Plan Review Notes
Plan Review Notes For Permit 07070693
Permit Number 07070693
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-08-10 00:09:42*****DENIED******
  
  
 1.PLEASE PROVIDE THE FOLLOWING INFORMATION:*
 OCCUPANCY TYPE (EXISTING AND NEW)* OCCUPANT LOAD*
 OCCUPANCY HAS A FIRE ALARM SYSTEM*OCUPANCY HAS A
 FIRE SPRINKLER SYSTEM
  
 2.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241
  
 4. THE REMOVAL AND/OR STOCKING OF BUILDING MATERIALS &
 SUPPLIES SHALL NOT INTERFERE OR HINDER EMERGENCY ACCESS
 RESPONSE TO THE SAID PROPERTY OR VICINITY THEREOF
 (INCLUDING STREETS, FIRE LANES, ETC).
  
 5.PROVIDE A SITE PLAN SHOWING TENANT SPACE LOCATION
 IN RELATION TO THIS 600 SOUTH ROSEMARY AVENUE
 BUILDING.
  
 6.THE COMPLETE ADDRESS INCLUDING THE SUITE NUMBER
 SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN
 SHEET.
  
 7.ON THE APPROPIATE EXTERIOR ELEVATION, SHOW THE
 LOCATION OF THE SUITE NUMBER OF THE PROJECT SITE.AS
 PER WEST PALM BEACH ADDRESSING CODE, THOSE NUMBERS
 SHALL BE NO LESS THAN 3" IN HEIGHT AND NO LESS THAN 1"
 IN HEIGHT.
  
 8.SPECIFY THE NEW INTERIOR FINISH MATERIAL FOR THE
 WALLS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 9.PROVIDE A LIFE SAFETY PLAN DETAILING THE LOCATION
 OF EXIT/EMERGENCY LIGHTS, FIRE EXTINGUISHER(S), AND
 TRAVEL DISTANCE TO THE EXIT.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722