| 2007-08-06 13:51:16 | |
| | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} THE ENGINEERING FIRM LISTED ON THE TITLE BLOCK SHALL |
| | INDICATE THE CERTIFICATE OF AUTHORIZATIONNUMBER ALONG |
| | WITH OTHER INFORMATION REQUIRED BY 61G15-23.002 |
| | FLORIDA ADMINISTRATIVE CODE. |
| | |
| | 2} A TITLE BLOCK PER 61G1-16-004 FAC MUST APPEAR ON THE |
| | PLANS SEALED BY THE ARCHITECT. |
| | |
| | 3} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR |
| | THE DEVICES BEING INSTALLED UNDER THIS PERMIT. |
| | |
| | 4} SUBMIT A PLAN FOR THE LIGHTING, INDICATE IF EXISING |
| | OR NEW,IF NEWINDICATE COMPLIANCE WITH CHAPTER 13 OF |
| | THE FLORIDA BLDG CODE. |
| | |
| | 5} PROVIDE EMERGENCY ILLUMINATION PER |
| | NFPA-101 7.8 (2003), AND CIRCUITED PER |
| | 700.12 NEC. INDICATE SAME ON PLANS. |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2005 |
| | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED |
| | PER WEST PALM BEACH, CHAPTER 1. |
| | |
| | FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN THE |
| | FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE INDICATE |
| | THE CODE CYCLES UNDER WHICH THIS PLAN WAS DESIGNED. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |