAS TO
 MEET THE DESIGN PRESSURESREQUIRED BYTABLE
 1609.6.2.1(2) OF FBC 2004.
  
 3- IF NEW SELECTED ASSEMBLY HAVE MORE THAN ONE BASE
 SHEET FASTENING OPTION, THEN, CLEARLY IDENTIFY WHICH
 FASTENING OPTION IS GOING TO BE USED.SEEATTACHED
 COPY OF CITY POLICY FOR RE-ROOFING PERMITS AND
 INFORMATIONREQUIRED TO BE SUBMITTED.
  
 3- PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BYGENERAL
 LIMITATION #7 ON LAST PAGE OF NOA SUBMITTED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER