Notes
Date Text
2007-09-20 21:22:44CITY MARKET EXTERIOR RENOVATION
 5011 BROADWAY
 SEPT 20,2007
  
 BUILDING PLAN REVIEW
 PERMIT: 07070711
 ADD: 5011 BROADWAY
 CONT: RED & BLUE CONSTRUCTION
 TEL: (561)542-5888
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3A) THE PHASE I PART OF THIS PROJECT IS FOR EXTERIOR
 RENOVATIONS AS STATED ON THE SHEET A-1. THE PLANS STATE
 THIS IS A TYPE IV-UNPROTECTED BUILDING, PLEASE TAKE
 REFERENCE TO THE 2004 FBC, TABLE 503 THIS IS STATING
 THIS BUILDING IS CLASSIFIED AS **HEAVY TIMBER
 CONSTRUCTION**, PLEASE CORRECT. IF ANY FRONTAGE
 INCREASES ARE TO BE TAKEN SHOW CALCULATIONS.
  
 3B) SINCE PHASE I IS FOR THE EXTERIOR OF THE BUILDING
 ONLY AND THIS PERMIT WILL BE FOR THE EXTERIOR ONLY, I
 BELIEVE IT IS ONLY FAIR TO WARN YOU OF THE REQUIREMENTS
 FOR FIRE SPRINKLERS WHEN A MERCANTILE BUILDING IS
 GREATER THAN 12,000 SQ. FT. 903.2.6 GROUP M. AN
 AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED THROUGHOUT
 BUILDINGS CONTAINING A GROUP M OCCUPANCY WHERE ONE OF
 THE FOLLOWING CONDITIONS EXISTS: 1. WHERE A GROUP M
 FIRE AREA EXCEEDS 12,000 SQUARE FEET.
  
 3C) THIS PROJECT WAS SUBMITTED UNDER PERMIT# 06030895
 AND THE PERMIT APPLICATION WAS EXPIRED. THE PLAN
 REVIEWER'S COMMENTS FROM THE FIRST REVIEW FROM THE
 FIRST REVIEW APPEAR AS QUOTES,
 104.2.1 W.P.B. ADMINISTRATIVE CODE, DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES.SUCH INFORMATION SHALL BE SPECIFIC
 AND THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE
 USED AS A SUBSTITUTE FOR SPECIFIC INFORMATION".
  
 3D) SHEET A-1 ALSO HAS WHITE OUT ON THE PLANS, WHICH
 ALSO ISN'T ACCEPTABLE.
  
  
 3E) PLEASE UPDATE THE CODE ANALYSIS TO REFLECT THE 2004
 FBC, BUILDING AND THE 2007REVISIONS, PLANS SUBMITTED
 AFTER JULY1,2007 WILL BE REVIEWED UNDER THE NEW 2007
 WIND REVISIONS TO THE BASE BUILDING CODE.
  
 3F) PLEASE SEE THE 2004 FLORIDA EXISTING BUILDING CODE
 WITH 2006 REVISIONS. IDENTIFY TO WHAT LEVEL OF
 ALTERATION WILL BE ACCOMPLISHED UNDER THIS PERMIT. SEE
 SECTION 303,304& 305.
  
 4) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE
 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) OF
 PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS
 FOLLOWS:
 4A) FIXED GLASS/ STORE FRONT
 4B) EXTERIOR GLAZED SWING DOORS & SIDELITES
 4C)SINGLE EXTERIOR HOLLOW METAL SWING DOORS
 4D) PAIRS OF EXTERIOR HOLLOW METAL SWING DOORS
 4E) POSSIBLE AUTOMATIC SLIDING DOORS& SIDE LITES 4F)
 TRUSS ANCHORS
 4G) WALL LOUVERS
 4H) EFIS WALL SYSTEMS
 4I) SHUTTERS BAHAMA STYLE- ON TOWERS
 4J) ROOF ASSEMBLIES
 UNDERLAYMENT
 MODIFIED BITUMEN
 ROOF TILE
  
 5)PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72.
  
 6) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 7) THE FOLLOWING ITEMS WILL DEAL WITH ROOFING REPORTS
 BE ADVISED OF THE INFORMATION THAT WILL NEED TO BE
 HIGHLIGHTED BEFORE SUBMITTAL TO THE BUILDING
 DEPARTMENT;
  
 7A) THIS ROOF IS MISSING OR NOT IN COMPLIANCE WITH THE
 FOLLOW ITEMS:
 (FLAT ROOF)
 ___ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT.
 ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH.___
 CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE USED.
 ___ THE SYSTEM PROVIDED HAS A LOWPRESSURE FOR ZONE
 ___ .
 ___ THE SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD
 THE FASTENERRESISTANCE BE LESS THAN THAT REQUIRED, AS
 DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED FASTENER SPACING,
 PREPARED , SIGNED AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOFCONSULTANT MAY BE
 SUBMITTED.
 ___THE SYSTEM PROVIDED INDICATESLIMITATION# 9, NO
 ENHANCED FASTENING ALLOWED.
  
 7B) ROOF TILE FOR SLOPED ROOFS, PLEASE INDICATE WHICH
 FASTENING SYSTEM SHALL BE USED.106.1.2 ADDITIONAL
 INFORMATION REQUIRED. MOMENT OF OVERTURNING, 1609.7.3
 RIGID TILE.
  
 7C) NO INFORMATION FOR FASTENING OF HIP BOARD OR HIP
 TILE. 1507.3.8 APPLICATION. TILE SHALL BE APPLIED
 ACCORDING TO THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS OR RECOMMENDATIONS OF THE FRSA/RTI
 07320/08-05 (FOURTH EDITION).
  
 8) A-6 NOR STRUCTURAL PLANS ARE MISSING THE NEW A/C
 CURBS, HOW THE WEIGHT WILL BE CARRIED ON THE BAR JOIST,
 WHERE THE POINT LOADING WILL NEED TO BE TAKEN IN AFFECT
 AND THE PANEL POINTS REINFORCED, NEW HEADERS SHAPE AND
 SIZE OF STEEL AND THE ACTUAL ATTACHMENT OF THE CURB TO
 THE ROOF SYSTEM.1609.6.1.1 MAIN WINDFORCE-RESISTING
 SYSTEMS.
  
 9) A-6 INDICATES THE USE OF ROOF DRAINS AND OVERFLOW
 DRAINS THERE IS NO INFORMATION PROVIDED, PLANS INDICATE
 A SECTION 4 SHEET D6 NOT PROVIDED.1503.4 ROOF
 DRAINAGE.
  
 UNLESS ROOFS ARE SLOPED TO DRAIN OVER ROOF EDGES,
 DESIGN AND INSTALLATION OF ROOF DRAINAGE SYSTEMS SHALL
 COMPLY WITH THE FLORIDA BUILDING CODE, PLUMBING ,
 CHAPTER 11 .
  
 10) NOTE PLANS DO NOT INDICATE COMPLIANCE WITH: 1503.6
 PROTECTION AGAINST DECAY AND TERMITES.
 CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR
 SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON
 ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 11) THE QUESTION WHY TOMMY TAVERAS P. E. NAME AND TITLE
 BLOCK INFORMATION IS ON THIS SHEET IF HE IS NOT THE
 DESIGNER OR ACONSULTING ENGINEER. 106.1.2* ADDITIONAL
 INFORMATION REQUIRED.
  
 12) SHEET S-1 SOUTH WALL OF STRUCTURE, THE PLAN
 INDICATES ON THE SOUTHWEST PORTION OF THE NEW CANOPY
 ROOFED AREA (2) 16"X16"BLOCK COLUMNS BUT THE FOOTER
 DESIGNATION IS STILL A SINGLE TYPE A FOOTER PLEASE
 VERIFY THIS IS CORRECT? 106.1.2* ADDITIONAL INFORMATION
 REQUIRED.
  
 13) SHEET S-1 NOTE # 2 INDICATES THERE IS A SHEET# 4
 WITH DETAILS FOR NEW MASONRY OPENINGS. 106.1.2*
 ADDITIONAL INFORMATION REQUIRED.
  
 14)SHEET S-2 DETAIL # 01 THE PLAN LACKS TO CLARIFY
 THE TYPE OF ANCHORS TO BE USED TO TIE THE W12 BEAM TO
 THE COLUMN TYPE A. 106.1.2*/ 1609.6.1.1.
  
 15) SHEET S2 ROOF PLAN NORTHEAST CORNER OF THE BUILDING
 THERE IS A SECTION OF TRUSSES C & D THAT DO NOT TIE TO
 THE SECTIONS, HOW ARE THEY ATTACHED, IS THIS AREA NEW
 OR EXISTING.
 106.1.2.
  
 16) SHEETS2 DETAIL 03 INDICATES HOW A COMMON TRUSS
 WILL BE CONFIGURED BUT FOR ALL OF THE JACKS THIS WILL
 NOT BE THE CONFIGURATION FOR THOSE TYPE OF TRUSSES
 THERE SHOULD BE SOME TYPE OF WALL CARRYING SYSTEM
 PLEASE DETAIL AND THE CONNECTIONS. 106.1.2/ 1609.6.1.1.
 MAIN FORCE RESISTING SYSTEM.
  
 17)SHEET S-3 UNDER DESIGN NOTES THE 2001 FBC IS
 REFERENCED AS WELL AS ASCE 7-98 BOTH REFERENCES WILL
 NEED TO BE UPDATED TO THE 2004 FBC W/ 2007 WIND
 REVISIONS AND THE ASCE 7-02.
  
 18) SHEET S-3 NOTES UNDER WIND LOAD DESIGN ALSO NEEDS
 TO REFLECT ASCE 7-02 UNDER THE 2004 FBC W/ 2007 WIND
 REVISIONS.
  
 19) SHEET S-3:
 19A)THEWINDOWSSCHEDULE IS BLANK, THERE IS NO
 INFORMATION AS TO INTERIOR ZONES OR END ZONES, PLANS
 INDICATE COASTAL EXPOSURE WITH A WALL HEIGTH OF 22'
 SEE
  
 TABLE 1609.6.2.1(4) FOR ADJUSTMENT FACTORS OF
 1.35 .
 19B)THE DOOR SCHEDULE NEEDS TO IDENTIFY THE PRESSURES
 FOR INTERIOR ZONES AS WELL AS END ZONES.
 19C)IDENTIFY THE END ZONES OF THE BUILDING FOR WALLS
 ZONE# 5.
 19D)THE DOOR SCHEDULE INDICATES OPENING D-1 AS 12'-4
 X 7'-9" THIS TYPE CONFIGURATION OR OPENING SIZE IS USED
 FOR AUTOMATIC SLIDING DOORS, THE PLAN INDICATES THE USE
 OF
 SWING DOORS WITH SIDE LITES REQUIRING
 STRUCTURAL MULLIONS AND THE CONTRIBUTING AREA FOR THE
 MULLION WOULD BE MUCH SMALLER.
 19E)PLANS ALSO DO NOT INDICATE ROOF ZONES AND OR
 PRESSURES PLEASE PROVIDE INFORMATION FOR ZONES 1, 2 AND
 3.
 19F)BUILDING HEIGHT NOT PROVIDED IN THE WIND
 INFORMATION1603.1.4.
  
 20)S-3 FOUNDATION NOTES REQUIRES A SOILS REPORT FOR
 THE MINIMUM SAFE BEARING VALUE.FBC 1802.2.1
 QUESTIONABLE SOILS, WHERE THE SAFE-SUSTAINING POWER OF
 THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL REQUIRE THAT THE NECESSARY
 INVESTIGATION BE MADE. SUCH INVESTIGATION SHALL COMPLY
 WITH THE PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6
 .
  
 21) SHEET A-2 ON THE WEST SIDE OF THE BUILDING THE
 PLANS INDICATE TO REMOVE 2'-0" OF SLAB, SHEET A-3
 INDICATES A NEW EXTERIOR MASONRY WALL, SHEET A-6
 INDICATES A NEW FLAT BUILT UP ROOF, BUT THE STRUCTURAL
 PLANS INDICATE THIS TO BE EXISTING, PLEASE CORRECT.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  