2007-10-10 16:25:52REVIEW #: 2
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE A-6 SHOWS FUTURE RTU'S AND REFRIGERATION
 EQUIPMENT ON NEW ROOF. SHOW COMPLIANCE WITH FBC 1509.7
 FOR EQUIPMENT HEIGHTS AND CLEARANCES. EQUIPMENT ON
 ELEVATED STANDS WHERE ROOFING MATERIALS EXTEND
 UNDERNEATH THE EQUIPMENT SHALL HAVE MINIMUM CLEARANCES
 IN COMPLIANCE WITH FBC TABLE 1509.7. OUTDOOR EQUIPMENT
 SHALL BE SECURED TO MEET WIND LOAD REQUIREMENTS IN
 ACCORDANCE WITH FBC,M 301.13 AND FBC 1609. PROVIDE WIND
 LOAD CALCULATIONS AND ATTACHMENT DETAILS TO DEMONSTRATE
 COMPLIANCE.
  
 2. EQUIPMENT ACCESS FOR SERVICE: WHERE EQUIPMENT AND
 APPLIANCES REQUIRING ACCESS ARE INSTALLED ON ROOFS OR
 ELEVATED STRUCTURES AT A HEIGHT EXCEEDING 16 FEET, SUCH
 ACCESS SHALL BE PROVIDED BY A PERMANENT APPROVED MEANS
 OF ACCESS, THE EXTENT OF WHICH SHALL BE FROM GRADE OR
 FLOOR LEVEL TO THE EQUIPMENT AND APPLIANCES? LEVEL
 SERVICE SPACE. SUCH ACCESS SHALL NOT REQUIRE CLIMBING
 OVER OBSTRUCTIONS GREATER THAN 30 INCHES HIGH OR
 WALKING ON ROOFS HAVING A SLOPE GREATER THAN 4 UNITS
 VERTICAL IN 12 UNITS HORIZONTAL. FBC,M 306.5 PERMANENT
 LADDERS INSTALLED TO PROVIDE THE REQUIRED ACCESS SHALL
 COMPLY WITH THE FOLLOWING MINIMUM DESIGN CRITERIA:
 1. THE SIDE RAILING SHALL EXTEND ABOVE THE PARAPET OR
 ROOF EDGE NOT LESS THAN 30 INCHES.
 2. LADDERS SHALL HAVE RUNG SPACING NOT TO EXCEED 14
 INCHES ON CENTER.
 3. LADDERS SHALL HAVE A TOE SPACING NOT LESS THAN 6
 INCHES DEEP.
 4. THERE SHALL BE A MINIMUM OF 18 INCHES BETWEEN
 RAILS.
 5. RUNGS SHALL HAVE A MINIMUM 0.75-INCH DIAMETER AND BE
 CAPABLE OF WITHSTANDING A 300-POUND LOAD.
 6. NOT APPLICABLE.
 7. LADDERS SHALL BE PROTECTED AGAINST CORROSION BY
 APPROVED MEANS.
  
 3. DETAIL 8 ON PG D-2: WHAT IS THE LOCATION OF THIS
 "SERVICE WALK"? CATWALKS INSTALLED TO PROVIDE THE
 REQUIRED ACCESS SHALL BE NOT LESS THAN 24 INCHES (610
 MM) WIDE AND SHALL HAVE RAILINGS AS REQUIRED FOR
 SERVICE PLATFORMS. FBC,M 306.5
  
 4. ENERGY: THE OVERALL SCOPE OF WORK RELATED TO THIS
 PROJECT APPEARS TO QUALIFY AS A RENOVATION AS DEFINED
 IN FBC 13-202. AS SUCH, SHOW COMPLIANCE WITH FBC CH.13
 BY PROVIDING FORM 400B-04 OR 400C-04 IN ACCORDANCE WITH
 FBC 13-400.0.C.4. ALSO, WHILE ONLY THE EXTERIOR WORK IS
 BEING DONE AT THIS TIME, INCLUDE ASSUMPTIONS ABOUT ALLL
 FEATURES TO BE INSTALLED AT A LATER DATE IN THE
 CALCULATIONS IN ACCORDANCE WITH FBC 13-101.1.6. ONCE
 ALL ASSUMPTIONS ARE BECOME KNOWN, A REVISED METHOD A
 FORM MAY BE SUBMITTED IN ACCORDANCE WITH FBC
 13-400.2.A.2.
  
 5. THE DESIGN PROFESSIONAL MUST ELECT ONE OR A
 COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE. FBC,EB 301.5.
  