| Plan Review Notes For Permit 07070709 |
| Permit Number |
07070709 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-08-20 15:01:08 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FACFLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R | | | 301.2.1.2.IF SHUTTERS ARE PROPOSED, PROVIDE PRODUCT | | | APPROVALS AND COMPLETE THE ATTACHED INSTALLATION | | | SCHEDULE.IF SHUTTERS IN COMPLIANCE WITH FBC ARE | | | EXISTING, PROVIDE A PERMIT NUMBER. | | | | | | 2 . ON THE FLOOR PLAN, PROVIDE ROOM DESIGNATION FOR ALL | | | NEW WINDOWS.NOTE EXISTING CONDITIONS (TYPE OF WINDOW) | | | AND OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB 505.1. | | | NO SIZE WAS PROVIDED FOR THE WINDOW BETWEEN THE NEW | | | WINDOW AND DOOR ALONG "OUTSIDE WALL". | | | | | | 3.PROVIDE A SCHEDULE.WINDOW SIZES SHOULD BE | | | PROVIDED IN INCHES, WIDTH X HEIGHT.THE NUMBERING | | | SHOULD CORRELATE WITH ITEM 1 IF SHUTTERS ARE USED. |
|